Loading...
HomeMy WebLinkAboutB10-0129 comment letterDepartment of Community Development 5 South Frontage Road Vail, Colorado 81657 970-479-2138 FAX 970-479-2452 www.vailgov.com ______________________________________________________________________ PROJECT REVIEW COMMENTS DATE: 6/11/10 TO: Geyer Construction pgeyerconstruction@gmail.com PERMIT APPLICATION #: B10-0129 PROJECT ADDRESS: 610 W Lionshead #701 OCCUPANCY GROUP: R2 TYPE OF CONSTRUCTION: IB NUMBER OF STORIES: existing BUILDING AREA: existing ● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified. ● Please respond in writing to each comment with a response letter addressing each comment. BUILDING DEPARTMENT COMMENTS Architectural Comments: 1 Indicate building construction type per IBC ch. 6 on the plans. Town of Vail records indicate IB construction type for the Landmark building 2 Indicate on plans all new framing to be non-combustible construction. Include wall and ceiling construction details. IBC 602.2 3 Revise loft guard height to 42” minimum per IBC 1013 4 Revise 6.1 wood framing notes on the plan sheets. Wood framing is not permitted in type IB construction. 5 Show stairway construction with non-combustible framing per IBC 1009.6 Structural Comments: 6 Clarify scope of structural work, include structural sheets in the plan sets