HomeMy WebLinkAboutSolaris Fire Pump Acceptance Test Report ire um est
e ort
Solaris
141 East Meadow Dr.
Vail, CO 81657
1/19/2010
Conducted by:
Fred Zacherl
Firepump Sales & Services, Inc.
P.O. Box 44362
Denver, CO 80201
Phone: 303.460.8734 Fax: 303.459.2100
fred@firepumpsalesandservices.com
FIRE PUMP TEST REPORT
Solaris
Company
ID: Frontier
Name: Frontier Fire Protection, Inc.
Address: 2617 West Holden Place
City/St/Zip: Denver, CO 80204-3348
Contact Name: Kenneth Koslowski
Title: Superintendent
Dept: Construction
Phone: 303-629-0221 Ext:
Fax: 303-623-7830 Cell:
Location
ID: Solaris
Name: Solaris
Address: 141 East Meadow Dr.
City/St/Zip: Vail, CO 81657
Pump
ID: FP-0080924
Manufacturer: Patterson Pump Co Label: UL/FM
Model Number: 6x5x17 SSC
Serial Number: FP-0080924
Pump Type: Horizontal RPM: 1775
Rating - Churn: 0 gpm @ 113 psi
100%: 1,000 gpm @ 85 psi
150%: 1,500 gpm @ 60 psi
Elevations -
Pump: ft Discharge Gauge: 1 ft Suction Gauge: 1 ft
Diameters -
Impeller: 15.5 in Discharge Pipe: 6 in Suction Pipe: 8 in
Rotation: Counterclockwise Max. Discharge Pressure: 250 psi
Driver Type: Electric
Brake Horsepower
Brake Horsepower: 75.00
Maximum BHP: 74.80 at Positive Suction Pressure: 137 psi
Electric Driver
Manufacturer: Weg Electric Motors Corp Label: UL
Model Number: OODD375
Serial Number: 18ABR08 1001185540
Horsepower: 75 RPM: 1780 AMP: 85.3
Volts: 460 Service Factor: 1.15 Frame: 365 TS
Fire Pump Evaluation Program 2002 Page 2 Fred Zacherl
FIRE PUMP TEST REPORT
Solaris
Pump Controller
Manufacturer: Metron Inc Label: UL/FM
Model Number: MP435-75-480C MTS
Serial Number: NA-08N38847-21
Jockey Pump
Manufacturer: Grundfos Pump Co Label: UL
Model Number: CR1-10 A-FGJ-A-E-HQQE
Serial Number: A96082127-P10833016
Horsepower: 1.00 RPM: 3466 Flow: 10 gpm
Pressure: 87 psi Suction Diam: 1.25 in Discharge Diam: 1.25 in
Jockev Pump Controller
Manufacturer: Metron Inc Label: UL
Model Number: M15AL-1-480
Serial Number: HK-08N38847-11
Relief Valve(s)
Manufacturer Size Pressure
Pump Casing - Aqualtrol 0.75 in 190 psi
Transfer Switch
Serial Number: NA-08N38847-21
Model Number: MTS 150
Manufacturer: Metron Inc
Emergency power Source: Onsite Standby Generator
Transfer Time: 3 secs
Location: Part of Fire Pump Controller
Pump Notes
This fire pump feeds a systems with a PRV ahead of dry valves, and also
directly to stand pipes.
Test
ID: 20100119
Date: 1/19/2010 Start: End:
Method: Devices with hose Discharge Device: Playpipes
Suction Pressure Location: Suction Flange
Discharge Pressure Location: Discharge Flange
Fire Pump Evaluation Program 2002 Page 3 Fred Zacherl
FIRE PUMP TEST REPORT
Solaris
Flows
Disch Suct Amperes Volts Net Corrected %
# Press Press Flow RPM A B C A-B B-C A-C Press Flow Press Flow
1 213.0 101.0 0 1,794 22.0 20.0 30.0 480.0 478.0 478.0 112.0 0 110.0 0
2 194.0 96.0 1,012 1,784 58.0 56.0 79.0 478.0 476.0 475.0 98.0 1,007 97.0 101
3 164.0 90.0 1,541 1,782 66.0 62.0 88.0 477.0 476.0 474.0 74.0 1,535 73.0 154
Tester s
Name License State
Fred Zacherl Patterson Pump Rep CO
Authority Havinq Jurisdiction
Name: Michael J. McGee
Title: Deputy Chief
Company: Town of Vail
Phone: 970-479-2135 Ext:
Fax: 970-479-2176 Cell:
E-mail: mmcgee@vailgov.com
Witness(es�
Name: Michael J. McGee
Company: Town of Vail
Phone: 970-479-2135 Fax: 970-479-9217
E-mail: mmcgee@vailgov.com
Name: Steve Martin
Company: Frontier Fire Protection
Phone: 303-629-0221 Fax: 303-623-7830
E-mail: smartin@frontierfireprotection.com
Temperatures
Pump Bearing - Inner: 84 °F Outer: 85 °F
Driver Bearing - Inner: 72 °F Outer: 74 °F
Transfer Switch
Transfer Time to Full Speed under Peak Load: 22 secs.
Retransfer Time under No Load: 11 secs
Gauges & Meters
Type Calibration Date
Pressure Gauges: Cecomp 9/16/2009
Volt Meter: Fluke 337 9/16/2009
Amp Probe: Fluke 337 9/16/2009
Tachometer: Extech 9/16/2009
Fire Pump Evaluation Program 2002 Page 4 Fred Zacherl
FIRE PUMP TEST REPORT
Solaris
Test Notes
This fire pump test consisted of three test runs of the fire pump: The first was with
flow out the test header for discharge to street drain, the results from this portion
are what are used in this report for flow data. The second portion the test was with
flow through the flow meter, this load was used to test the transfer of power to and
from the generator. The times in this report are from that portion of the test. The
third portion of the test was also with the use of the flow meter and was to confirm
the operation of the motor current draw of the pump. That test indicated that the
Amps displayed by the fire pump controller are within the error allowed by the
manufacture. This motor does appear to have a "lead leg" that draws more current
then the other two; however when measured in portion three of the test it was within
the limits of NFPA-20. At not time during any portion of the tests does it appear the
the motor became over loaded.
The pitot pressures a used for flow through the PRV and during the set up and
testing of that valve are: 35 and 31 psi, equaling 1044 gpm.
Flow Points
Flow Point# 2 Flow Point# 3
Noz Size Coef Pitot Flow Noz Size Coef Pitot Flow
# inch psi gpm # inch psi gpm
1 1.750 0.995 32.0 514 1 1.750 0.995 33.0 522
2 1.750 0.995 30.0 498 2 1.750 0.995 34.0 530
3 1.750 0.995 0.0 0 3 1.750 0.995 29.0 489
4 1.750 0.995 0.0 0 4 1.750 0.995 0.0 0
5 1.750 0.995 0.0 0 5 1.750 0.995 0.0 0
6 1.750 0.995 0.0 0 6 1.750 0.995 0.0 0
7 1.750 0.995 0.0 0 7 1.750 0.995 0.0 0
8 1.750 0.995 0.0 0 8 1.750 0.995 0.0 0
Fire Pump Evaluation Program 2002 Page 5 Fred Zacherl
Solaris - 1/19/2010
FP-0080924
120
t Flow Test Data O Fire Pump Nameplate Data
110
100
90
O
80
70
.N
n
�
� 60 O
�
�
�
a`
50
40
30
20
10
0
0 200 400 600 800 1000 1200 1400 1600
Flow(gpm)
Patterson Pump Company
Serial No: FY-0080924-001 Sold To: FRONTIER F1RE PROT. Job: 206702
Pu�np Type:6X5X17SSC Test Driver:W}�,STINGHOUSE (��� GPM:1000
Imp Pattern:C-10892 HI':150 • FM Ft. Head:196
Imp Dia:l 5.5 Effi�'/o:0_924 Rated RPM:1775
Vane Tips:.l 25 Test RPM:1780 Test Num:l
No. Stages:l Test Type:Performance Test I�ate:Aug-20-2008
Certified By_ A� Approved By:_��f�„ / Witnessed By:_
�� �-�fy�G�
� �
10Q 500 - Eff. % Ft. Head _ BHP NPSH ll,
�
90 450 225
-- � r0
�
80 400 ;'��)0
7�? - 350 — '
6t� 300
� � �
o �
° 50 = 250 - _ - .�
� �
�i � -
�
40 200 ^�"��_.:
30 150 y _ -
� J
20 100 - °�`i ; ,
1Q 50 -
� �
0 0 i , �-
0 250 500 750 1000 1250 1500 1750 2000
GPM
PATTERSON PUMP COMPANY
ORDER 1NFORMATInN PUMP DATA RATING (Design)
Customer: FRONTTER F1RE PROT. Pump Size&Type: 6XSX17SSC GPM: 1000
5erial No: FP-0080924-001 lrnpeller Pattern: C-10892 FT HD: 196
Job: 206702 lmpeller Diameter: I5.500 RPM(N2): 1775
Vane Tips: .I?5
Stages: 1
TEST INFORMATiON TEST DRiVER INFORMATION SI;CONDARY RATINGS
Positive Pressure Test HP: ]50 GPM: 1,500.00, 0.00
Venturi Meter: 6" RPM: 1780 FT HD: 127.40, 0.00
Vei�turi Constant: 108.01 Manufacturer: WGS"I'INGHOUSE
Discharge Dia: 5.00 Serial No.: 474f3859G09 Data Collected by: AL
Suction Dia: 6.00 Volts: 4(0 Test Date : Aug-20-2008
Discharge Guage Elev.(Id): 0.00 Amps: 177 Test No.: 1
Suction Guage Elev. (7_,$): 0.00 S.F.: I.I S
Pressure Ga: 300PSI Eff.(.00j: 0.924
Panel No.: 1
WaterTemp
Test Data Calculated Data �� CalculaCed Data at Rated Speed
No Pd(PSI)� Ps(PSl) kW Nl h���H2o) Ql (GPM) � Hl (F� whp ehp bhpl npump ' Q2(GPM) � Ei2(FT) bhp2
] 127.0 I 1.70 I 23.00 1,796.00' 0.00 0.00 266.34 0.00 i 30.83 2$.49 0.00 0.00 260.15 27.50
2� 121.0 1120 44.80 1,794.00 22.50 512.34 254.20 ' 32.89'', 60.05 55.491i 59.27 �i; I 506.91 248.85 53J5
3� 1 I t.5 10.�0+ 52.80 1,792.00 54.50� 797.37 234.4� 47.21 70.78 65.401 72.18 789.81 I 230.02 63.5�I
� 102.5 ]0.]0� 57.40 1,79].00 86.00 1,001.64 215.60 54.53 76.94 7l.10 76.71 i 992.70 21].77 II 69.2]
5 95.5 9.70 59.60 1,791.00 110.00 I 1,132.82 200.96 57.49 I!� 79.89 I 73.82 77.87 1,122.70 197.39I� 71.86 !
6i 88A 9.30 61.20 I 1,791.00 Ii4.50 i 1,252.64 P 1g5•17 5 7 82.04 75.80 , 1241.45 181.88 73.79
i
7 68.5 7.90 62.00 1,791.00 I93.00 1,500.52 144.83 54.88 ' 83.11 76J9 71.46 �,: i 1,487.12' 142.26 74.7� I
8� 57.SOI- 8.00_, 62.00 1,791.00 223.00 '� 1,612.93 . 119.95 48.85I 83.11-- 76.79, 63.62 �I 1,598_SZII - 117.81 _7�
Comments:
ULlFM RATING 75��.
To��RANCES PAT �ERSON PUMp COMPANY �"K°. sca�E o�wc. No.
��xc�Pr �,s .�ur�o> rocco,�, cFOFCiA A.L.B, 7/i9/78 FULL
PJO. ECN DATF BY _ � _ �� �� � �
DECIMAL � ��� Q- 1_ I APPRVD. CAI E
' A.P. 6-28- /8
FFZACTIONAL � � � � � � MAT. bRAWN PATT. N0.
. �J�, ��� �.� �I A,����,��� F �T �
_ PURCFLL
ANGULAk PART N0. R�F. JOB PJG.
' ; 23001014
_ ��
� D ,
F M I , �� ;
A SU6S1�)IAKY U� THE GORMA��-R�PF CG. �
TOCCO�,GEJRGIA `��
CENTR'FUGAI FIRE_ I'UMP S SP�IT CASF
�IZE-TYPE N0. STGS. SERIAL N0.
6X5X17 SSC �1 ! FP-0080924 �
RATE� B.�I.F. 75 MAX.B.H.P. 7L�.8 MAX. SUCT. il �3� P.S.I.
'.50 CAN.
G.P.M. R.P.M. PSIG MAX. I-'�IG P��G I��P. DIA..
, �_ 1 00 0 1775 �i 85 113 � 60 �, C5.50���-
MADE I� U.S.A.
i
f
:
I �
A d l�arn�n-Rupplaonlpry
HYDROSTATIC�YRE TEST REPORT '
Sena� Number �L ������
Pump Model �i X��`� 5�C
Test Pressure(PSq 3�`>� I
Test Duration(MiN.) ��
Test Liquid Water, Temperature ranging from 50 t0 70 degrees F
. Test Facility C3�'�Small Pump Assy Gauge S!N 216619-63
0 Large Pump Assy Gauge S!N
❑ Ofher Gauge S/N
Test Results � PASS ❑ FAIL
COMMENTS: �
. Tested By: i� � Date: � � O�
Witnessed By: L�f N/A Date: