HomeMy WebLinkAboutP10-0023 NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT ALL TIMES
.•
�ow�o�va¢ •
Town of Vail,Community Development, 75 South Frontage Road,Vail,Colorado 81657
p.970.479.2139 f.970.479.2452 inspections 970.479.2149
PLUMBING PERMIT Permit #: P10-0023
NCOM Project #: PRJ08-0039
Job Address: 600 W LIONSHEAD CIR VAIL Status. . . : ISSUED
Location.....: FIRST CHAIR Applied . . : 04/29/2010
Parcel No...: 210106308004 Issued. . : 05/13l2010
Expires . .: 11/09/2010
OWNER VAIL CORP 04/29/2010
PO BOX 7
VAIL
CO 81658
CONTRACTOR R.K.MECHANICAL, INC 04/29/2010 Phone:303-355-9696
9300 E SMITH RD
DENVER
CO 80207
License: 181-P
Desciption: DOM WATER&PLUMBING INSTALLATION
Valuation: $564,402.00
...«..............,.�...<....................».«...........:...........«.»....�.. FEE SUMMARY .........�.....»».............*....................,�,.............................
Plumbing Permit Fee---> $8,475.00 Will Call------------------> $4.00 Total Calculated Fees---> $10,597.75
Plan Check----------------> $2,118.75 Use Tax Fee------------> $0.00 Additional Fees------------> $0.00
Investigation--------------> $0.00 TOTAL PERMIT FEES--> a10,597.75
Total Calculated Fees--> $10,597.75 Payments-------------------> $10,597.75
BALANCE DUE-----------> �0.00
N*4R1frRff*#MY#ifRfFft****IMt###*fhi4�!#*41fYfFRfH#*R**k41'**/nlRthhf*kf�►fM4fMet4M*t#V fef�Fllrt►RRRR##4#R#Mf1et4Yf*t4t4t*ttRf*#*tRMt#tRRtrkfeikfhf'1Hetk/i#iN/t#***ft W Rtftf4**ft#iM*fftt!*##*i#fftYfrtYtltfrYtRt*i#**H*tttf#ift
APPROVALS
Item:05100 BUILDING DEPARTMENT
04/29/2010 SAB/MH Action:AP REVIEWED WITH BUILDING-APPROVED PER MARTIN
Item:05600 FIRE DEPARTMENT
•,.,.��+�wv.rrir:�rx.��xxxxewrr�rtwr�w�x��+��+x+xxrxx::::xx+�,r,r�wrr��+,r�t+wwx���+��xwx�t�x�xrrrx:w�,rx�+.t��>r+.:xx.r::�,rxrwwr+rr,r��rrrwxw�,��:,r�xv::ws,r::,er�,.et�r+x��x���::�x�x.x�+wrxxx,r��eww�,e�r
; CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond:42
(BLDG 2009)CARBON MONOXIDE DETECTORS REQUIRED TO BE INSTALLED PER 2009 IRC R315
w�t,r#tt�+�*r�f��e,e��r�r:w►wrwatxwr+r+.+���r�►►��►►�ws�rr►r�wer�r,rwwwwwtiw��w+r+r+rw:w�t+�iR**�.�*►�*w+x*►wnwwwrwrer��:,ti�*��,rx,t►►,t++r:,tfrrtr:�wx�ear+rwwwwx,e►ww�w�w��i.,ts.tii�#�:►�+"«t:�*w*►►►�r�x
DECLARATIONS
I hereby acknowledge that I have read this application,filled out in full the information required,completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan,to comply with all Town ordinances and state laws, and to build this structure
according to the towns zoning and subdivision codes,design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FOR INSPE TION SHALL BE MADE TWENTY-FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM 8:0(
AM- PM.
S 'I�i' � �
Signature of Owner or Contractor Date
; � fC.� V"1y���
Print Name
�
I
i
i
�
� �
plmbpermtl_041908
�
*******�**********�*�**+***r*********�*****************+*******************r******�***+*****
� TOWN OF VAIL, COLORADO Statement
*****�*�++**************�*++********r*********�*+*******�***+*********r******+�++***********
� Statement Number: R100000459 Amount: $10, 597.7505/13/201012 :21 PM
Payment Method: Check Init: LC
� Notation: #175238 RK
� MECHANICAL
� -----------------------------------------------------------------------------
� Permit No: P10-0023 Type: PLUMBING PERMIT
� Parcel No: 2101-063-0800-4
�
� Site Address: 600 W LIONSHEAD CIR VAIL
� Location: FIRST CHAIR
� Total Fees: $10, 597.75
` This Payment: $10,597.75 Total ALL Pmts: $10, 597.75
� Balance: $0.00
� *******�************************************�********�**********�*******+*****r*******�*****
C ACCOUNT ITEM LIST:
� Account Code DesCription Current Pmts
j -------------------- ------------------------------ ------------
� PF 00100003112300 PLAN CHECK FEES 2, 118.75
' PP 00100003111100 PLUMBING PERMIT FEES 8,475.00
� WC 00100003112800 WILL CALL INSPECTION FEE 4.00
!
� -----------------------------------------------------------------------------
�
�
�
4
y
f
�
s
�
i
i
{
i
i
I
,
I
�
�
�
i
�
�
i
�
i
I
�
�
i
�
I
�
�
�
�
�
�
�' � �� �` � �� � _ ` �
� :,� •��` ,_.:,� ._��.i..;-=," v� �3��` �xY'' y. ,;:
A
� . � . ;,,x _ ,�
� Y- �`�'�t'�' ,� � �� ��i^� 4 �" y af.� �, � : �� • .. .:
—r a
'� �� ,,. a� �[� '��Cl�#�f1 � �� ' tMe��
�� � � . g��• �� � `°� �c � ����. �- �a��
�;�� � � � � �S�uth Fr�ntage .
�
.,� � �� ���' ' :;� � � ,,.
i _ �- ���.'��� � .°�� f ���`� , '•� • �
.�. �- � - ,,.
_,. *.� � .� „�. - >. � : �.�
� -�3, �
� � � ��
`�: �� � ��'� �... �� ��'�� �..• � -�:.�_ , .
�� '�' �°�"r ��� � �R � - �'` , �
� '� �:r' ; �
r.��� � � � ..r-�� ,� � � � e
� � ��.
_ ,. .
_� . �"
;
PLUMBING PERMIT
iPlumbin4 Permit Submittal Reauirements
!
r ❑ Floor plan/Site plan showing proposed work ❑ Building sewer/water service
I ❑ DWV plan ❑ Water heater/storage tank size&efficiency
� ❑ Water Piping plan ❑ Building type
❑ Gas Piping layout,including developed length and sizing ❑ Occupancy Group
i calculation
� Project Street Address: Office Use:
' lr1�b W��«��PQU �!/fCX� Project#: T().� W-DL�.�`7
� !(Number) (Street) (Suite#) /�
� . Y�1 �//� ./ D )_� Building Permit#: 17(��- ()30��
� !BuildinglComplex Name• 1" ✓ (�!�/ /v 1��1 l--U n/U_��a�
� ' Plumbing Permit#: Y°
� Contractor Infortnation: ` Lot#: Block# Subdivision:
3 �7�/ /,�f,,,,/ �7
;Company:--K/� /"l�C�'(C1iyt c.CQ.�'
p � �/ h
Company Address /�� �- �[�h � ' Define Scope and Location of Work: s'�''^ ��P.v�" '
I � �G��7 � �
� City: �2K(f� State:�Zip: �.�.�•. in•���C
! 'Contact Name: ���� �/�1 '
i
i c�
� 'Contact Phone: �7G� / 7 7- ��7'�
' 'E-Mail IJ��j'I �� ��! !�� b'� I ,Cj�-y. (use additional sheet if necessary)
i ..,,..
� Work Class:
� Town of Vail Contractor Registration No.: � �� ' �
, New� Addition( ) Remodel( ) Repair( ) Other( )
i t� _
� ',X � �`'�-'\ �-'� \�_�' TYPe of Building. . _ _
; !Contractor Signature(required) `{ )Single-Family( )Duplex( )Multi-Family( )Commercial '
I ...:... ....... ..... ...... .......,. ,., . .
„ .:.,. .
� Property Information ( )Restaurant( )Other '
� _ _ _
i I Parcel#: o�1(7� ' 0(a� "��CS� '� _ _ _
� '(For parcel#,contact Eagle County Assessors Office at 970.328-8640 or ' Date Received:
'. 'visit www.eaglecounty.us/patie) '
i '� '�
i Tenant Name:
� cu� �-r' p (� �/7
( Owner Name: _ _ _ _ IS � � � V �
' Complete Valuation for Plumbing Permit: D
I
� ',Plumbing$: '���� APR 2 9 2010
�
� TOWN OF VAIL
i �
, �����5
E I�' 01-Jan-10
I
I
' Zi
� � �
� �� � v��
03-02-2011 Inspection Req t Re orting age 23
4:32 m
Requested Inspect Date: Thursday, March 03, 2011
Inspection Area: JRM
Site Address: 600 W LIONSHEAD CIR VAIL
FIRST CHAIR
A/P/D Information
Activity: P10-0023 Type: B-PLMB Sub Type: NCOM Status: ISSUED
Const Type: Occupancy: Use: Insp Area: JRM
Owner: VAIL CORP
Contractor: R.K. MECHANICAL, INC Phone: 303-355-9696
Description: DOM WATER & PLUMBING INSTALLATION
Requested Inspectionls)
Item: 290 PLMB-Final Requested Time: 08:00 AM
Requestor: R.K. MECHANICAL, INC Phone: 303-355-9696
Comments: unit finals 566-0838
Assigned To: """"'"*""* Entered By: JMONDRAGON K
Action: Time Exp:
, //�
�
� . �
���.�
��-� �i°
�2 � J
�
Inspection History
Item: 210 PLMB-Underground
06/30/10 lns ector: CG Action: PI PARTIAL INSPECTION
Comment: UN�ERSLAB DWV, STORM AND SAND/OIL LINE
11/19/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Tub waste and overflow Units
504,505,506,507,508,509,510,511
Item: 220 PLMB-Rough/D.W.V.
10/07/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Rooms 204,205,206,207
10/13/10 Inspector: CG Action: CR CORRECTION REQUIRED
Comment: 208-STUD WALL FRAMING MISSING. RE-TEST IF VENT HAS TO BE MOVED
2ND FLOOR LAUNDRY-INSTALL TRAP ARM AND VENT FOR SINK
211-VENT TO PITCH BACK TO DRAIN FIRESTOP ALL PIPING
209,210-STUD WALL FRAMING MISSI�VG, RE-TEST IF VENT HAS TO BE MOVED. FIRESTOP
ALL PIPING
GARAGE LEVEL CEILING-PATCH MONOCOAT AT MECH ROOM WHERE REMOVED AT
WASTE PIPE
10/22/10 Inspector: cg Action: NR NOT READY FOR INSPECTION
Comment:
11/05/10 Inspector: cg Action: PI PARTIAL INSPECTION
Comment: TUB WASTE AND OVERFLOWS
UNITS 205,206,204,207,209,211,210
11/05/10 Inspector: cg Action: CR CORRECTION REQUIRED
Comment: UN1T 208-TUB WASTE AND OVERFLOW LEAKS AT BOTH TUBS
11/08/10 Inspector: CG Action: PI PARTIAL INSPECTION
Comment: 208-TUB DRAINS REINSPECTION APPROVED
11/11/10 Inspector: cg Action: PI PARTIAL INSPECTION
Comment: 310-TUBS OK
311-TUBS OK
309-TUBS OK
308-TUBS OK
307-TUBS OK
304-TUBS OK
306-TUBS OK
305-TUBS OK FIRESTOP NORTH TUB DRAIN
11/17/10 Inspector: cg Action: PI PARTIAL INSPECTION
REPT131 Run Id: 12746
�� � ���- � ���
� �
d�
� 03-09-2011 Inspection Request Reporting P ge 18
4:19 pm _ __Vail, CQ�ityQf
Requested Inspect Date: Thursday, March 10, 2011
Inspection Area: JRM
Site Address: 600 W LIONSHEAD CIR VAIL �
FIRST CHAIR � '`
A/P/D Information
Activity: P10-0023 Type: B-PLMB Sub Type: NCOM Stat � U
Const Type: Occupancy: Use: Insp Ar
Owner: VAIL CORP
Contractor: R.K. MECHANICAL, INC Phone: 303-355-9696
Description: DOM WATER & PLUMBING INSTALLATION
Requested Inspection(s)
Item: 290 PLMB-Final Requested Time: 10:00 AM
Requestor: R.K. MECHANICAL, INC Phone: 303-355-9696
Comments: gas piping and plmb level 4 566-0838
Assigned To: JMOf�DFZ�AGON Entered By: JMONDRAGON K
Action: Time Exp:
Comment: VEL UNIT FINALS�'ION TO DISHWASHER/SINK AIR GAP AS PER
STATE OF COLORADO REQUIR M�NTS MUST BE CORRECTED
� .
' L�i9""�` '��//
i / /�
/ / w V l
�
�
�
V P�
� � / ,
Inspection History � �
fi(,(-.C�
Item: 210 PLMB derground
06/ /10 lnspector. CG Action: PI PARTIAL NSPECTION Li�-�—
Comment: UNDERSLAB DWV, STORM AND SAND/OIL LINE •
11/19/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Tub waste and overflow Units
504,505,506,507,508,509,510,511
Item: 220 PLMB-Rough/D.W.V.
10/07/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Rooms 204,205,206,207
10/13/10 Inspector: CG Action: CR CORRECTION REQUIRED
Comment: 208-STUD WALL FRAMING MISSING. RE-TEST IF VENT HAS TO BE MOV
2ND FLOOR LAUNDRY-INSTALL TRAP ARM AND VENT FOR SINK
211-VENT TO PITCH BACK TO DRAIN FIRESTOP ALL PIPING
209,210-STUD WALL FRAMING MISSI�VG, RE-TEST IF VENT HAS TO BE VED. FIRESTOP
ALL PIPING
GARAGE LEVEL CEILING-PATCH MONOCOAT AT MECH ROOM WHERE REMOVED AT
WASTE PIPE
10/22/10 Inspector: cg Action: NR NOT READY FOR INSPECTION
Comment:
11/05/10 Inspector: cg Action: PI PARTIAL INSPECTION
Comment: TUB WASTE AND OVERFLOWS
UNITS 205,206,204,207,209,211,210
11/05/10 Inspector: cg Action: CR CORRECTION REQUIRED
Comment: UN1T 208-TUB WASTE AND OVERFLOW LEAKS AT BOTH TUBS
11/08/10 Inspector: CG Action: PI PARTIAL INSPECTION
Comment: 208-TUB DRAINS REINSPECTION APPROVED
11/11/10 Inspector: cg Action: PI PARTIAL INSPECTION
Comment: 310-TUBS OK
311-TUBS OK
309-TUBS OK
308-TUBS OK
307-TUBS OK
304-TUBS OK
REPT131 Run Id: 12812
i
• I
04-0�11 Inspection Request Reporting Page 24 !�
8:13 am Vail, CO - Citv Of
Requested Inspect Date: Thursday, April 07, 2011
Inspection Area: JRM
Site Address: 600 W LIONSHEAD CIR VAIL
FIRST CHAIR
A/P/D Information '�
Activity: P10-0023 Type: B-PLMB Sub Type: NCOM Status: ISSUED '
Const Type: Occupancy: Use: Insp Area: JRM ,
Owner: VAIL CORP
Contractor: R.K. MECHANICAL, INC Phone: 303-355-9696 '
Description: DOM WATER&�P�UMBING INSTALLATION '
' �1 I
Re uested Ins ection
Item: 29 PLMB-Final Requested Time: 04:00 PM
Requestor. Phone:
Comments: 977-1053
Assigned To: JMONDRAGON r Entered By: MHAEBERLE K
Action: ` J Time Exp:
Comment: VEL UNIT FINALS ZDF�ECTION TO DISHWASHER/SINK AIR GAP AS PER
STR�E OF CO RADO REQUIREM�NTS MUST BE CORRECTED
Comment: APPKU�T LEVEL UNITS(404-411) ONLY
Comment: Vacuum reaker in boiler room for hose bib
Pipe Identification
access identification
Comment: units only
�
�
r �
`� �
1
Inspection History �
Item: 210 PLMB-Underground
06/30/10 Inspector: CG Action: PI PARTIAL INSPECTION
Comment: UNDERSLAB DWV, STORM AND SAND/OIL LINE
11/19/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Tub waste and overflow Units
504,505,506,507,508,509,510,511
Item: 220 PLMB-Rough/D.W.V.
10/07/10 Inspector: Martin Action: PI PARTIAL INSPECTION
Comment: Rooms 204,205,206,207
10/13/10 Inspector: CG Action: CR CORRECTION REQUIRED
Comment: 208-STUD WALL FRAMING MISSING. RE-TEST IF VENT HAS TO BE MOVED
2ND FLOOR LAUNDRY-INSTALL TRAP ARM AND VENT FOR SINK
211-VENT TO PITCH BACK TO DRAIN FIRESTOP ALL PIPING
209,210-STUD WALL FRAMING MISSING, RE-TEST IF VENT HAS TO BE MOVED. FIRESTOP
ALL PIPING
GARAGE LEVEL CEILING-PATCH MONOCOAT AT MECH ROOM WHERE REMOVED AT
WASTE PIPE
10/22/10 Inspector: cg Action: NR NOT READY FOR INSPECTION
Comment:
11/05/10 Inspector: cg Action: PI PARTIAL INSPECTION
Comment: TUB WASTE AND OVERFLOWS
UNITS 205,206,204,207,209,211,210
11/05/10 Inspector: cg Action: CR CORRECTION REQUIRED
Comment: UN1T 208-TUB WASTE AND OVERFLOW LEAKS AT BOTH TUBS
11/08/10 Inspector: CG Action: PI PARTIAL INSPECTION
Comment: 208-TUB DRAINS REINSPECTION APPROVED
11/11/10 Inspector: c�g Action: PI PARTIAL INSPECTION
Comment: 310-TUBS OK
REPT131 Run Id: 12941