HomeMy WebLinkAboutM03-0011 PLANSWATER HEATER SCHEDULE
STOR. CAP. RECOVERY WATER INPUT MANUFACTURER &
MARK TYPE GALLONS G.P.H. EM(7) IS MBH KW MODEL NUMBER REMARKS
WH -1 GAS 50 28 80 40 - A.O. SMITH _
FSG -50
mm
BOILER SCHEDULE
HEATING CAPACITY MANUFACTURER*
MARK SERVICE TYPE INP T @ OUTPUT @ MODEL NUMBER REMARKS
SL MBH ALT. MBH
B -1 HEATING WATER CAST IRON 462 251.6 BURNHAM _
SERIES 8B 8088
I I
* 1. WEIL- MCLAIN.
PUMP SCHEDULE
MARK SERVICE TYPE GPM I TDH FLUID MOTOR MANUFACTURER * SUGT DISC REMARKS
(FT) HP RPM VOLT/PH MODEL NUMBER
P -1 HEATING WATER INUNE 10 15 30% GLYCOL 1/2 1725 120/1 TACO 1 1 Y4" OPERATE IN PARALLEL
P -2 HEATING WATER INLINE 10 15 30% GLYCOL 1/2 1725 120/1 TOACO 1 Y4" l Y4" OPERATE IN PARALLEL
* B&G OR AURORA EQUIVALENT
EXHAUST FAN SCHEDULE
FAN MOTOR MANUFACTURER &
MARK TYPE S P.0 S S.P.0 ALT. VOLTAGE/ MODEL NO. ACCESSORIES REMARKS
CFM IN W.C. IN W.G. HP /WATT PHASE
EF -1 EXHAUST 6000 1.25 .92 5 230/3 COOK SQN -B 245 BACKDRAFT DAMPER PROVIDE HOA MAG. STARTER
EF -2 1 BATHROOM 225 1 .23 .17 t 1/6 115/1 i COOK SQN -B 60 BACKDRAFT DAMPER -
UNIT, CABINET HEATER SCHEDULE
HEATING COIL MANUFACTURER
MARK TYPE CFM HP/WATT GPM P.D.(FT.) T.MBH EWT ('F) & MODEL NO. REMARKS
CUH -1 HOT WATER 125 60 W 1.0 3.8 13.8 180 TRANE UNIT MOUNTED THERMOSTAT
FFBB020 -1
u
A
GRILLE, REGISTER, DIFFUSER, & LOUSIER SCHEDULE
SYMBOL
USE
PATTERN
ACCESSORIES
FINISH
MANUFACTURER &*
REMARKS
LAT
('F)
ESP@
WATER P.D.
(FT W'C')
GPM
ROWS
MODEL NO.
REMARKS
0
OUTSIDE AIR
INTAKE &
FIXED
-
ALUMINUM
LOUVERS & DAMPERS
WITH BIRDSCREEN & FLANGE
BUILDING DURING PERIODS THE BUILDINGS HEATING PLANT IS NOT
EXHAUST
( IN W.C.
INW.C.
EL -27
CONDITIONS (70') FOR OCCUPANTS DURING WORKING HOURS AND
AIR VENT
S SUPPLY
FIXED
OBD
MITE
TITUS
-
1000
AIR
60
95
.13
TDC
0.04
�--�
L /
RETURN
FIXED
-
WHITE
TITUS
_
COTG
AIR
Ea"
THERMOMETER
PAR
ON
DOWN
RETURN
35'
-
ALUMINUM
TITUS
_
HOT
WATER
R
1700
47.2
60
350 FL
.36
" GRD EQUIVALENT. KRUEGER, METALLAIRE, HART & COOLEY, ANEMOSTAT
LOUVER EQUIVALENT: PENN, DOWCO, RUSKIN
DUCT HEATING COIL (HYDRONIC)
MARK
SERVICE
TYPE
COIL
DIMENSIONS
CFM
MBH
EAT
(-F)
LAT
('F)
ESP@
WATER P.D.
(FT W'C')
GPM
ROWS
MANUFACTURER &*
MODEL NUMBER
REMARKS
A
S
FLEXIBLE CONNECTOR
7.
CONTRACTOR SHALL PROVIDE TEMPORARY HEAT FOR THE.COMPLETE
AFG
ABOVE FINISHED GRADE
BUILDING DURING PERIODS THE BUILDINGS HEATING PLANT IS NOT
SAFETY RELIEF VALVE
( IN W.C.
INW.C.
BELOW FINISHED GRADE
CONDITIONS (70') FOR OCCUPANTS DURING WORKING HOURS AND
AIR VENT
MAINTAIN (55') DURING NON - WORKING HOURS. _
DC -1
OPEN OFFICE
AREA &
HOT
WATER
18x12
1000
27.8
60
95
.13
.18
0.04
3.5
2
DL T RA NE
COIL
PRESSURE GAUGE W/ PIG TAIL do COCK
OFFICE #8
COTG
CLEAN OUT TO GRADE
Ea"
THERMOMETER
ON
DOWN
(`JT
THERMOSTAT
DC -2
SOUTH
OFFICES
HOT
WATER
22x12
1700
47.2
60
95
.36
.49
0.14
5.5
2
TRANE
DL COIL
-
DC -3
OFFICES
WATER
18x12
1325
36.8
60
95
.22
.3
0.4
4.5
2
W TRANE
COIL
-
DC -4
NORTH
OFFICES
HOT
WATER
12x12
600
16.6
60
95
.09
.12
0.62
2.0
1
TRANE
ST COIL
-
DC -5
INTERIOR
AREAS
HOT
WATER
20x12
1400
38.9
60
95
.35
.48
0.09
4.5
2
TRANE
DL COIL
-
* CARRIER, EQUIVALENT
MECHANICAL LEGEND
CONTRACTOR SHALL REVIEW ASBESTOS REPORT AND PRQVID
NOTE. ALL SY S ARI S " pWN ON
ARE NOT N USED.
INN
6.
CONTRACTOR SHALL PROVIDE CONSTRUCTION PLAN THAT MINIMIZE
IMPACT OF BUILDING OPERATION DURING WORKING HOURS, DEMO &
•
CONSTRUCTION WITHIN OCCUPIED SPACES IS RESTRICTED TO NON-
AFF
ABOVE FINISHED FLOOR
-{SAD -
FLEXIBLE CONNECTOR
7.
CONTRACTOR SHALL PROVIDE TEMPORARY HEAT FOR THE.COMPLETE
AFG
ABOVE FINISHED GRADE
BUILDING DURING PERIODS THE BUILDINGS HEATING PLANT IS NOT
SAFETY RELIEF VALVE
OPERATIONAL, TEMPORARY HEATING SHALL PROVIDE COMFORTABLE
BFG
BELOW FINISHED GRADE
CONDITIONS (70') FOR OCCUPANTS DURING WORKING HOURS AND
AIR VENT
MAINTAIN (55') DURING NON - WORKING HOURS. _
CFM
CUBIC FEET PER MINUTE
�-
PRESSURE -TEMP. TAP
CLG
CEILING
•
CONN
CONNECT
PRESSURE GAUGE W/ PIG TAIL do COCK
COTG
CLEAN OUT TO GRADE
Ea"
THERMOMETER
ON
DOWN
(`JT
THERMOSTAT
(E)
EXISTING
0
HUMIDISTAT
EAT
ENTERING AIR TEMPERATURE
�I
HORIZONTAL CLFJWOUT
EXH
EXHAUST
EWT
ENTERING WATER TEMPERATURE
VERTICAL CLEANOUT
FBO
FURNISHED BY OWNER
Q
FLOOR DRAIN
LAT
LEAVING AIR TEMPERATURE
®
FLOOR SINK
LWT
LEAVING WATER TEMPERATURE
NIC
NOT IN CONTRACT
-- {o)
ROOF DRAIN
OBD
OPPOSED BLADE VOLUME DAMPER
(&F /S
FIRE /SMOKE DAMPER
OSA
OUTSIDE AIR
®
FIRE DAMPER
TYP.
TYPICAL
tp)
EXHAUST FAN ON ROOF Wf DUCT THRU ROOF.
LINO
UNLESS NOTED OTHERWISE
FA.
FIRE ALARM
- HWS -
HEATING WATER SUPPLY
- HWR -
HEATING WATER RETURN
STRAINER W/ BLOW -OFF VALVE
- CHS -
CHILLED WATER SUPPLY
-CHR-
CHILLED WATER RETURN
- CS -
CONDENSER SUPPLY
H
SHOCK ABSORBER
- CR -
CONDENSER RETURN
H 8
HOSE BIBB /WALL HYDRANT
- SMS -
SNOWMELT SUPPLY
- SMR -
SNOWMELT RETURN
_ RMS -
RADIANT MANIFOLD SUPPLY
FLOW SWITCH
- RMR -
RADIANT MANIFOLDE RETURN
G ---
NATURAL GAS
- D -
DRAIN PIPE
DUCT SMOKE DETECTOR
- GF -
GLYCOL FEED
- RS -
REFRIGERANT SUCTION
- RL -
REFRIGERANT LIQUID
TEMPERATURE CONTROLLER
- RD -
REFRIGERANT DISCHARGE
- - -
DOMESTIC COLD WATER
ACCESS PANEL
- RD -
REVERSE OSMOSIS WATER
-
SUPPLY DUCT DOWN
- -
DOMESTIC HOT WATER
RETURN /EXHAUST DUCT DOWN
-- -140'-
DOMESTIC HOT WATER ( TEMP. SHOWN)
I
TURNING VANES SHOWN IN 90 ELBOW.
- -
HOT WATER CIRCULATING
I i
- F
FIRE LINE
SBD
- PW-
PRESSURIZED WASTE
SINGLE BLADE DAMPER ( S.B.D.) MOTORIZED
-V-
PLUMBING VENT PIPE
-� -i
DAMPER, OPPOSED BLADE DAMPER ( O.B.D.)''
- W-
WASTE PIPE
- S-
SANITARY SEWER PIPE
-�
AIR EXTRACTOR
- ST --
STORM DRAIN PIPE
STORM DRAIN OVERFLOW PIPE
DUCT SIZES ARE OUTSIDE SHEET METAL
SHUT OFF VALVE (BALL. GATE, BUTTERFLY)
DIMENSIONS. 1ST NO. IS SIZE OF SURFACE
-}-
GLOBE VALVE
C,
SHOWN. 2ND NO. IS DUCT DEPTH.
o
CHECK VALVE
r�
SUPPLY REGISTER
Z
---
BALL VALVE
CFM
RETURN AIR OR EXHAUST AIR REGISTER.
---- -# --
PLUG OR BALANCING VALVE
SIZE
CIRCUIT SETTER VALVE
A
Al C FM
SUPPLY DIFFUSER; ARROWS INDICATE
- - ---
PLUG VALVE IN RISER
SIZE
DIRECTION OF THROW.
- ----
GATE OR GLOBE VALVE IN RISER
�SIZ
DRAIN VALVE W/ HOSE END
--}
DOOR GRILLE
TEMPERATURE CONTROL VALVE
SECTION THRU SUPPLY AIR DUCT.
-{(-
PRESSURE REDUCING VALVE
SECTION THRU OUTSIDE AIR INTAKE,
---- III- --
PIPE UNION
RETURN AIR OR EXHAUST DUCT.
A�
(A) SECTION GUT LETTER.
pqy .�4
BACKFLOW PREVENTER TYPE AS REQUIRED
VRT
(B) SHEET SHOWN ON.
BIDDING NOTES:
1. PROVIDE PRICE ALTERNATE FOR DIRECT DIGITAL CONTROL SYSTEM
ON THE AIR HANDLING SYSTEM.
2. PROVIDE PRICE ALTERNATE TO DEMO ALL RADIANT BASEBOARDS,
AND PATCH FLOORS & WALLS AS REQUIRED,..
3. PROVIDE PRICE ALTERNATE TO CLEAN & REUSE EXISTING CEILING
DIFFUSERS.
4. PROVIDE TEMPORARY HET BLDG.
AIR HANDLING UNIT SCHEDULE (HYDRONIC)
FAN COOLING COIL PREHEAT COIL
MARK SERVICE TYPE ESP ELEC EAT EAT LAT EAT LAT FILTER MANUFACTURER* REMARKS
CFM 0 ALT @ S.L. HP VOLT /PH db wb db GPM P.D. T.MBH S.MBH EWT ('F) ( ( GPM P.D.(FT) T.MBH EWT('F) WTD('F) & MODEL NO.
I N W. C.) 1N W. C.) ('F) ('F) ('F)
AHU -1 ENTIRE HYDRONIC 6500 1.85 1.36 5 208/3 79 59 60 1/2 - - 139.4 40 53 60 3.0 0.1 59 180 20 2" T.A. CARRIER PREMIER 12" MEDIA EVAP.
BUILDING 39LH12KA- JA- AGN -A9 COOLING MODULE
■
CONTRACTOR SHALL REVIEW ASBESTOS REPORT AND PRQVID
INN
6.
�1
5.
CONTRACTOR SHALL REVIEW ASBESTOS REPORT AND PRQVID
ADDITION CONTINUENCE (TIME & MONEY) FOR ASBESTOS ABATEMENT.
6.
CONTRACTOR SHALL PROVIDE CONSTRUCTION PLAN THAT MINIMIZE
IMPACT OF BUILDING OPERATION DURING WORKING HOURS, DEMO &
•
CONSTRUCTION WITHIN OCCUPIED SPACES IS RESTRICTED TO NON-
WORKING HOURS (NIGHTS & WEEKENDS).
7.
CONTRACTOR SHALL PROVIDE TEMPORARY HEAT FOR THE.COMPLETE
;..
BUILDING DURING PERIODS THE BUILDINGS HEATING PLANT IS NOT
5.
CONTRACTOR SHALL REVIEW ASBESTOS REPORT AND PRQVID
ADDITION CONTINUENCE (TIME & MONEY) FOR ASBESTOS ABATEMENT.
6.
CONTRACTOR SHALL PROVIDE CONSTRUCTION PLAN THAT MINIMIZE
IMPACT OF BUILDING OPERATION DURING WORKING HOURS, DEMO &
Ike
CONSTRUCTION WITHIN OCCUPIED SPACES IS RESTRICTED TO NON-
WORKING HOURS (NIGHTS & WEEKENDS).
7.
CONTRACTOR SHALL PROVIDE TEMPORARY HEAT FOR THE.COMPLETE
;..
BUILDING DURING PERIODS THE BUILDINGS HEATING PLANT IS NOT
OPERATIONAL, TEMPORARY HEATING SHALL PROVIDE COMFORTABLE
CONDITIONS (70') FOR OCCUPANTS DURING WORKING HOURS AND
um
MAINTAIN (55') DURING NON - WORKING HOURS. _
8.
PROVIDE PRICE ALTERNATE TO RELOCATE EXISTING MOP SINK, IN
mi
SHEET 1 OF 5
Ike
.I'
•
•
i
f
SEQUENCE OF CONTROL:
SEQUENCE OF CONTROLS
1. AHU -1: AIR HANDLING UNIT
A. GENERAL
1.
OA, RA & EA DAMPERS SHALL BE PROVIDED UNDER DIV. 15 SECTION.
EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS
ACTUATORS BY CONTROL CONTRACTOR
2.
THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE RETURN DAMPER
2.
SHALL OPEN WHENEVER THE SUPPLY FAN STOPS UNDER ANY CONDITION.
3.
MINIMUM POSITION OF OUTSIDE AIR DAMPER TO BE 1420 CFM AND
AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE
THE RETURN AIR DAMPER SHALL BE 5080 CFM.
B. CONTROLLER SHALL BE PROVIDED AND SHALL INCLUDE:
1.
OUTSIDE AIR TEMPERATURE SENSOR.
2.
FREEZESTAT FOR FCU WIRE AND PROVIDED BY CONTROL CONTRACTOR.
FREEZESTAT TO SHUT DOWN SUPPLY FAN AND ALLOW FULL FLOW THROUGH
THE CONSTRUCTION DOCUMENTS, DRAWING, AND DETAILS, AND SHALL
HEATING COIL IN FCU
3.
ROOM MOUNTED "DAY -NIGHT -AUTO" & "SUMMER /WINTER" FUNCTION
WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERAL
SWITCH
4.
IN THE "DAY" POSITION, THE UNIT PROVIDES A NORMAL DAY CYCLE
�--
OPERATION AT ALL TIMES. 24 HOURS A DAY. THE DAY PILOT WILL BE
CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL AND
ON.
5.
IN THE "NIGHT POSITION, THE NIGHT LIGHT WILL BE ON
"
CONTINUOUSLY, AND THE BUILDING WILL REMAIN ON NIGHT SETBACK 24
HOURS A DAY.
6.
IN THE WINTER MODE THE EVAP COOLER SECTION AND ECONOMIZER
WILL BE LOCKED OUT. THE 3 -WAY VALVE WILL MODULATE TO MAINTAIN
SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND
65?F (ADJ.) DISCHARGE AIR TEMPERATURE.
7.
IN THE SUMMER MODE THE EVAP COOLER SECTION AND ECONOMIZER
SECTION WILL BE ACTIVATED PER THE SEQUENCE BELOW.
8,
THE "AUTO" POSITION PROVIDES 24/7 AUTOMATIC OPERATION WITH
EXAMINATION OF BIDDING DOCUMENTS.
CHANGEOVER FROM NIGHT SETBACK TO DAY TEMPERATURES. IN THE "AUTO"
:>
POSITION, THE PILOT LIGHTS WILL INDICATE WHERE IN THE CYCLE THE
DESIGN PLUS ANY SPECIFIED OPTIONS.
UNIT IS OPERATING, AS FOLLOWS:
A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY,
'Mo) DAY CYCLE: THE SUPPLY FAN IS TO RUN CONTINUOUSLY.
b) NIGHT CYCLE: DURING THE NIGHT CYCLE THE SUPPLY FAN SHALL BE
3. BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT,
OFF. THE OUTSIDE AIR DAMPER SHALL BE CLOSED AND THE RETURN AIR
BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR
DAMPER SHALL BE OPEN. A ROOM SENSOR SHALL CYCLE FAN ON WIDE
DIFFERENTIAL TO MAINTAIN 60F (ADJ.) MINIMUM TEMPERATURE.
9.
EVAPORATOR CYCLE:
INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER, THE
l%e) ON A CALL FOR COOLING AND THE OUTSIDE AIR TEMPERATURE IS
<
ABOVE 60 (ADJ.), THE RETURN AIR DAMPER SHALL CLOSE AND THE
DESIGN.
OUTSIDE AIR DAMPER SHALL OPEN 100% AND EF -1 (RELIEF FAN) SHALL
ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY
ACTIVATE. ENABLE THE EVAPORATIVE COOLING MODULE PUMP,
10.
ECONOMIZER CYCLE
26. ALL MATERIALS AND /OR EQUIPMENT SHALL BE HANDLED AND
'Me) ON A CALL FOR COOLING AND THE OUTSIDE AIR TEMPERATURE IS
INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF
BELOW 60 (ADJ.), THE RETURN AIR DAMPER SHALL CLOSE AND THE
OUTSIDE AIR DAMPER SHALL OPEN. 3 -WAY HEATING VALVE SHALL MODULATE
RECOMMENDATIONS.
TO MAINTAIN 55F (ADJ.) DISCHARGE AIR TEMPERATURE.
11.
EVAPORATOR MODULE
lM6) PROVIDE AN AUTO -FILL AND DRAIN DOWN KIT ON UNIT BY MC.
27. SUBMIT ENTIRE HVAC AND PLUMBING SHOP DRAWING SUBMITTAL DATA
WIRED BY CONTROL CONTRACTOR
RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE
b) WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 45F (ADJ.) THE
BASIN SHALL AUTOMATICALLY DRAIN DOWN.
INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL
c) THE SYSTEM SHALL REFILL WHEN THE OUTSIDE AIR TEMPERATURE IS
DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED
ABOVE 60F (ADJ.).
11. B -1: BOILERS
A. ENABLE BOILERS AND CIRCULATION PUMPS UPON A CALL FOR HEAT
FROM ANY HEATING COIL AND /OR CABINET UNIT HEATER. MANUFACTURERS
CONTROL SYSTEM TO MAINTAIN A HEATING WATER SUPPLY TEMPERATURE
INVERSELY WITH OUTDOOR AIR TEMPERATURE ON THE FOLLOWING SCHEDULE:
OUTDOOR AIR TEMPERATURE WATER TEMPERATURE
0` 180'
60' 140'
Ill. P -1. P -2: HEATING WATER PUMPS
A. ENABLE PUMPS UPON A CALL FOR HEAT FROM A HEATING COIL AND /OR
CABINET UNIT HEATER.
IV. WH -1: WATER HEATER
A. AN AQUASTAT LOCATED IN THE TANK SHALL PROVIDE A SIGNAL TO
MODULATE THE GAS VALVE TO MAINTAIN 120F (ADJ) TANK
TEMPERATURE.
V. EF -1: RELIEF FAN
A. INTERLOCK TO RUN ONLY UPON CALL FOR COOLING WHEN THE
EVAPORATIVE COOLING MODULE IS OPERATING AND /OR THE ECONOMIZER
SYSTEM IS ACTIVATED.
VI. EF -2: BATHROOM EXHAUST FAN
A. EXHAUST FAN CONNECTED TO TIME CLOCK TO RUN DURING THE
OCCUPIED (DAY CYCLE) TIME ONLY. TIMECLOCK PROVIDED BY CONTROL
CONTRACTOR
VII. DC -1, DC -2, DC -3. DC -4, DC -5: HYDRONIC DUCT COILS
A. WALL MOUNTED SPACE THERMOSTATS SHALL OPEN THE TWO -WAY
HEATING WATER VALVE UPON A CALL FOR HEATING TO MAINTAIN SPACE SET
POINT. CONTROL VALVE & THERMOSTATS BY CONTROL CONTRACTOR
VIII. CUH -1: CABINET UNIT HEATER
A. A UNIT MOUNTED THERMOSTAT SHALL CYCLE THE HEATER FAN TO
MAINTAIN THE THERMOSTAT SETPOINT. FAN CYCLE SWITCH BY MC
GENERAL SPECIFICATIONS:
1.
DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO
25. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED
COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL
EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS
hi w
DIMENSIONS.
FOR THE LISTED EQUIPMENT SHALL BE ALLOWED IN THE BASE BID,
2.
IT SHALL BE ASSUMED THAT ALL SUBCONTRACTORS ARE EXPERIENCED
A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON
AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE
THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED
CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A RESPONSIBLE MANNER
ARE CONSIDERED GENERAL EQUIVALENTS ONLY.
IN ESTABLISHED CONSTRUCTION SEQUENCE. RECOGNIZING THE PRIORITY OF
THE CONSTRUCTION DOCUMENTS, DRAWING, AND DETAILS, AND SHALL
B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS:
LLJ
INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN DRAWINGS
WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERAL
ARE UNCLEAR OR INCONSISTENT.
EQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE
�--
00
CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL AND
3.
SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME
OTHER WORK.
"
CONTRACTOR OF DISCREPANCIES OR CONFLICTS ON THESE CONSTRUCTION
L,..1
DOCUMENTS FOUND DURING BIDDING AND /OR CONSTRUCTION PRIOR TO
1. PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR
PERFORMING THE WORK. SUCH DISCREPANCIES SHALL BE RECEIVED
SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND
EXPEDITIOUSLY AND NOTIFICATION GIVEN TO THE SUBCONTRACTOR EITHER
PROPERLY FITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF
VERBALLY OR IN WRITING AS APPLICABLE TO THE CONDITION.
DESIGN.
4.
EXAMINATION OF BIDDING DOCUMENTS.
2. PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF
:>
DESIGN PLUS ANY SPECIFIED OPTIONS.
A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY,
AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF
3. BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT,
�'"...
BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR
FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR
INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES,
SUBSTITUTIONS DO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL
INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER, THE
DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE
<
ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN
DESIGN.
ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY
0
ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON
26. ALL MATERIALS AND /OR EQUIPMENT SHALL BE HANDLED AND
INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF
INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND
DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT
RECOMMENDATIONS.
COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL
z
INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION
27. SUBMIT ENTIRE HVAC AND PLUMBING SHOP DRAWING SUBMITTAL DATA
RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE
AT ONE TIME. SUBMITTAL TO BE BOUND IN THREE -RING BINDERS,
OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR
INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL
DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED
NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED
ABOVE.
TO: EQUIPMENT, FIXTURES, INSULATION, DIFFUSERS, PUMPS, FANS,
PIPING, VALVES, BOILERS, CONTROLS, AND FIRE PROTECTION.
B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF
V)
ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE
28. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND /OR
CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE
EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE
CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE
ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND
SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS.
29. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH
EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN
5.
IN AS MUCH AS DESIGN FOR REMODEL AND /OR REHABILITATION
CONTINUITY, APPEARANCE OR FUNCTION,
REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING
CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE
30. PROVIDE 4" HIGH CONCRETE EQUIPMENT PADS BENEATH FLOOR
VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE
MOUNTED MECHANICAL EQUIPMENT, IN ADDITION TO ANY BASE ASSEMBLIES
PORTIONS OF THE BUILDING, THE ENGINEER CANNOT ASSURE THE OWNER OR
REQUIRED BY MANUFACTURER.
THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES HEREIN
ENCOMPASS ALL CONTINGENCIES, FIELD COORDINATION DURING
31. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS
CONSTRUCTION IS IMPERATIVE, MAKE REASONABLE ALLOWANCES FOR
AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING
UNSEEN CONDITIONS.
THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE
REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM -E-
6.
THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING
814. ACCEPTABLE MATERIALS INCLUDE: DOW CORNING RTV FIRE STOP
CONSTRUCTION, CONTINUED OPERATION OF THE FACILITY SHALL NOT BE
FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE
HINDERED BY THIS WORK, ACCOUNT FOR ALL ADDITIONAL COSTS WHICH
DAM 150 CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING
MAY BE INCURRED DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND
CONSTRUCTION GAPS; 3M CP -25 CAULK AND FS -195 INTUMESCENT STRIPS
EMPLOYEES, FURNITURE, EQUIPMENT, ETC.; AND DUE TO THE HOURS OF
FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICAL
THE DAY IN WHICH AN AREA MAY BE ACCESSIBLE WHEN COMPILING HIS
CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF
BID.
PENETRATION ENCOUNTERED.
7.
BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR
32. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL
DUCTWORK REMAINING TO BE CONNECTED TO NEW OR EXISTING SYSTEMS.
HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE
PROVIDE DUCTWORK, PIPING, CONTROLS, DIFFUSERS, ETC., AS REQUIRED
ARCHITECTURAL DRAWINGS. IN THE ABSENCE OF ANY OTHER
TO RESTORE CONTINUITY OF SYSTEM (S), OR TO MAKE NEW WORK MEET
REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS
EXISTING CONDITIONS, WHETHER INDICATED OR NOT,
IN BUILT -UP ROOFS, TALL CONE WITH EPDM BOOT FOR PIPE AND CONDUIT
IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL
8.
SUBCONTRACTOR SHALL VERIFY EXISTENCE AND LOCATION OF ALL
TYPES OF ROOF, INSTALLATION SHALL BE WATERTIGHT.
UTILITY SERVICES AND COORDINATE AS REQUIRED BY EITHER RESPECTIVE
AREA OF THE CONSTRUCTION INDUSTRY. NOTIFYING THE PRIME
33. COORDINATE MECHANICAL, FIRE PROTECTION AND ELECTRICAL
CONTRACTOR OF VARIATIONS OR CONFLICTS.
DRAWINGS PRIOR TO INSTALLATION.
9.
IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS,
34. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE
MATERIALS AND /OR EQUIPMENT SHALL BE IDENTIFIED BY THE
AVAILABLE.
SUBCONTRACTOR WITHIN A REASONABLE TIME TO ALLOW SELECTION,
PURCHASE, AND DELIVERY SO AS TO PREVENT DELAY ON THE JOB
35. MOUNT ALL STATS AT 4'6" A.F.F. COORDINATE LOCATION WITH
SCHEDULE.
WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT
SOURCES, AND EXTERIOR WALLS. NOTIFY ENGINEER OF ANY CONFLICTS
10.
PROVIDE MECHANICAL DEMOLITION REQUIRED. VISIT SITE PRIOR TO
PRIOR TO BEGINNING THERMOSTATS AT INSTALLATION.
BID TO DETERMINE EXTENT OF WORK INVOLVED. EXISTING FIXTURES,
MECHANICAL EQUIPMENT, ETC., BEING REMOVED SHALL BE RETURNED TO
36. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED
THE OWNER, DISPOSE OF ALL REMOVED PIPING, DUCTWORK, ETC. UNLESS
BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN
NOTED OTHERWISE. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED,
ACCORDANCE WITH NEBB OR AABC GUIDELINES FOR PROPORTIONAL BALANCE,
ARE SHOWN HATCHED, UNLESS OTHERWISE NOTED.
SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW
PRIOR TO BALANCING. MEASUREMENTS SHALL INCLUDE ALL MOTOR
11.
VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND
AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC
UTILITIES, PIPING, AND RACEWAY SYSTEMS PRIOR TO THE TRENCHING.
PRESSURE AT INLET AND OUTLET OF ALL PACKAGED EQUIPMENT, FANS,
CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS
COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST,
AND REQUIREMENTS.
RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM OUTSIDE AIR, AND
100% (ECONOMIZER) OUTSIDE AIR; VELOCITY DISTRIBUTION ACROSS THE
12.
ALL DUCTWORK, DIFFUSERS, PIPING, FIXTURES, AND EQUIPMENT
FACE OF FILTERS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOW
SHOWN IN LIGHT LINE WEIGHT IS EXISTING, NEW INDICATED BY HEAVIER
MEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH
LINE WEIGHT, EXCEPT WHERE NOTED. PIPES, DUCTWORK, EQUIPMENT,
FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE
ETC. TO BE REMOVED, ARE SHOWN HATCHED.
DROP, AND PRESSURE DROP AT ALL COILS.
13.
OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE
A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO
STRUCTURE, BEAMS, COLUMNS, AND EXISTING EQUIPMENT.
ADJUST FAN SPEED.
14.
ALL EXISTING SUPPORT RODS AND STRAPS NOW SUPPORTING DUCTS,
B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE ROOM
PIPES, AIR TUBING, ELECTRICAL CONDUIT, ETC. THAT ARE REMOVED TO
AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN
ALLOW ROOM FOR INSTALLATION OF NEW EQUIPMENT SHALL BE RELOCATED
BY A DIFFERENTIAL OF SUPPLY AND EXHAUST /RETURN OR BY NOTE, ADJUST
AND REINSTALLED, OR REPLACED IF DAMAGED.
SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST /RETURN TO PROVIDE
THE INDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN
15.
ALL "CAPPED" SANITARY AND VENT LINES SHALL BE RECONNECTED OR
90% INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER.
RE- ROUTED AS NECESSARY TO PREVENT "DEAD -ENDS" IN THE PIPING. ALL
SUBMITTAL OF BALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT
PIPING SHALL DRAIN TO ACTIVE SANITARY WASTE LINES AND ALL
EXPLANATION IS CAUSE FOR REJECTION OF REPORT.
BRANCHES WITH TRAPS SHALL BE ADEQUATELY VENTED.
C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY
16.
CAP ALL DEMOLISHED AND ABANDONED DUCT TAKE -OFFS AT TRUNK
REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL
DUCT.
BE RETAINED BY THE OWNER, ARCHITECT, AND ENGINEER.
17.
WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE
37. DUCTWORK: (LOW VELOCITY)
SATISFACTION OF THE ARCHITECT,
A. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS
18.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS /HER
CLOTH, 10" W.C. RATED. -
WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND
LIFE SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR NATIONAL
B. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR
AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF
5 GORE ELBOWS. "SNAP - LOCK ", LONGITUDINAL SEAM DUCT, OR
MODIFICATION OF HIS /HER WORK IS REQUIRED FOR COMPLIANCE.
ADJUSTABLE FITTINGS ARE ACCEPTABLE ON INDIVIDUAL GRILLE /DIFFUSER
RUNOUTS ONLY.
19.
ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR
EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE 1997
C. LINER: _
BUILDING, MECHANICAL, PLUMBING, FIRE AND 1999 NATIONAL ELECTRICAL
CODES, NFPA, AND ALL LOCAL ORDINANCES AND AMENDMENTS AND
1. LINE ALL SUPPLY AND OUTSIDE AIR, RETURN AIR DUCTS, EXHAUST
MANUFACTURER'S INSTALLATION RECOMMENDATIONS. IF A CONFLICT
AIR RISERS, AND MAKE UP AIR RISERS WITH 1 ", 1.5 PCF, BLACK MATTE
BETWEEN THOSE PUBLICATIONS EXIST, THE MOST STRINGENT REQUIREMENT
COATED INSULATING DUCT LINER.
SHALL APPLY.
2. MATERIAL SHALL MEET ALL REQUIREMENTS OF NFPA -90.
20.
PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS.
PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES
3. INSTALL WITH ADHESIVE AND PINS IN ACCORDANCE WITH SMACNA
OF COMPLETION. __ ,.
"HVAC DUCT CONSTRUCTION - STANDARDS ".
21.
GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND
4. EXTERNALLY LINE ALL ROUND - SUPPLY AIR DUCTS WITH FLEXIBLE
LABOR WHICH MAY OCCUR UNDER NORMAL USAGE. THE GUARANTY SHALL BE
GLASS FIBER, ANSI /ASTM C612; 0._002 INCH FOIL SCRIM FACING.
FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL
BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
D. DUCTWORK: GALVANIZED SHEETSTEEL; LOCK FORMING QUALITY;
CONSTRUCTED TO THE LATEST EDITION OF SMACNA "HVAC DUCT
22.
PROVIDE RECORD DRAWINGS TO THE ENGINEER. DRAWINGS SHALL
CONSTRUCTION STANDARDS "; +/- 1" W.C. PRESSURE CLASSIFICATION,
INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS,
SEAL CLASS "C "; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES,
REROUTINGS, ETC.
STRAPS, ETC.
23.
SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR
E. SEAL ALL SEAMS (LONGITUDINAL - AND TRANSVERSE) AIRTIGHT WITH
CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY OWNER.
UNITED MCGILL "UNI -GRIP" UL LISTED, WATER BASED, NON- HARDENING,
.. _,
ELASTIC SEALANT OR EQUIVALENT.
24.
SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A
_ ,_._ ....._..
MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE
38. PROVIDE Y4" GALVANIZED MESH SCREEN I ON: ALL COMBUSTION AIR
DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO
DUCTS OR OPENINGS, AND ALL OPEN AND RETURN AND EXHAUST DUCTS.
ADDITIONAL COST TO OWNER.
39. ALL DUCTWORK DIMENSIONS ARE OUTSIDE SHEET METAL DIMENSIONS.
DUCT LINER HAS BEEN ACCOUNTED FOR.
40. DUCTWORK NOTES:
A. DIFFUSER NECK SIZES IS SAME AS FLEXIBLE DUCT SIZE.
B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE
MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5
DUCT WIDTH.
1. WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT
ELBOWS WITH SINGLE WIDTH (NON - AIRFOIL) TURNING VANES,
2. FOR DUCT DEPTHS OF 36" OR LESS, PROVIDE MANUFACTURED SINGLE
WIDTH (NON - AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE
WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR "STANDARD SPACING ",
USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36 .
USE NO TRAILING EDGES.
C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED EIGHT FEET IN LENGTH,
FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT
POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASS
INSULATION, HIGH - STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN
REINFORCED "RIP STOP" ALUMINUM LAMINATE INTERIOR CORE, UL LISTED
AND LABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POS.
_. 6 ", NEC. 4 ". FLEXMASTER TYPE - 5 OR EQUIVALENT. SUBMIT SAMPLES TO
DETERMINE EQUIVALENCE.
41. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR
CLAMPS. NO PIPE TAPE ALLOWED, ALL HANGERS SHALL BE SIZED FOR OD
OF INSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET
METAL SHIELDS FOR PIPING 1 -1/2" AND LESS. PROVIDE CALCIUM
SILICATE INSULATION INSERTS FOR ALL INSULATED PIPING 2" AND
LARGER. MAINTAIN VAPOR BARRIER ON ALL COLD LINES, ISOLATE BARE
COPPER LINES FROM HANGERS WITH VIBRASORB OR EQUIVALENT, COPPER
COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT
ACCEPTABLE.
42. COPPER PIPE VALVES AND SPECIALTIES
A. GATE VALVES:
B. BALL VALVES: BRONZE, CLASS 125, 600 LB. W.O.G.
C. CHECK VALVES: BRONZE, CLASS 125, 200 LB, W.O.G.
D. BALANCING VALVES: 125 PSI W.P. FOR 250 DEGREE FARENHEIGHT
SERVICE TIGHT SHUTOFF, TOUR AND ANDERSON STA, ARMSTRONG CBV,
GERAND, OR FLOWSET, BELL AND GOSSETT CIRCUIT SETTER.
E. DIRECT UNIONS: FURNISH AND INSTALL A DIELECTRIC UNION AT
ALL CONNECTIONS WHERE NONFERROUS MATERIALS IS IN CONTACT WITH
FERROUS MATERIALS.
43, GAS PIPING- SCHEDULE 40 BLACK STEEL PIPE, 150 LB, MALLEABLE
IRON SCREWED FITTINGS ON ABOVE GROUND PIPE, WELDED FITTINGS WITH
ALL PIPING COATED AND WRAPPED ON BURIED PIPE.
44. GAS VALVES - NON - LUBRICATED BALLSTYLE VALVE WITH RESILIENT
SEATS, AND ADJUSTABLE GLAND PACKING NUT, AGA AND UL LISTED FOR
NATURAL GAS SERVICE,
45. FILL HEATING WATER SYSTEM WITH 30% PROPYLENE GLYCOL /WATER
SOLUTION.
46. GRADE AND VALVE ALL HEATING AND CHILLED WATER PIPING WITH
3/4" HOSE END VALVES TO PERMIT COMPLETE DRAINAGE OF THE SYSTEM.
VENT ALL HIGH POINTS IN EQUIPMENT ROOMS AS NECESSARY WITH
AUTOMATIC AIR VENTS PIPED TO CONVENIENT DRAIN. ALL HIGH POINTS
IN SYSTEM OUTSIDE OF EQUIPMENT ROOMS WITH COMBINATION
AUTOMATIC /MANUAL AIR VENTS AS REQUIRED TO RELIEVE AIR IN THE
SYSTEM.
47. PROVIDE PLASTIC GROMMETS ON ALL HEATING WATER PIPING PASSING
THROUGH WOOD JOISTS AND STUDS.
48. MATERIALS; HYDRONIC PIPING
A. ABOVE GRADE, UP THROUGH 2 -1/2 ": SCHEDULE 40 STEEL PIPE WITH
MALLEABLE IRON THREADED FITTINGS, OR TYPE "L" COPPER TUBE WITH
WROUGHT COPPER FITTINGS AND 95 -5 NO LEAD SOLDER.
B. ABOVE GRADE, 3" AND LARGER: SCHEDULE 40 STEEL PIPE WITH
CAST IRON OR STEEL WELDING FITTINGS.
49. DRAIN PAN PIPING -NOT BURIED -TYPE "M" COPPER, WROUGHT COPPER
FITTINGS, AND 95 -5 SOLDER; BURIED -TYPE L" COPPER WROUGHT COPPER
FITTINGS, AND 95 -5 SOLDER.
50. SUPPORT EACH AIR HANDLING UNIT AND FAN BY MASON INDUSTRIES
OR EQUIVALENT SPRING TYPE VIBRATION ISOLATORS.
51. INSULATE ALL NEW HEATING WATER AND DOMESTIC HOT WATER RE-
CIRCULATION WITH U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER,
SNAP -ON, PIPE INSULATION. INSULATE FITTINGS WITH GLASS FIBER
BLANKET INSULATION AND PREMQLDED P.V.C. COVERS. ALL MATERIALS
SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME
SPREAD RATING OF 25 OR LESS. INSULATION SHALL PASS UNINTERRUPTED
THROUGH HANGERS. VAPOR SHALL BE CONTINUOUS, AND SEALED
WITH "NON - BREATHING" MASTIC ON COLD PIPING. ALL RAW EDGES OF
INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC.
A. INSULATION THICKNESS:
1. HEATING WATER: ALL SIZES 1" RUNOUTS WITHIN 20 FEET OF
TERMINAL UNIT - 1/2
52. EQUIPMENT LABELS: LABEL ALL NEW PIPING AND EQUIPMENT.
PROVIDE FULL BAND -OR STRIP TYPE MARKERS AND -FLOW ARROWS ON
PIPING. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER
AND ATTACH WITH STANDARD CHAIN OR S- HOOKS. PROVIDE ENGRAVED
PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT.
ffffm
no
1� /l
r�
now
,
m
�
€v
a
0)
�
0 -
c
hi w
-0
p
ci s
o
LLJ
�--
00
""..
ul
"
c
L,..1
t.
0
:>
-«
�'"...
>
0
Ld
<
C
0
J
0
z
La ZE
w=- c)
w W
r
w
w
V)
NOTES:
1. NBWQ.A. DUCTWORK TO BE ROUTED BELOW
HARD CEILING AND Q
COORDINATE ROUTING AS REQUIRED. U.N.O.
2. ALL S.A. DIFFUSERS TO BE TYPEtB>'
3. EXISTING EXHAUST [AN ABOVE FRONT DESK AREA
T0 BE ABANDONED IN PLACE.
4. EXISTING S.A. DUCTWORK ABOVE HARD/LOWERED
CEILING TO BE ABANDONED IN PLACE,
5. DOOR BY NEW R.A. GRILLE TO BE RELOCATED AS SHOWN,
6. ALL PENETRATION TO WALL 8cHARD CEILING ASSEMBLIES
SHALL BE COORDINATED WITH ASBESTOS ABATEMENT
CONTRACTOR.
7. CONTRACTOR SHALL CLEAN & REFURBISH ALL EXISTING
R.A. DUCTWORK THAT IS REUSED.
— — —
'
'
—
--
NEW CHASE 11GHT T0 WALL T0l�8���
TO EXISTING WALL RNBN,
-
�
SHEET M4,
��K��������U���kU K������ PLAN
��K�������U�U����K� �������
SCALE: 1/4" = V-07
?EWAIKL
VE HARD
ICT CONTINUES
NOT SHOWN FOR
,
REMAIN.
Lij
LA
mo
TACO 433 ---- --
AIR SCOOP.
EXPANSION TANK. -
_ 1 Ys"
1 •
HOSE END VALVE. FILL SYSTEM
} WITH 30% PROPYLENE GLYCOL/
WATER SOLUTION.
HWS ---- AIR VENT AT ALL HIGH
3 POINTS, TYPICAL.
z
TO SYSTEM. ----
} 1 �„
(7 o HWR
, 1 i- —HWS
UP " C T TO )ROOF CAP. __.-
BOTH TO REMAIN.
r
�
(E) EXPANSION TANK - /
-'
TO REMAIN.
REFER TO DIAGRAM O , THIS
SHEET FOR DOMESTIC WATER
HEATER DIAGRAM.
& MAN FACTURER'S s
RECOMMENDED
BASE,
BOILER PIPING DIAGRAM
NO SCALE
REFER TO DIAGRAM THIS
SHEET FOR BOILER PIPING.
(E) 2W G
EXISTING WATER
ENTRY.
X X
WIN
SUPPORT
FROM FLOOR.
�7
¢ 03
x
Q n
EYAP-1
J f f -
L- I - - - - -i I -- -j
I i
(E) 22x12 R.A. DUCT ABO'
NEW SA DUCT TO REMAIN.
HOT WATER-'
TO FIXTURES.
GAS SUPPLY
a
♦
O ak ,
r
EXPANSION TANK
AMTROL ST -12
DOMESTIC WATER HEATER DIAGRAM
NO SCALE (GAS)
(E) COMBUSTION AIR LOUVER &
DAMPER TO REMAIN.
-REFER TO DIAGRAM Q , THIS
SHEET FOR LOUVER DIAGRAM.
-- (E) O.A. INTAKE TO BE DEMO'D
PENETRATION TO BE WIDENED
ACCORDINGLY TO ACCOMMODATE
NEW LOUVER.
FLEX DUCT CONNECTION
20 "x20 "x24" HIGH --�
SHEET METAL BOX
(NO INSULATION).
NOT USED
\ `--WORM DRIVE S.S. CLAMP
— CEILING DIFFUSER
CEILING DIFFUSER
}
HWR- ----�
HWS -
PIPING DIAGRAM
NO SCALE
(E) MOP SINK TO REMAIN.
CONNECT (E) R.A. DUCT TO
NEW R.A. PLENUM.
'`-- -- (E) RA GRILLE TO BE DEMO'D.
PROVIDE
WATERPROOFING
ON BOTTOM
& SIDES.
12" MIN
1-
LINTELS
LOUVER & SCREEN.
COIL. ----- --
AIR VENT. ----
PRESS. -TEMP 'LAP
TYPICAL
NOTE:
PIPE COIL FOR COUNTERFLOW.
ZONE HEATING
COIL ASS Y DIAGRAM
NO SCALE
RETURN SHEET METAL
UNDER WALL BOX &
EXTEND 2" BEYOND FACE
OF WALL TO DRIP LIP.
-SEE ENLARGEMENT "A"
` k
NOTE: ENLARGEMENT A
REFER TO MANUFACTURER'S INSTRUCTIONS
NOTES:
MECHANICAL ROOM PLAN
—
SCALE: 1/4 - l' -O "
1. CONNECT NEW BOILER, ,@=, &
WATER HEATER, M-1 TO
EXISTING FLUE & GAS CONNECTION
AS REQUIRED.
2. NEW EXHAUST FAN EF -1 TO BE
SUPPORTED FROM STRUCTURE WITH
VIBRATION ISOLATION.
3. SMOKE DETECTOR TO BE INSTALLED
IN SUPPLY AIR DUCT IN MECHANICAL
ROOM,
DEMO NOTES:
1. (E) AIR HANDLING UNIT TO BE DEMO'D.
2. ALL (E) DUCTWORK IN MECH. ROOM TO
BE DEMO'D EXCEPT FOR (E) RETURN AJR
DUCT FROM FRONT AREA OF BUILDING.
3. ABANDONED (E) EXPANSION TANK HANGING
OVER (E) BOILER TO BE DEMO'D.
4. (E) BOILER & (E) ASSOCIATED PIPING IN
MECH ROOM TO BE DEMO'D.
5. (E) WATER HEATER TO BE DEMO'D. ASSOCIATED
DOMESTIC WATER PIPING TO BE CONNECTED
TO NEW WATER HEATER, MU-1
FOR SPECIFIC MOUNTING DETAILS. NO SCALE
COOR'D WITH ARCITECTURAL
REQUIRMENTS.
WATERTIGHT INTAKE DUCT CONNECTION DIAGRAM ,�-
NO SCALE ( I )
MANUAL VOLUME
DAMPER, TYP.
TURNING VANES.
AIR F
D
15'
LOUVER.
GROUT.-
e •- r
AIR FLOW j
SHEET METAL NOSING FOR
LINED DUCT.
W O
NOTE:
D =W x Al
D = W - D
COLD WATER SUPPLY.
WATER HEATER.
b
A ~
OR 0
THIS PORTION OF —
DUCTWORK SHALL BE
ALUMINUM.
MASTIC.
WEEPHOLES
20 GA.
ALUMINUM.
Z [Sys BMWs
1 �4 OF "W" OR
6 MINIMUM.
45' i
END
J BEARING
f �
SINGLE BLADE
DAMPER IF H <8"
OPPOSED BLADE
DAMPER IF H > =8"
SEAL AIRTIGHT
AROUND ENTIRE
TAKE -OFF.
45° DUCT TAKE- -
OFF DIAGRAM
NO SCALE
USE DUCT SEALANT OR
GASKETED FITTING ON
HIGH VELOCITY DUCT.
CONICAL SPIN -IN FITTING W/
MANUAL DAMPER,
HANDLE, & LOCK NUT.
FLEX DUCT.
w
a `
¢ T
M 4
SHEET 'i OF 1
nnr0`_ rrun - A n
`° —WORM DRIVE S.S.
CLAMP.
NOTE:
DIAGRAM FOR LOW
& HIGH VELOCITY
DUCTWORK EXCEPT
UPSTREAM OF
VAV BOXES. OMIT DAMPER UPSTREAM
OF VAV BOXES.
ROUND
DUCT
TAKE -OFF DIAGRAM
NO SCALE
0
M 4
SHEET 'i OF 1