HomeMy WebLinkAboutVK462 May 14, 2010 Sprinkler 54a
MIRAGE° STANDARD AND
N I I a:N:G:*: QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
1. DESCRIPTION
Viking Mirage°Standard and Quick Response Concealed Pendent Sprinkler VK462 and
HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for installa-
tion on concealed pipe systems where the appearance of a smooth ceiling is desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-profile
cover assembly that provides up to '/2' (12.7 mm) of vertical adjustment. The two-piece -
design allows installation and testing of the sprinkler prior to installation of the cover plate. 50,11
The "push-on", "thread-off' design of the concealed cover plate assembly allows easy
installation of the cover plate after the system has been tested and the ceiling finish has -
been applied. The cover assembly can be removed and reinstalled, allowing temporary
removal of ceiling panels without taking the sprinkler system out of service or removing
the sprinkler.
2. LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89-92-E, Volume 32
VdS Approved: Certificate G4080021
LPC Approved: Ref. No. 096e/12
CE Certified: Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2032 and 0786-CPD-40249
Refer to Approval Chart 1 and Design Criteria on page 54c for cULus Listing requirements, and refer to Approval Chart 2 and
Design Criteria on page 54d for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)* Viking Technical Data may be found on
Maximum Working Pressure: Sprinkler VK463 is rated for use with water
working pressures ranging from the minimum 7 psi (0.5 bar) up to The Viking Corporation's Web site at
250 psi (17.2 bar)for high-pressure systems. High-pressure (HP) http://www.vikinggroupinc.com.
sprinklers can be identified by locating "250" stamped on the deflec- The Web site may include a more recent
tor. Sprinkler VK462 is rated to a maximum 175 psi (12 bar)wwp. edition of this Technical Data Page.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metrict)
Glass-bulb fluid temperature rated to-65 °F (-55 °C)
Patents Pending
`cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
tMetric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C19500 for Sprinkler VK462
Phosphor Bronze UNS-C51000 for Sprinkler VK463
Deflector Pins: Stainless Steel Alloy
Bulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-C51000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Form No. F_103005 Replaces page 54a-e, dated August 13, 2009. (Split the Approval Charts
to separate cULus Listing requirements from FM Approval requirements.)
Sprinkler 54b May 14, 2010
MIRAGE° STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Cover Assembly Materials:
Cover: Copper UNS-C11000
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Mirage°Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. 13503A, 14697A, or HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix (°F/°C): 155°/68° = B, 175°/79° = D, 200°/93° = E
For example, sprinkler VK463 with a 155 °F/68 °C temperature rating = 13667AB.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No.
15394 (square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by first adding the appropriate suffix for the finish and then the
appropriate suffix for the cover temperature rating to the base part number:
Finish Suffix: Polished Chrome= F, Painted White=M-/SW1004, Painted Ivory= M-/SW1634, Painted Black= M-/SW1007
Temperature Suffix(°F/°C): 135°/57° LIL(139°/59° FM)=A, 165°/74°=C
For example, cover 13504 with a Polished Chrome finish and a 165 °F/74 °C temperature rating = 13504FC.
Note: Square cover plate 15394 cLlLus Listing is for the 135°F(57°C)temperature rated cover plate only. Refer to the Approval Chart.
Available Finishes And Temperature Ratings:
Refer to Table 1
Accessories: (Also refer to the"Sprinkler Accessories"section of the Viking data book.)
Sprinkler Wrenches":
A. Heavy Duty Wrench Part No. 14047W/B (available since 2006), or
B. Head Cabinet Wrench Part No. 14031— (available since 2006)
C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007)
–Requires a''/i'ratchet(not available from Viking).—Optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A, Capacity: five (5)sprinklers (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
May 14, 2010 Sprinkler 54c
MIRAGE° STANDARD AND
a:N:G:*: QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
TABLE 1:AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient Temperature Rating of Cover Bulb Color
Classification Temperature Rating' Ceiling Temperature Assembly(Required)
Ordinary 155 °F (68 °C) 100 °F (38 °C) 135 °F (57 °C)cULus Red
139 °F (59 °C) FM
Intermediate 175 °F (79 °C) 150 °F (65 °C) 165 °F (74 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) 165 °F (74 °C) Green
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted
Ivory, or Painted Black
Footnotes
The sprinkler temperature rating is stamped on the sprinkler deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
��� C U S j0�
Q�
DO NOT PAINT
9�
y �
o n
v
VIKING ��
Identification of Custom Paint Color
All custom color painted, cover plates will
have an identifying label affixed to the
inside of the cover, that Indicates custom 3-5/16" (84,1 mm)
color and will have a representative sample
Ca paint dot) of the paint or the label
Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394
Sprinkler 54d May 14, 2010
MIRAGE° STANDARD AND
i CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Approval Chart 1 (UL) Sprinkler Temperature Rating
Cover Plate Temperature Rating
Mirage"Concealed Pendent Sprinklers VK462 and VK463 AW1*Cover Plate Finish KEY
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum Listings and Approvals°
SIN Water Working (Refer also to Design Criteria below.)
Part No. Inch mm U.S. metric2 Pressure cli NYC6 VdS LPCB
Standard Response Applications
13503A VK462 1/2" 1 15 1 5.6 1 80.6 1 175 psi (12 bar) -- AY1,CZ1 —
14697A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) — AV2, BW2 AV2, BW2'
Quick Response Applications
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX1 AV1, BW1 — — AY2, CZ28
14697A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX1 AV1, BW1 — — —
13667A VK463 1/2" 15 5.6 80.6 250 psi(17.2 bar)3 AV1, BX1 AV1, BW1
Cover Plate Assembly Temperature Ratings' Cover Plate Assembly Finishes10
Sprinkler Temperature Ratings V- 135°F(57°C)cULus Listed cover 13504'or 13642' (large diameter) 1 - Polished Chrome, Brushed
A- 155°F(68°C) W- 165°F(74°C)cover 13504' or 13642' (large diameter) Chrome, Bright Brass, Antique
X- 165 °F (74 °C) cover 135041, 13642' (large diameter), or 15394' Brass, Brushed Brass, Brushed
B-175°F(79°C)and 200°F(93°C) (square cover plate) Copper, Painted White, Painted
C-200°F(93°C) Y- 135°F(57°C)cover 13504' Ivory,or Painted Black
Z- 165°F(74°C)cover 13504' 2-Polished Chrome, Painted White
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
Z Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in i divide the metric K-factor shown by 10.0.
3The Water Working Pressure rating is stamped on the deflector.
°This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for an
additional approvals.
5 Listed by Underwriter's Laboratories for use in the U.S.and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E,Vol. 32.
' Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032.
S Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40249.
'The 135/139°F cover has an orange label.The 165°F cover has a white label.
1'Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA- UL
(Also refer to Approval Chart 1 above.)
cli Listing Requirements:
Mirage®Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
• For hazard occupancies up to and including Ordinary Hazard, Group ll.
• Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13.Maximum spacing allowed is 15 ft.(4.6 m).
• Minimum spacing allowed is 6 ft. (1.8 m)unless baffles are installed in accordance with NFPA 13.
• Minimum distance from walls is 4 in. (102 mm).
• Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1-3 or Ii for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stand-
ards, whenever applicable.
May 14, 2010 Sprinkler 54e
MIRAGE° STANDARD AND
NJ I KJ:N:C:*j: QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Approval Chart 2 (FM) Sprinkler Temperature Rating
Cover Plate Temperature Rating
Mirage" Standard Response Concealed Pendent Sprinkler VK462 Awl 4-Cover Plate Finish KEY
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum FM Approvals3
Part No.' SIN Water Working (Refer also to Design Criteria below.)
Inch mm U.S. metric2 Pressure
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AW1,BX1
Cover Plate Assembly Temperature Ratings^ Cover Plate Assembly Finishes'
Sprinkler Temperature Ratings W- 135 OF (57 °C)cULus Listed cover 135041, 13642' 1 - Polished Chrome, Brushed Chrome, Bright
A- 155 OF(68°C) (large diameter), or 15394 (square cover plate) FM Brass, Antique Brass, Brushed Brass,
Approved as 139 OF(59°C)
B-175 OF(79°C)and 200 OF(93°C) X - 165 OF (74 °C) cover 135041, 13642' (large diam- Brushed Copper, Painted White, Painted
eter),or 15394' (square cover plate) Ivory,or Painted Black
Footnotes
' Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar.When pressure is measured in kPa,divide the metric K-factor shown by 10.0.
3 This chart shows the FM Approvals available at the time of printing.Other approvals may be in process.Check with the manufacturer for any additional
approvals.
^The 135/139 OF cover has an orange label.The 165 OF cover has a white label.
' Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA- FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets(including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design,ceiling slope and obstructions, minimum and maximum allowable spacing,and deflector distance below the ceiling.
NOTE:The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT. Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD,VdS or other similar organizations,and also with the provisions of governmental codes, ordinances,and
standards, whenever applicable.
Sprinkler 54f May 14, 2010
MIRAGE° STANDARD AND
NIKJNG* QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 K5.6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs @vikingcorp.com
Sprinkler
Wrench
Sprinkler bK Flat
2-1/4' (57,2 mm) Frame
diameter opening Arms
is required in
the ceiling.
Sprinkler and
Adapter Assembly
(Protective Cap
is removed for
installation--use
Wrench 14031 > Iff
NEVER install the sprinkler
by applying the installation
Sprinkler wrench across the frame arms,
Wrench
(Part No. D❑ NOT overtighten,
14047W/B)Kw Use only the designated
_ is shown) sprinkler wrench, Viking Part
Number 14047W/B or 14031.
AwA 1/2' ratchet
is required (not D❑ NOT apply more than
available from Viking). 25 ft. lbs. of torquie. A leak
tight seal should be achieved
Step 2: Carefully press the by turning the sprinkler
Step 1; Carefully slide the wrench upward and turn slightly clockwise 1 to 1-1/2 turns
wrench sideways around to ensure engagement with the beyond finger tight.
the deflector and pins. sprinkler wrench flats,
Figure 3: Sprinkler Installation and Correct Use of Wrenches
1/2'
(15 mm)
NPT
2-9/16" 2-1/16'
2-3/16" (65 mm) (52 mm)
(55 mm) Maximum
Minimum
2-3/4' (70 mm) or
3-5/16" (84.1 mm)
Note) Upon sprinkler activation, the deflector descends
to approximately 13/16' (20.6 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F103005 Replaces page 54a-e, dated August 13, 2009. (Split the Approval Charts
to separate cULus Listing requirements from FM Approval requirements.)