5809
WIRELESS HEAT DETECTOR �'
��
"�
,�
Honeywell's 5809 wireless fixed heat and rate-of-rise surrounding area. The 5809's rate-of-rise thermostat senses
temperature sensor offers expanded fire detection and the rise in temperature and signals an alarm if the increase is
installation flexibility. It is ideal for hard to wire locations and 15° or more per minute. A built-in fixed temperature sensor
applications that require more than smoke detection. With no will also signal an alarm if the environmental temperature rises
wires to run, the 5809 is fast and easy to install. above 135°F. The 5809 is UL Listed (UL521) and CSFM
The 5809 combines both rate-of-rise and fixed temperature approved for commercial and residential applications.
sensors. Fires typically cause a rapid rise in temperature in the
FEATURES
• Contains a built-in transmitter which battery. If the battery voltage gets too the control if the unit is removed from
can send alarm, supervisory and low, the 5809 sends a low battery the mounting base
battery condition messages to the signal to the control panel . UL Listed for Commercial (when using
system's receiver/control unit . Features a tamper switch, which 5881 EH Receiver)or Residential
• Powered by a three-volt lithium causes a trouble signal to be sent to applications
5809
WIRELESS HEAT DETECTOR
SPECIFICATIONS:
• Power: - Fixed temperature: 135°F(57°C) Residential applications
- 3V lithium battery(Duracell DL123A, - Maximum spacing: 50 ft x 50 ft UL,
•Wireless Transmission Path Test:
Panasonic CR123A, Sanyo CR123A, 30 ft x 30 ft FM (refer to National Fire _A good RF transmission path must
Varta CR123A) Alarm Code Standard NFPA 72 for be established from the proposed
- Operating temperature: 40°to application requirements) mounting location before permanently
140°F(6°to 60°C) - Dimensions: 4.4" diameter/2/2"
- Rate-of-rise temperature: 15°F(8°C) deep installing the detector. To determine
that there is a good signal reception
increase per minute (NOTE: Rate-of- .Agency Listings: from the proposed location, perform
rise sensor does not operate above _ UL 521 Listed for Commercial the test procedure described in the
38�C� (when using 5881 EH Fieceiver) or installation instructions procedure.
MOUNTING THE DETECTOR:
- You can mount the 5809 on a wall or - Refer to NFPA Standard 72 for be used for property protection.
ceiling within the protection area: detector spacing and other Reliance should not be placed soley
- Wall mounting: Mount the detector requirements. Maximum spacing for on heat detectors for life safety.
4" 6" from the ceiling UL installations is 50' x 50' When life safety is involved, smoke
Ceiling mounting: Mount the detector - Avoid mounting the detector near detectors MUST also be used.
at least 4" from any wall. Make sure heat generating devices (e.g. ovens, Detectors must not be painted.
the normal ceiling temperature will not heat vents, furnaces, boilers)
exceed 100°F (37.8° C). IMPORTANT: Heat detectors should
TESTING THE DETECTOR:
The test procedure should be performed - Use either method (a) or(b) or activate - Exit the control's test mode
to determine a good RF transmission the detector FCC ID: CFS 8DL 5809
path and again after installation is
(a) Press and release the activation This device complies with part 15 of
completed.
button on the PC board assembly OR FCC rules.
CAUTION:The fixed temperature sensor (b) Holding a portable hair dryer about
Operation is subject to the following
is intended for one-time use. Prolonged 12 to 18 inches away from the detector,
conditions:
heat during testing can damage the unit. turn the dryer on and aim the warm air
(1)This device may not cause harmful
If used carefully following the instructions at the side of the detector.
interference, and (2)this device must
described below, the heat from a portable CAUTION:Aiming the dryer directly at accept any interference received,
hair dryer can be used to test the unit. If the round disk on the detector can
including interference that may cause
the round disk on top of the detector damage the unit to be replaced.
undesired operation.
detaches, the detector must be replaced. -The system's keypad should beep and
- Activiate the control panel's test mode the detector's ID should be displayed