HomeMy WebLinkAboutTOV Smoke Control Submittal Review Letter 082509 � �. � _ � ,, � � ' '�,
� .. . � � . � - : .
. . . . ... :�� .
- . - � �-
Email: brian.thompson(c�q.com
August 21, 2009 VIA HAND DELIVERY
Mr. Martin Haeberle
Chief Building Official
Town of Vail
75 South Frontage Road
Vail, CO 81657
Mr. Mike McGee
Deputy Chief
Vail Fire Department
42 W. Meadow Drive
Vail, CO 81657
Re: Solaris DigitallysignedbyMichaelMcGee
Smoke Control System Submittal M i c h a e I DN:cn=Michael McGee,o=Vail Fire
Val�, C� &EmergencyServices,ou=Deputy
Chief,email=mmcgee@vailgov.com,
Schirmer Project No.: 2408014 McGee �=us
Date:2009.09.03 15:3623-06'00'
Dear Martin and Mike,
This is to document my review and approval, as the Smoke Control System Rational Analysis
Engineer of Record, of the enclosed Solaris Smoke Control System submittal. This submittal
consists of the drawings and documents identified on the attached Submittal List.
I would like to address what is not being included in this submittal to establish a level of
understanding about the Smoke Control System as a whole. The following is a list of items and
explanation for exclusion from this submittal:
1. Smoke Control Rational Analysis (SCRA)—The SCRA, dated October 31, 2008, was
submitted and approved by the Town of Vail. Stamped and signed copies should be
retained by the Building Department and the Fire Department. Those copies should be
referenced for consistency with this Smoke Control System submittal.
2. Fire Alarm System —The Fire Alarm System shop drawings (FA sheets) and applicable
manufacturer product data was submitted by Johnson Controls Incorporated and
approved by the Vail Fire Department on June 1, 2009. BCER is the Engineer of Record
for this Fire Alarm System. This approved Fire Alarm System submittal should be
referenced when reviewing this Smoke Control System submittal. As-built Fire Alarm
System drawings will be provided to the Vail Fire Department upon installation
completion.
Flre�rotection �ngineering ■ Code Gonsulting ■ Alternate Means&Methods ■ Performance 13asecl Design
S�laris -2- August 21,2009
5rnoke C�nfrol System Subrrri�taf
3. Automatic Sprinkler System—The Automatic Sprinkler System sh�p drawir�gs and
appiicable manufa�turer pradu�t data�ra� s�bmitted by Frontier Fire Protection and
approved by th��laiE Fire D�partment an Nov�mber 25, 2008. �CER is the Engineer of
Record for this Automatic Sprinkle�System. This approved Autornatic Sprinkler submittaf
should be ref�rer�ced for fiow svaitch info�rr�ati�n when re�i�;wing thi�Smoke Contrc�l
Syst�m submittal. As-built drawings Auto►natic Sprinkler System drawings wiEl be
provided tm the 0/ai! Fir� CDep�rter�en� upon ir�st�liation completion.
4. Architectur�i, Mechanica! and E6�ctrical drawings enclosed in this Smake Cantrol
System s�bmittal have ncst been stamped and sign�d by th� associated Engineer of
Ftecord as th�y are copie� of the sarne drawings that have bee� or avil! be submitted to
Town of Vail as part of the �uilding Departm�nt��brreittal package.
My review of the enclosed Smoke Gontrol System subcmittal alc�r�g�vith the Fire Alarm System
�nd Au4omatic�prir�kEer Systerv�wr�s bas�d or� accuracy with the Smok� G�ntrol Rational
Analysis as we91 as coordination and consistency amo�gst the �or�struetien documer�ts and
contractor submittals. You should be aware that numer�u� revisior��wer� rraade to the Srrrake
Control Systern submittai docurr�ents as a resuit of my previous r�views prior t�this final version
being subrnifited to you today.
I feel very confident that this Smoke �ontrol System subm►ttal is in compliance with tl�e
approved Srnoke Control Rational Analy�is. Pfease firad my professior�al engineer stamp and
signature befow signifying my approval of this submittai as fihe Sm�ke Controi Ration�f Analysis
Engineer of Rec�rd. I iook forward to receiving respon�e documenting y��or review.
Please do not hesitate to contacf ine if clarifcation of the subrrrittal or its cont�nt is necessary.
Sincerely,
�PQD �IC�
,.....,���a/�,
,•'�.T
i ia• �p`"
.
fi .,.....-
♦
.� 32264 �c
� :
�o�..e/,z� o�►.��,�
FsS��NA����\�
Brian Thompson, P.E.
President
C: Dan Feen�y, Solaris via emaii: d�n.feenev�so0arisvail.com
C: Mark Rochho9z, �chirmer E�gineering via erraaii: Mark RochholzCcaschirmereng.com
C: Jim Buckner, Davis Pa�#nership �ia em�il: 3bucknerCc�davispartner.com
G: Mike\laughan, Fire Marshal,V�il Fire Department via Hand �eiivery
� � � _. �. _ ry � . . �u ,�v
� .. . � � . � - : .
. . . . ... :�� .
- . - � �-
Solaris — Smoke Control
Submittal Package for Town of Vail
August 21, 2009
Number of Copies
1. TOV Building Department
2. TOV Fire Department
3. Smoke Control Engineer of Record —
Thompson LifeSafety Consulting
4. Solaris Property Ownership
Submittal List
1. Smoke Control System Rational Analysis Engineer of Record Review Letter
2. Applicable Smoke Control System Drawings
a. Architectural
i. A2.01: Garage Level Plan Overall
ii. A2.02: Garage Level Enlarged Plan —Area #1 (Door ST-1 Garage Level)
iii. A2.03: Garage Level Enlarged Plan —Area #2 (Door ST-2 Garage Level)
iv. A2.04: Garage Level Enlarged Plan —Area #3 (Doors ST-3 & ST-4
Garage Level and BMS Owner Work Station Location in Room G017—
Wall Partition Types Identified)
v. A2.05: Garage Level Enlarged Plan —Area #4 [Door ST-5 Garage Level
and BMS Owner Work Station (OWS) Location in Room G017 — Room
Door Type and Wall Partition Types Identified]
vi. A2.07: Level 1 Plan — Overall
vii. A2.08: Level 1 Enlarged Plan —Area #1 (Door ST-1 Level 1)
viii. A2.09: Level 1 Enlarged Plan —Area #2 (Door ST-2 & ST-6 Level 1)
ix. A2.10: Level 1 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 1)
x. A2.11: Level 1 Enlarged Plan —Area #4 (Door ST-5 Level 1)
xi. A2.13: Level 2 Plan — Overall
xii. A2.14: Level 2 Enlarged Plan —Area #1 (Door ST-1 Level 2)
xiii. A2.15: Level 2 Enlarged Plan —Area #2 (Doors ST-2 & ST-6 Level 2)
xiv. A2.16: Level 2 En�arged Plan —Area #3 (Doors ST-3 & ST-4 Level 2)
xv. A2.17: Level 2 Enlarged Plan —Area #4 [Door ST-5 and BMS Network
Automation System (NAE — 2) Location in Room Telecom 224A— Room
Door Type and Wall Partition Types Identified]
xvi. A2.19: Level 3 Plan — Overall
xvii. A2.20: Level 3 Enlarged Plan —Area #1 (Door ST-1 Level 3)
xviii. A2.21: Level 3 Enlarged Plan —Area #2 (Doors ST-2 & ST-6 Level 3)
xix. A2.22: Level 3 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 3)
xx. A2.23: Level 3 Enlarged Plan —Area #4 (Doors ST-5 Level 3)
xxi. A2.24: Level 4 Plan — Overall
xxii. A2.25: Level 4 Enlarged Plan —Area #1 (Door ST-1 Level 4)
Fire Protection Engineering ■ Code Consulting ■ Al4ernate Means&Methods ■ Performance Based Design
2
Solaris Smoke Control System
TOV Submittal Package
xxiii. A2.26: Level 4 Enlarged Plan —Area #2 [Doors ST-2 & ST-6 Level 4 and
BMS Stair No. 1 Control Panel (CP-402) Location in Room Elec 423—
Door Type and Wall Partition Types Identified]
xxiv. A2.27: Level 4 Enlarged Plan -Area #3 (Doors ST-3 & ST-4 Level 4)
xxv. A2.28: Level 4 Enlarged Plan —Area #4 (Doors ST-5 Level 4)
xxvi. A2.29: Level 5 Plan — Overall
xxvii. A2.30: Level 5 Enlarged Plan —Area #2 (Doors ST-2 & ST-6 Level 5)
xxviii. A2.31: Level 5 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 5)
xxix. A2.32: Level 5 Enlarged Plan —Area #4 (Doors ST-5 Level 5)
xxx. A2.33: Level 6 Plan — Overall
xxxi. A2.34: Level 6 Enlarged Plan —Area #2 [Doors ST-2 & ST-6 Level 6 and
BMS Stair No. 6 Control Panel (CP-601) Location in Room Elec 623—
Door Type and Wall Partition Types Identified]
xxxii. A2.35: Level 6 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 6)
xxxiii. A2.36: Level 6 Enlarged Plan —Area #4 (Doors ST-5 Level 6)
xxxiv. A2.37: Level 7 Plan - Overall
xxxv. A2.38: Level 7 Enlarged Plan —Area #2 [Door ST-2 Level 7 and BMS
Stair No. 2 Control Panel (CP-702) Location in Room Elec 722 — Door
Type and Wall Partition Types Identified]
xxxvi. A2.39: Level 7 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 7)
xxxvii. A2.40: Level 7 Enlarged Plan —Area #4 (Door ST-5 Level 7 and BMS
Stair No. 5 Control Panel (CP-703) Location in Room Elec 727— Door
Type and Wall Partition Types Identified]
xxxviii. A2.41: Level 8 Plan - Overall
xxxix. A2.42: Level 8 Enlarged Plan —Area #2 [BMS Stair No. 3 Control Panel
(CP-804) and Elevator No. 4 Control Panel (CP-802) Location in Room
Elec 821 — Door Type Wall Partition Types Identified]
xl. A2.43: Level 8 Enlarged Plan —Area #3 (Doors ST-3 & ST-4 Level 8)
xli. A2.44: Level 8 Enlarged Plan —Area #4 [BMS Stair No. 4 Control Panel
(CP-805) and Elevator No. 5 Control Panel (CP-803) Location in Room
Elec 824 — Door Type and Wall Partition Types Identified]
xlii. A2.45: Level 9 Plan — Overall
xliii. A2.47: Overall Roof Plan
xliv. A5.04: Vertical Circulation Elevators 4 & 5
xlv. A5.05: Vertical Circulation Stair 1
xlvi. A5.05A: Stair 1 — Mechanical Loft
xlvii. A5.06: Vertical Circulation Stair 2
xlviii. A5.06A: Vertical Circulation Stair 2
xlix. A5.07: Vertical Circulation Stair 3
I. A5.07A: Vertical Circulation Stair 3
li. A5.08: Vertical Circulation Stair 4
lii. A5.08A: Vertical Circulation Stair 4
liii. A5.09: Vertical Circulation Stair 5
liv. A5.09A: Vertical Circulation Stair 5
Iv. A5.09B: Stair 5 Pressurization Shaft
Ivi. A5.10: Vertical Circulation Stair 6
Ivii. A5.10A: Stair 6 Mechanical Loft
Iviii. A13.01: Interior Partition Types with UL listing and fire rating identified
lix. A14.01: Door Types
8/25/2009
3
Solaris Smoke Control System
TOV Submittal Package
b. Vertical Circulation (Elevator) by Lerch Bates
i. VT05: Plans and Hoistway Section Elevators 4 & 5
c. Mechanical
i. M0.01 Mechanical Legend and Abbreviations
ii. M0.03 Mechanical Equipment Schedules — Fan Schedule
iii. M0.04 Mechanical Equipment Schedules —Air Outlets and Inlets
iv. M2.24 Mechanical Condo Level 4 Plan Orientation
v. M2.25 Mechanical Condo Level 4 Enlarged Plan —Area #1 (ST-1 Level 4
injection point)
vi. M2.26 Mechanical Condo Level 4 Enlarged Plan —Area #2 (ST-2 and ST-
6 Level 4 Injection Points)
vii. M2.27 Mechanical Condo Level 4 Enlarged Plan —Area #3 (ST-3 and ST-
4 Level 4 Injection Points)
viii. M2.29 Mechanical Condo Level 5 Plan Orientation
ix. M2.30 Mechanical Condo Level 5 Enlarged Plan —Area #2 (ST-2 and ST-
6 Level 5 Injection Points)
x. M2.31 Mechanical Condo Level 5 Enlarged Plan —Area #3 (ST-3 and ST-
4 Level 5 Injection Points)
xi. M2.33 Mechanical Condo Level 6 Plan Orientation
xii. M2.34 Mechanical Condo Level 6 Enlarged Plan —Area #2 (ST-2 and ST-
6 Level 6 Injection Points)
xiii. M2.35 Mechanical Condo Level 6 Enlarged Plan —Area #3 (ST-3 and ST-
4 Level 6 Injection Points)
xiv. M2.37 Mechanical Condo Level 7 Plan Orientation
xv. M2.38 Mechanical Condo Level 7 Enlarged Plan —Area #2 (ST-2 Level 7
Injection Point and ST-6 Stair Pressurization Fan and Outside Air Damper
@ Inlet)
xvi. M2.39 Mechanical Condo Level 7 Enlarged Plan —Area #3 (ST-3 and ST-
4 Level 7 Injection Points)
xvii. M2.40 Mechanical Condo Level 7 Enlarged Plan —Area #4 (ST-5 Level 7
Injection Point)
xviii. M2.41 Mechanical Condo Level 8 Plan Orientation
xix. M2.42 Mechanical Condo Level 8 Enlarged Plan —Area #2 (ST-2 Stair
Pressurization Fan and Outside Air Damper @ Inlet)
xx. M2.43 Mechanical Condo Level 8 Enlarged Plan —Area #3 (ST-3 and ST-
4 Pressurization Duct)
xxi. M2.44 Mechanical Condo Level 8 Enlarged Plan —Area #4 (ST-5 Stair
Pressurization Fan)
xxii. M2.45 Mechanical Condo Level 9 Plan Orientation
xxiii. M2.46 Mechanical Condo Level 9 Enlarged Plan —Area #3 (ST-3 and ST-
4 Pressurization Fans and Outside Air Damper @ Inlet) (E-4 and E-5
Pressurization Fans and Outside Air Damper @ Inlet)
xxiv. M2.47 Mechanical Roof Plan Orientation
xxv. M5.03 Mechanical Air Riser Diagram
xxvi. M6.01 Solaris Controls
xxvii. M6.06 Solaris Controls Elevator Hoistway Pressurization
xxviii. M6.07 Solaris Controls Stairway Pressurization
xxix. M6.08 Solaris Controls Stairway Pressurization
8/25/2009
4
Solaris Smoke Control System
TOV Submittal Package
i. M6.09 Solaris Controls Stairway Pressurization
d. Electrical
i. E0.04: Electrical Panel Schedules (Emergency Generator Schedule
showing Smoke Control Pressurization Fans on the schedule)
e. Building Automation and Fire Alarm by Johnson Controls Incorporated
i. Cover Sheet
ii. 0000-0.00 Title Page
iii. 0000-1.00 Building Automation Drawing Index
iv. 0000-2.00 Abbreviations and Legend
v. 2000-1.00 BAS Smoke Control One Line
vi. 2000-1.01 NAE-2 Bacnet MSTP Riser Diagram
vii. 2000-2.00 NAE-2 Control Panel
viii. 3000-1.00 Garage Level Overall Smoke Control Plan
ix. 3000-2.00 First Level Overall Smoke Control Plan
x. 3000-3.00 Second Level Overall Smoke Control Plan
xi. 3000-4.00 Third Level Overall Smoke Control Plan
xii. 3000-5.00 Fourth Level Overall Smoke Control Plan
xiii. 3000-6.00 Fifth Level Overall Smoke Control Plan
xiv. 3000-7.00 Sixth Level Overall Smoke Control Plan
xv. 3000-8.00 Seventh Level Overall Smoke Control Plan
xvi. 3000-9.00 Eighth Level Overall Smoke Control Plan
xvii. 3000-10.00 Ninth Level Overall Smoke Control Plan
xviii. 9002-1.00 Elevator Pressurization One-Line Diagrams
xix. 9002-2.00 Elevator EPF-4 Control Panel CP-802
xx. 9002-2.01 Elevator Pressurization EPF-4 Point Schedule
xxi. 9002-3.00 Elevator Pressurization EPF-5 Control Panel (CP-803)
xxii. 9002-3.01 Elevator Pressurization EPF-5 Point Schedule
xxiii. 9002-4.00 Elevator Shaft Temperature Monitoring Panel (CP-303)
xxiv. 9002-4.01 Elevator Shaft Temperature Point Schedule
xxv. 9003-1.00 Stairwell 1 & 2 Pressurization One-Line Diagrams
xxvi. 9003-2.00 Stairwell 1 Pressurization Control Panel (CP-402)
xxvii. 9003-2.01 Stairwell 1 Pressurization Point Schedule
xxviii. 9003-2.02 Stairwell 1 Pressurization Point Schedule Continued
xxix. 9003-3.00 Stairwell 2 Pressurization Control Panel (CP-702)
xxx. 9003-3.01 Stairwell 2 Pressurization Point Schedule
xxxi. 9004-1.00 Stairwell 3 & 4 Pressurization One-Line Diagrams
xxxii. 9004-2.00 Stairwell 3 Pressurization Control Panel (CP-804)
xxxiii. 9004-2.01 Stairwell 3 Pressurization Point Schedule
xxxiv. 9004-3.00 Stairwell 4 Pressurization Control Panel (CP-805)
xxxv. 9004-3.01 Stairwell 4 Pressurization Point Schedule
xxxvi. 9005-1.00 Stairwell 5 & 6 Pressurization One-Line Diagrams
xxxvii. 9005-2.00 Stairwell 5 Pressurization Control Panel (CP-703)
xxxviii. 9005-2.01 Stairwell 5 Pressurization Point Schedule
xxxix. 9005-3.00 Stairwell 6 Pressurization Control Panel (CP-601)
xl. 9005-3.01 Stairwell 6 Pressurization Point Schedule
xli. Title Page and Fire Alarm Drawing Index
xlii. SC-00 Panel Layout Smoke Control System
8/25/2009
5
Solaris Smoke Control System
TOV Submittal Package
xliii. SC-01 Stair 1 Pressurization
xliv. SC-02 Stair 2 Pressurization
xlv. SC-03 Stair 3 Pressurization
xlvi. SC-04 Stair 4 Pressurization
xlvii. SC-05 Stair 5 Pressurization
xlviii. SC-06 Stair 6 Pressurization
xlix. SC-07 Elevator 4 Pressurization
I. SC-08 Elevator 5 Pressurization
li. SC-09 "Not Used"
lii. SC-10 Smoke Control System Card Wiring Details and Schedules
liii. SC-11 Voice Command Center Fire Alarm System
liv. SC-12 Field Device Installation and Wiring Details
Iv. SC-13 Smoke Control Sequence of Operation Matrix 1 of 4
Ivi. SC-14 Smoke Control Sequence of Operation Matrix 2 of 4
Ivii. SC-15 Smoke Control Sequence of Operation Matrix 3 of 4
Iviii. SC-16 Smoke Control Sequence of Operation Matrix 4 of 4
3. Applicable Smoke Control System Door Schedule and Manufacturer Product Data
a. Architectural
i. Door Schedule
ii. Door Closer Manufacturer Product Data
b. Mechanical
i. Outside Air Damper/ Hoistway Vent Damper Manufacturer Product Data
ii. Stair Injection Point Damper Manufacturer Data
iii. Pressurization Fans & Fan Curves Manufacturer Product Data
iv. Variable Frequency Drive Manufacturer Product Data
c. Automatic Sprinkler System
i. Flow Switch Manufacturer Product Data
d. Building Automation and Fire Alarm by Johnson Controls Incorporated
i. Air Pressure Sensing Switch AFS-222 (Confirmation of Airflow)
Manufacturer Product Data
ii. Enclosures Manufacturer Product Data
iii. DC Power Supply (DCP-1.5W) Manufacturer Product Data
iv. Differential Pressure Transducer (DPT 264) Manufacturer Product Data
v. Air Pressure Sensor Plate (RPS) Manufacturer Product Data
vi. Field Equipment Controller (FEC) Manufacturer Product Data
vii. Network Automation Engine (NAE) Manufacturer Product Data
viii. Input/Output Module (IOM) Manufacturer Product Data
ix. Control Panel Enclosure Manufacturer Product Data
x. Power Supply Manufacturer Product Data
xi. Elevator Temperature Sensor Manufacturer Product Data
xii. Elevator Temperature LCD Panel Manufacturer Product Data
xiii. Control Air Tubing Manufacturer Product Data
xiv. Wiring Conduit Manufacturer Product Data
xv. Firefighter Smoke Control Panel (FSCP) Manufacturer (Kirkland) Product
Data
8/25/2009
6
Solaris Smoke Control System
TOV Submittal Package
1. Panel Product Data
2. Panel Ordering Information
3. Panel Specification
4. Panel Driver Diagrams
5. Panel Cabinet Data
xvi. Auxiliary Power Supply (APS2-6R) Manufacturer Product Data
xvii. Lamp Driver Module Manufacturer Product Data
xviii. Control Module and Relay Module Manufacturer Product Data
xix. Monitor Module Manufacturer Product Data
xx. Enclosed Relay Manufacturer Product Data
xxi. Smoke Control Station (SCS) Manufacturer Product Data
8/25/2009