HomeMy WebLinkAboutM10-0118NOTE: THIS PERMIT MUST BE POSTED ON JOBSITE AT
MWWOFVK
Town of Vail, Community Development, 75 South Frontage Road, Vail, Colorado 81657
p. 970 - 479 -2139 f. 970.479.2452 inspections. 970.479.2149
MECHANICAL PERMIT
AMF
Job Address: 1370 SANDSTONE DR VAIL
Location.....: UNIT 8, EIGER CHALETS
Parcel No...: 210312103008
OWNER LOPEZ, IVAN 07/06/2010
PO BOX 6852
AVON
CO 81632
APPLICANT ERIC'S PLUMBING & HEATING IN 07/06/2010 Phone: 970 - 524 -0743
PO BOX 112
GYPSUM
CO 81634
License: 425 -M
CONTRACTOR ERIC'S PLUMBING & HEATING IN 07/06/2010 Phone: 970 - 524 -0743
PO BOX 112
GYPSUM
CO 81634
License: 425 -M
Desciption: ADDITION & REMODEL: INSTALL RADIANT IN -FLOOR HEAT AND
VENTILATION
Valuation: $12,100.00
ALL TIMES
Permit #: M10-0118
Project #: PRJ10 -0068
Status ...:
ISSUED
Applied..
07/06/2010
Issued. .:
07/13/2010
Expires . .:
01/09/2011
Mechanical Permit Fee --- > $260.00 Will Call --- ------- > $4.00 Total Calculated Fees - ->
$329.00
Plan Check------------ - - - - -> $65.00 Use Tax Fee ------ > $0.00 Additional Fees--- - - - - -> $0.00
Investigation — ------ — ------- > $0.00 TOTAL PERMIT FEE —> $329.00
Total Calculated Fees - -> $329.00 Payments------------ ---- -> $329.00
BALANCE DUE - - -> $0.00
Item: 05100 BUILDING DEPARTMENT
07/13/2010 JRM Action: AP
APPROVALS
Item: 05600 FIRE DEPARTMENT
CONDITION OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 42
(BLDG 2009) CARBON MONOXIDE DETECTORS REQUIRED TO BE INSTALLED PER 2009 IRC R315
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot plan, and state that all the information
as required is correct. I agree to comply with the information and plot plan, to comply with all Town ordinances and state laws, and to build this structure
according to the towns zoning and subdivision codes, design review approved, International Building and Residential Codes and other ordinances of the Town
applicable thereto.
REQUESTS FOR INSPEC'jION SE
AM - 4 PM. �1+ LL BE MADE TWENTY -FOUR HOURS IN ADVANCE BY TELEPHONE AT 970.479.2149 OR AT OUR OFFICE FROM 8:0(
Signaturvof Owner or Contractor
YV rrl O G 2D
Print Name
? - U3 -10
Date
m e ch ca n ica I_pe rm it_041908
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO
Statement
*************************************************************
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Statement Number:
R100000851 Amount: $329.00 07/13/201002:32
PM
Payment Method:
Check Init: SAB
Notation:
8329 ERIC
PLUMBING & HEATING
-----------------------------------------------------------------------------
Permit No:
M10 -0118 Type: MECHANICAL PERMIT
Parcel No:
2103 - 121 - 0300 -8
Site Address:
1370 SANDSTONE DR VAIL
Location:
UNIT 8, EIGER CHALETS
Total Fees:
$329.00
This Payment:
$329.00 Total ALL Pmts:
$329.00
Balance:
$0.00
ACCOUNT ITEM LIST:
Account Code
Description Current Pmts
-------------- - - -
MP 00100003111100
- -- ------------------------ - - - - -- ------
MECHANICAL PERMIT FEES
- - - - --
260.00
PF 00100003112300
PLAN CHECK FEES
65.00
WC 00100003112800
WILL CALL INSPECTION FEE
4.00
Lo C.�
Boiler/ Furnace Applicz
ik- Mechanical Room Layou I A, r ,n L ' f
vr Combustion Air Duct Siz oval listing)
Oh Flue or Vent Size
w Gas Piping Plan (if appli( /
lr Heat Loss Calculations* l � —
❑ Equipment Cut Sheets fr
* Not required for same size (BTU) boiler replacement with no system
changes, or snow melt
Project Street Address:
1350 _ hJ5FG nk Orw<_' S
(Number) (Street) (Suite #)
Building /Complex Name: 510rZ Chad ETS
Contractor Information:
Company: 6R I C S P 16 G A
Company Address: Po I I -.�-
City: G w S y m State: (A zip: 9 1 6 �}
Contact Name: 6 (L
S' C_
Office Use:
a Project #: . w
Building Permit #: (6 (u rr, o (( a'
Mechanical Permit #: f 1 V Q 1 1 9
Lot #: Block # Subdivision:
Detailed Description of Work: 2-fl F.(vor Hel�tT
U e6y'L�a V(U h ,
Contact Phone: 31?o - Y
(use additional sheet if necessary)
E -Mail C�G n�uv P_ CUevr -lT-< ( < ✓1 er
Gas Piping Included
Town of Vail Contractor egistration No.: �� ❑ Gas Piping by Others
�(ZS ❑ Wood to Gas Fireplace Conversion
X Boiler Location���
Contractor Signature (required)
�. Interior (XS Exterior ( )
Property Information - - -
Number of Existing Fireplaces:
Parcel #:
(For parcel #, contact Eagle County Assessors Office at 970 - 328 -8640 or I Gas Appliances Gas Logs
visit www.eaglecounty.us /patie) . >._
Other ( )
Wood /Pellet
Tenant Name:
a (0 3 la t 03 0 02 1 Number of Proposed Fireplaces:
Gas Appliances Gas Logs Wood /Pellet
(Commercial Properties)
Owner Name: to PCz
Complete Valuation for Mechanical Permit:
Mechanical $:
Type of Building:
i
Single - Family ( ) Duplex ( ) Multi - Family (k) Commercial
Restaurant( ) Other(
Date Received:
JUL 06 2010
t&
TOWN OF VA!
�ol���z Ve�T C:��n� �on -,�o /�ib2 ir
'` S o (� D Co ►'fie- P v �- I �r i ►^'�
C
0
i�
� CAS ��VIe Pr ck�n� vr; Stove, o/, ( 66 � � ►z -y��
Zso 0)
oi go° v�)
116,000 6
a �k
M
Radiant Works Pro Zone List Report 7/1/2010
Project Information
Project Number:
Project Quote: 1
Project Name: Lopez Renovation
Designed For: Eric's Plumbing & Heating
1350 Sandstone Drive Unit #8
Vail, 81657
Design Guidelines:
Contact Information Project Assumptions
Designed By: Andy Casper Outdoor Temp: -20 `F
Company Name: Ferguson Enterprises Inc. Elevation: 8,250 ft
Phone Number: 970- 328 -0740 Wind Speed: 13 mph
Job Type: Residential
R Values - Wails R19, Ceilings R30, Windows & Doors R2.
. . ,
Tubing to be installed under all tubs and showers.
Zone Name: Zone 2
Baseboard
Zone Name: Zone 1 (Baseboard)
Radiant Heatin
Radiant Heatin
Product: 1/2" RadiantPEX
Construction: Slab
0.57
Supply Fluid Temp: 180.0 OF Required Heat: 5,384 BTU /h
Slab Thickness:
4.00 in
Delta T: 20 OF Panel Load: 6,499 BTU /h
Thickness Above Tube.
2.00 in
Flows 0.65 GPM Manifold Distance: - -- ft
Slab Conductivity:
0.81 BTU /(h-ft- °F)
Head: 3.7 ft Glycol %: 0%
Slab Conductivity:
0.81 BTU /(h1 - - F)
# of Circuits: 1
ft Glycol %: 0%
125
Circuit Length: 300 ft
# of Circuits: 1
Room Name
I Garage
No Floor Covering
Tube II I Banded Max Surface Required
Heated Area Unheated Area �Spacing �Banded Area tSpacing� Temp Intensity I Required Heat
ft ft2 in ft ` in - F IBTU /h ft' BTU /h
280 12 — - -- 85 19.2 5,384
Int Capacity
BTU /h
36,319
'oom Name
_ntry
Tile- wl Mudset : R -0.15
'hower / Sauna
Tile - w/ Mudset . R -0.15
I .VIIC IV
3 roduCt:
Tube Banded Max Surface Required
Heated Area Unheated Area Spacing Banded Area Spacing Temp. Intensity Required Heat Radiant Capacity
ft ft in ft in °F BTU /h ft BTU /h BTU /h
155 - -- 12 - -- — 85 16.6 2,577 16,393
108 -- 12 — - -- 85 8.8 956 11.457
_._.. _..
. . ,
„� r rcm- Q,V4 1 u l urn
Zone Name: Zone 2
Baseboard
20
Radiant Heatin
Product: 112" RadiantPEX
Subfloor Thickness: 0.75 in
Construction: Slab
0.57
Supply Fluid Temp: 180.0
OF Required Heat. 3,532 BTU /h
Slab Thickness:
4.00 in
Delta T, 20
OF Panel Load: 4,501 BTU/h
Thickness Above Tube:
2.00 in
Flow; 0.45
GPM Manifold Distance: - -- ft
Slab Conductivity:
0.81 BTU /(h1 - - F)
Head: 2.0
ft Glycol %: 0%
125
ft
# of Circuits: 1
Circuit Length: 300
ft
'oom Name
_ntry
Tile- wl Mudset : R -0.15
'hower / Sauna
Tile - w/ Mudset . R -0.15
I .VIIC IV
3 roduCt:
Tube Banded Max Surface Required
Heated Area Unheated Area Spacing Banded Area Spacing Temp. Intensity Required Heat Radiant Capacity
ft ft in ft in °F BTU /h ft BTU /h BTU /h
155 - -- 12 - -- — 85 16.6 2,577 16,393
108 -- 12 — - -- 85 8.8 956 11.457
_._.. _..
. . ,
„� r rcm- Q,V4 1 u l urn
jolsi 5pacjng: 116.00 in
)elta T:
20
OF
Panel Load - 5,725 BTU /h
Subfloor Thickness: 0.75 in
-low:
0.57
GPM
Manifold Distance: -- ft
Subfloor Conductivity: 0.09 BTU /(h•ft• °F)
iead-
0.4
ft
Glycol %: 0%
t of Circuits:
2
:ircuit Length:
125
ft
Copyright(c) Watts Radiant 2007
Product: 112" RadiantPEX
-
Radiant Heatin
Construction: UnderFloor
Supply Fluid Temp:
160.0
OF
Required Heat: 5,856 BTU /h
Joist Spacing: 16.00 in
Delta T:
20
OF
Panel Load: 6,461 BTU /h
Subfloor Thickness: 0.75 in
Flow.
0.65
GPM
Manifold Distance: -- ft
Subfloor Conductivity: 0.09 BTU /(h•ft.
Head:
0.4
ft
Glycol %: 0%
Subfloor Conductivity: 0.09 BTU /(h•ft• °F)
# of Circuits
3
Glycol %: 0%
# of Circuits: 2
Circuit Length:
200
ft
Circuit Length: 125
ft
Room Name
Heated Area
W
Tut>e Banded Max Surface Required
lted Area Spacing Banded Area Spacing Temp. Intensity Required Heat
ft in ft in °F BT /h ft BTU /h
— 8 — - -- 85 15.8 5,856
int Capacity
BTU /h
12,628
I Living ! Dining Area
Hardwood- 3/4" : R -0.90
370
I t-one Name: zone 5
-
Product: 1 /Z" RadiantPEX
Radiant Heatin
Construction: UnderFloor
Supply Fluid Temp: 160.0
OF
Required Heat: 2,900 BTU /h
Joist Spacing: 16.00 in
Delta T: 20
OF
Panel Load. 3,177 BTU /h
Subfloor Thickness: 0.75 in
Flow: 0.32
GPM
Manifold Distance: -- ft
Subfloor Conductivity: 0.09 BTU /(h•ft• °F)
Head; 0.1
ft
Glycol %: 0%
# of Circuits: 2
Circuit Length: 125
ft
2oord Name
I Guest Bedroom West & Upper Hall
Hardwood- 3/ R -0.90
Tube Banded Max Surface Required
Heated Area Unheated Area Spacing Banded Area Spacing Temp. Intensity Required Heat Radiant Capacity
ft ft in ft in °F BTU /h-ft BTU /h BTU /h
155 -- 8 - -- -- 85 18.7 2,900 5,303
cone Name: zone 6
-
Product: 112" RadiantPEX
Radiant Heatin
Construction: UnderFloor
Supply Fluid Temp: 160.0
OF
Required Heat: 3,034 BTU /h
Joist Spacing: 16.00 in
Delta T 20
OF
Panel Load : 3,319 BTU /h
Subfloor Thickness: 0.75 in
Flow: 0.33
GPM
Manifold Distance: - -- ft
Subfloor Conductivity: 0.09 BTU /(h•ft• °F)
Head: 0.1
ft
Glycol %: 0%
# of Circuits: 2
Circuit Length: 125
ft
I Copyright(c) Watts Radiant 2007 2
Radiant Works Pro Zone List Report (cont.) 7/1/2010
one
Supply Fluid Temp:
Tube
Heated Area Unheated Area Spacing Banded Area
Banded Max Surface Required
Spacing Temp, Intensity
Delta T:
Room Name
W ftin
°F
EII: ed Hea# Radiant Capacity
Guest Bathroom
ft 2
29 14
in BT U /h fP
U /h BTU / h
Tile- w/ Mudset : R -0.15
8
85 15.2
441 1,534
Guest Bedroom East
118 8
Hardwood- 3/4": R -0.90
--
85 22.0
2,593 4,040
one
Supply Fluid Temp:
160.0
°F
Delta T:
20
°F
Flow.
0.59
GPM
Head:
0.1
ft
# of Circuits,
4
Circuit Length:
125
ft
Required Heat: 5,389 BTU /h
Panel Load: 5,938 BTU /h
Manifold Distance: -- ft
Glycol %: 0%
Joist Spacing: 16.00 in
Subfloor Thickness: 0.75 in
Subftoor Conductivity: 0.09 BTU /(h- ft- °F)
ROOM Name Heated Area (Unheated
R2 ft
Master Bathroom 50 20
Tile- w/ Mudset : R -0.15
Master Bedroom / Closet & Water Clo 241 4
Hardwood- 3/4": R -0.90
Project Summary
Total Flow: 3.56 GPM
Total Head. 3.70 ft
Total Project Panel Load: 35,622.00 BTU /h
I 'lease verify all project information for accuracy.
Signature:
Tube Banded Max Surface Required
pacing Banded Area Spacing Temp intensity Required Heat Radiant Capacity
in ft in °F I BTU/h-ft2 BTU /h BTU /h
8 - 85 23.7 1,183 2,603
s - -- — 85 17.5 4,206 8,014
Date:
I Copyright(c) Watts Radiant 2007 3
N y
CL
d1
C
m
m
_a
Cc
0
o
� E
314' Pipe Size
M
a 5
Bypaea Loop
= c
0
o .�
E
. C
_
C
O
N
C', O
9
Q ;
f0
E w
_.
�o
c c
o m
0
--
a m
o
A
E
:a
m r CD
a
m C
O
«
m
Q)
O
O
z y
O
Z
=
L
N
cu
CL
O
U
�
c
N
a
Q
Q
o
U
J
N_c
w
�
llLLttJJ7
�
d
a
a
L
O
-0
U
c
N
(D
O
t 0)%J...
Q
Q.
+�
a)
Q)
ez!S ad!d 4
d
a-
0
Z
p
>. v O
v
az S !d l
C:
O
V
azfS ad!d
to — to
.1
yr
CA
O O
Q J
cu
> L >
– z1 .... --- 3oHMH(7
W MHO
(d L
ez!S ad!d ,,
co N
L c O
O c
`
U) o O
t0
o
m E
C O c
F– E>
N c
> `m c
� N
I
_ Y.
O O O
O M
z
oa
r
C
G I
7 �
7
r
Z
A
c ,
S -4
Jy
C
Q �
N
V)
� o
n
r 0
o (r)
W
dA, I �) --- 0 HO
I
11 -09 -2010 Inspection Request Reporting Page 24
7:33 am Vail, CO - City Of
Requested Inspect Date: Tuesday, November 09, 2010
Inspection Area: CG
Site Address: 1370 SANDSTONE DR VAIL
UNIT 8, EIGER CHALETS
A/P /D Information
Activity: M10 -0118 Type: B -MECH Sub Type: AMF Status: ISSUED
Const Type: Occupancy: Use: Insp Area: CG
Owner: LOPEZ, IVAN
Contractor: ERIC'S PLUMBING & HEATING INC. Phone: 970 - 524 -0743
Description: ADDITION & REMODEL: INSTALL RADIANT IN -FLOOR HEAT AND VENTILATION
Reauested Inspections
Item: 390 MECH -Final
Requestor:
Comments: 390 -4522
Assigned To: JMONDRAGON
Action: Time Exp:
Requested Time: 04:30 PM
Phone:
Entered By: MHAEBERLE K
4) F UV-`Ce_r)
Inspection History
Item:
200 MECH -Rough
** Approved **
07/30/10 Inspector:
sgremmer
Comment:
Item:
310 MECH - Heating
** Approved **
07/30/10 inspector:
sgremmer
Comment:
Item:
315 PLMB -Gas Piping
Item:
320 MECH - Exhaust Hoods
Item:
330 MECH - Supply Air
Item:
340 MECH -Misc.
Item:
390 MECH -Final
Action: AP APPROVED
Action: AP APPROVED
REPT131 Run Id: 12146