HomeMy WebLinkAboutA10-0047 405-05 cut sheet
Product:
Smoke Detector Accessory, Polarity Reversal
Module, For Sounder Tandem Interconnection, 1
Circuit, 12/24VDC, UL
Description: Polarity reversal modules are designed for use with
smoke detectors that have built-in sounders. On alarm,
the module disconnects the detector from its normal
power supply and applies reverse polarity from the
notification appliance circuit. Applying reverse polarity
causes the sounders on detectors not in alarm to
activate.
Both 2- and 4-wire modules are available. The 405-01
and 405-03 modules come assembled for installation
on a standard 4-inch commercial electrical box. The
405-05 and 405-06 modules ship with double-sided
adhesive.
Field Wiring Size
[Maximum]
18.0 AWG
Length[Nominal] 1.8 in
Operating Humidity
[Minimum]
0.0 % RH
Operating Humidity
[Maximum]
85.0 % RH
Operating Temperature
[Minimum]
32.0 °F
Operating Temperature
[Maximum]
120.0 °F
Operating Voltage
[Minimum]
12.0 V
Operating Voltage
[Maximum]
24.0 V
Regulatory Approval UL
CSFM
MEA
Relay @ Contact Rating 2.0 A @ 30.0 V
1.0 A @ 120.0 V
Width[Nominal] 1.7 in
Page 1 of 1GE Security - Products