Loading...
HomeMy WebLinkAboutSolaris Fire Pump Acceptance Test Report ire um est e ort Solaris 141 East Meadow Dr. Vail, CO 81657 1/19/2010 Conducted by: Fred Zacherl Firepump Sales & Services, Inc. P.O. Box 44362 Denver, CO 80201 Phone: 303.460.8734 Fax: 303.459.2100 fred@firepumpsalesandservices.com FIRE PUMP TEST REPORT Solaris Company ID: Frontier Name: Frontier Fire Protection, Inc. Address: 2617 West Holden Place City/St/Zip: Denver, CO 80204-3348 Contact Name: Kenneth Koslowski Title: Superintendent Dept: Construction Phone: 303-629-0221 Ext: Fax: 303-623-7830 Cell: Location ID: Solaris Name: Solaris Address: 141 East Meadow Dr. City/St/Zip: Vail, CO 81657 Pump ID: FP-0080924 Manufacturer: Patterson Pump Co Label: UL/FM Model Number: 6x5x17 SSC Serial Number: FP-0080924 Pump Type: Horizontal RPM: 1775 Rating - Churn: 0 gpm @ 113 psi 100%: 1,000 gpm @ 85 psi 150%: 1,500 gpm @ 60 psi Elevations - Pump: ft Discharge Gauge: 1 ft Suction Gauge: 1 ft Diameters - Impeller: 15.5 in Discharge Pipe: 6 in Suction Pipe: 8 in Rotation: Counterclockwise Max. Discharge Pressure: 250 psi Driver Type: Electric Brake Horsepower Brake Horsepower: 75.00 Maximum BHP: 74.80 at Positive Suction Pressure: 137 psi Electric Driver Manufacturer: Weg Electric Motors Corp Label: UL Model Number: OODD375 Serial Number: 18ABR08 1001185540 Horsepower: 75 RPM: 1780 AMP: 85.3 Volts: 460 Service Factor: 1.15 Frame: 365 TS Fire Pump Evaluation Program 2002 Page 2 Fred Zacherl FIRE PUMP TEST REPORT Solaris Pump Controller Manufacturer: Metron Inc Label: UL/FM Model Number: MP435-75-480C MTS Serial Number: NA-08N38847-21 Jockey Pump Manufacturer: Grundfos Pump Co Label: UL Model Number: CR1-10 A-FGJ-A-E-HQQE Serial Number: A96082127-P10833016 Horsepower: 1.00 RPM: 3466 Flow: 10 gpm Pressure: 87 psi Suction Diam: 1.25 in Discharge Diam: 1.25 in Jockev Pump Controller Manufacturer: Metron Inc Label: UL Model Number: M15AL-1-480 Serial Number: HK-08N38847-11 Relief Valve(s) Manufacturer Size Pressure Pump Casing - Aqualtrol 0.75 in 190 psi Transfer Switch Serial Number: NA-08N38847-21 Model Number: MTS 150 Manufacturer: Metron Inc Emergency power Source: Onsite Standby Generator Transfer Time: 3 secs Location: Part of Fire Pump Controller Pump Notes This fire pump feeds a systems with a PRV ahead of dry valves, and also directly to stand pipes. Test ID: 20100119 Date: 1/19/2010 Start: End: Method: Devices with hose Discharge Device: Playpipes Suction Pressure Location: Suction Flange Discharge Pressure Location: Discharge Flange Fire Pump Evaluation Program 2002 Page 3 Fred Zacherl FIRE PUMP TEST REPORT Solaris Flows Disch Suct Amperes Volts Net Corrected % # Press Press Flow RPM A B C A-B B-C A-C Press Flow Press Flow 1 213.0 101.0 0 1,794 22.0 20.0 30.0 480.0 478.0 478.0 112.0 0 110.0 0 2 194.0 96.0 1,012 1,784 58.0 56.0 79.0 478.0 476.0 475.0 98.0 1,007 97.0 101 3 164.0 90.0 1,541 1,782 66.0 62.0 88.0 477.0 476.0 474.0 74.0 1,535 73.0 154 Tester s Name License State Fred Zacherl Patterson Pump Rep CO Authority Havinq Jurisdiction Name: Michael J. McGee Title: Deputy Chief Company: Town of Vail Phone: 970-479-2135 Ext: Fax: 970-479-2176 Cell: E-mail: mmcgee@vailgov.com Witness(es� Name: Michael J. McGee Company: Town of Vail Phone: 970-479-2135 Fax: 970-479-9217 E-mail: mmcgee@vailgov.com Name: Steve Martin Company: Frontier Fire Protection Phone: 303-629-0221 Fax: 303-623-7830 E-mail: smartin@frontierfireprotection.com Temperatures Pump Bearing - Inner: 84 °F Outer: 85 °F Driver Bearing - Inner: 72 °F Outer: 74 °F Transfer Switch Transfer Time to Full Speed under Peak Load: 22 secs. Retransfer Time under No Load: 11 secs Gauges & Meters Type Calibration Date Pressure Gauges: Cecomp 9/16/2009 Volt Meter: Fluke 337 9/16/2009 Amp Probe: Fluke 337 9/16/2009 Tachometer: Extech 9/16/2009 Fire Pump Evaluation Program 2002 Page 4 Fred Zacherl FIRE PUMP TEST REPORT Solaris Test Notes This fire pump test consisted of three test runs of the fire pump: The first was with flow out the test header for discharge to street drain, the results from this portion are what are used in this report for flow data. The second portion the test was with flow through the flow meter, this load was used to test the transfer of power to and from the generator. The times in this report are from that portion of the test. The third portion of the test was also with the use of the flow meter and was to confirm the operation of the motor current draw of the pump. That test indicated that the Amps displayed by the fire pump controller are within the error allowed by the manufacture. This motor does appear to have a "lead leg" that draws more current then the other two; however when measured in portion three of the test it was within the limits of NFPA-20. At not time during any portion of the tests does it appear the the motor became over loaded. The pitot pressures a used for flow through the PRV and during the set up and testing of that valve are: 35 and 31 psi, equaling 1044 gpm. Flow Points Flow Point# 2 Flow Point# 3 Noz Size Coef Pitot Flow Noz Size Coef Pitot Flow # inch psi gpm # inch psi gpm 1 1.750 0.995 32.0 514 1 1.750 0.995 33.0 522 2 1.750 0.995 30.0 498 2 1.750 0.995 34.0 530 3 1.750 0.995 0.0 0 3 1.750 0.995 29.0 489 4 1.750 0.995 0.0 0 4 1.750 0.995 0.0 0 5 1.750 0.995 0.0 0 5 1.750 0.995 0.0 0 6 1.750 0.995 0.0 0 6 1.750 0.995 0.0 0 7 1.750 0.995 0.0 0 7 1.750 0.995 0.0 0 8 1.750 0.995 0.0 0 8 1.750 0.995 0.0 0 Fire Pump Evaluation Program 2002 Page 5 Fred Zacherl Solaris - 1/19/2010 FP-0080924 120 t Flow Test Data O Fire Pump Nameplate Data 110 100 90 O 80 70 .N n � � 60 O � � � a` 50 40 30 20 10 0 0 200 400 600 800 1000 1200 1400 1600 Flow(gpm) Patterson Pump Company Serial No: FY-0080924-001 Sold To: FRONTIER F1RE PROT. Job: 206702 Pu�np Type:6X5X17SSC Test Driver:W}�,STINGHOUSE (��� GPM:1000 Imp Pattern:C-10892 HI':150 • FM Ft. Head:196 Imp Dia:l 5.5 Effi�'/o:0_924 Rated RPM:1775 Vane Tips:.l 25 Test RPM:1780 Test Num:l No. Stages:l Test Type:Performance Test I�ate:Aug-20-2008 Certified By_ A� Approved By:_��f�„ / Witnessed By:_ �� �-�fy�G� � � 10Q 500 - Eff. % Ft. Head _ BHP NPSH ll, � 90 450 225 -- � r0 � 80 400 ;'��)0 7�? - 350 — ' 6t� 300 � � � o � ° 50 = 250 - _ - .� � � �i � - � 40 200 ^�"��_.: 30 150 y _ - � J 20 100 - °�`i ; , 1Q 50 - � � 0 0 i , �- 0 250 500 750 1000 1250 1500 1750 2000 GPM PATTERSON PUMP COMPANY ORDER 1NFORMATInN PUMP DATA RATING (Design) Customer: FRONTTER F1RE PROT. Pump Size&Type: 6XSX17SSC GPM: 1000 5erial No: FP-0080924-001 lrnpeller Pattern: C-10892 FT HD: 196 Job: 206702 lmpeller Diameter: I5.500 RPM(N2): 1775 Vane Tips: .I?5 Stages: 1 TEST INFORMATiON TEST DRiVER INFORMATION SI;CONDARY RATINGS Positive Pressure Test HP: ]50 GPM: 1,500.00, 0.00 Venturi Meter: 6" RPM: 1780 FT HD: 127.40, 0.00 Vei�turi Constant: 108.01 Manufacturer: WGS"I'INGHOUSE Discharge Dia: 5.00 Serial No.: 474f3859G09 Data Collected by: AL Suction Dia: 6.00 Volts: 4(0 Test Date : Aug-20-2008 Discharge Guage Elev.(Id): 0.00 Amps: 177 Test No.: 1 Suction Guage Elev. (7_,$): 0.00 S.F.: I.I S Pressure Ga: 300PSI Eff.(.00j: 0.924 Panel No.: 1 WaterTemp Test Data Calculated Data �� CalculaCed Data at Rated Speed No Pd(PSI)� Ps(PSl) kW Nl h���H2o) Ql (GPM) � Hl (F� whp ehp bhpl npump ' Q2(GPM) � Ei2(FT) bhp2 ] 127.0 I 1.70 I 23.00 1,796.00' 0.00 0.00 266.34 0.00 i 30.83 2$.49 0.00 0.00 260.15 27.50 2� 121.0 1120 44.80 1,794.00 22.50 512.34 254.20 ' 32.89'', 60.05 55.491i 59.27 �i; I 506.91 248.85 53J5 3� 1 I t.5 10.�0+ 52.80 1,792.00 54.50� 797.37 234.4� 47.21 70.78 65.401 72.18 789.81 I 230.02 63.5�I � 102.5 ]0.]0� 57.40 1,79].00 86.00 1,001.64 215.60 54.53 76.94 7l.10 76.71 i 992.70 21].77 II 69.2] 5 95.5 9.70 59.60 1,791.00 110.00 I 1,132.82 200.96 57.49 I!� 79.89 I 73.82 77.87 1,122.70 197.39I� 71.86 ! 6i 88A 9.30 61.20 I 1,791.00 Ii4.50 i 1,252.64 P 1g5•17 5 7 82.04 75.80 , 1241.45 181.88 73.79 i 7 68.5 7.90 62.00 1,791.00 I93.00 1,500.52 144.83 54.88 ' 83.11 76J9 71.46 �,: i 1,487.12' 142.26 74.7� I 8� 57.SOI- 8.00_, 62.00 1,791.00 223.00 '� 1,612.93 . 119.95 48.85I 83.11-- 76.79, 63.62 �I 1,598_SZII - 117.81 _7� Comments: ULlFM RATING 75��. To��RANCES PAT �ERSON PUMp COMPANY �"K°. sca�E o�wc. No. ��xc�Pr �,s .�ur�o> rocco,�, cFOFCiA A.L.B, 7/i9/78 FULL PJO. ECN DATF BY _ � _ �� �� � � DECIMAL � ��� Q- 1_ I APPRVD. CAI E ' A.P. 6-28- /8 FFZACTIONAL � � � � � � MAT. bRAWN PATT. N0. . �J�, ��� �.� �I A,����,��� F �T � _ PURCFLL ANGULAk PART N0. R�F. JOB PJG. ' ; 23001014 _ �� � D , F M I , �� ; A SU6S1�)IAKY U� THE GORMA��-R�PF CG. � TOCCO�,GEJRGIA `�� CENTR'FUGAI FIRE_ I'UMP S SP�IT CASF �IZE-TYPE N0. STGS. SERIAL N0. 6X5X17 SSC �1 ! FP-0080924 � RATE� B.�I.F. 75 MAX.B.H.P. 7L�.8 MAX. SUCT. il �3� P.S.I. '.50 CAN. G.P.M. R.P.M. PSIG MAX. I-'�IG P��G I��P. DIA.. , �_ 1 00 0 1775 �i 85 113 � 60 �, C5.50���- MADE I� U.S.A. i f : I � A d l�arn�n-Rupplaonlpry HYDROSTATIC�YRE TEST REPORT ' Sena� Number �L ������ Pump Model �i X��`� 5�C Test Pressure(PSq 3�`>� I Test Duration(MiN.) �� Test Liquid Water, Temperature ranging from 50 t0 70 degrees F . Test Facility C3�'�Small Pump Assy Gauge S!N 216619-63 0 Large Pump Assy Gauge S!N ❑ Ofher Gauge S/N Test Results � PASS ❑ FAIL COMMENTS: � . Tested By: i� � Date: � � O� Witnessed By: L�f N/A Date: