PROJECT REVIEW COMMENTS
DATE: 7/7/10
TO: sparks@vailplazahotel.com
PERMIT APPLICATION #: B10-0135
PROJECT ADDRESS: 16 Vail Road
OCCUPANCY GROUP: mixed
TYPE OF CONSTRUCTION: IB
NUMBER OF STORIES: existing
BUILDING AREA: existing
● Submit three complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING DEPARTMENT COMMENTS
Architectural Comments:
1 Revise sheet A1.0 to indicate the construction type as I-B per TOV records
2 Revise plans to provide minimum clearances to combustibles and a non-combustible hearth per table 4 (page 3) of the ICC ES report number ESR-2401for the Mason-lite fireplace. Refer
to ICC ES report section 5.1 conditions of use. The ICC ES report governs the installation requirements, the letter written by Bill Harris is in conflict with the requirements of the
ICC ES report and listing.
3 Show 2 hour shaft wall construction for the chimney venting per IBC 708.4
Plumbing Comments:
4 Include a gas pipe plan with CFH and gas pipe sizing stamped by a Colorado State Licensed Engineer. Verify BTU input of proposed gas log set.
Mechanical Comments:
5 Include a venting and combustion air plan for the fireplace stamped by a Colorado State Licensed Engineer. Please note the maximum listed height is 40’ for the chimney per section
3.2 of the ICC ES report.