C01224T
Carbon Monoxide � �
Detector �
,
�
with RealTestTmTechnology A ,�„_ _
��.Y�� � �
The System Sensor C01224T CO detector provides early = _ . �� �,�:
warning by using electrochemical sensing technology
to measure carbon monoxide levels in the air.
Features With RealTest`"technology,the CO gas sensing cell of the
•RealTest�"technology allows installer to test detector with CO gas C01224T CO detector can be tested using a carbon monoxide gas
agent Simply hold the test button for two seconds.After the alarm
•Full compliance with UL 2075 cyde(temp 4)the green LED will flash about once per second,
•A code required trouble relay indicating that the detector is ready to accept CO for testing.
•Wiring supervision with SEMS terminals Spray a small amount of CO into the detector per the installation
instructions,and within seconds the detector will alarm,indicating
•A six year end-of-life timer successful gas entry.
•12/24 VDC
•A current draw of 20mA in standby and 40mA in alarm If dangerous amounts of carbon monoxide is detected,the C01224T
detector will alert residents by sounding and flashing a temp-4 signal
•Versatile mounting for wall and ceiling alarm.Protection is guaranteed 24/7 by a central station,regardless
•Electrochemical sensing technology of whether residents are away from home,sleeping or already
suffering from the efFects of C0.
This specific device is designed for system operation.The detector is
fully listed to UL 2075.It offers a code required trouble relay to send
a sensor failure or end-of-life signal to the control panel and the
central station.It also uses SEMS-type terminal Philips head screws
to provide a quicker and more positive wiring connection and code
required wiring supervision.The C01224T detector offers a low
current draw,allowing more devices to be connected to the panel
without having to purchase a more expensive panel or an extra
power supply.
The C01224T model will operate on most industry security and fire
Agency Listings alarm control panels because it is is a 12/24VDC detector.
U`
LISTED
�o�s
C01224T Carbon Monoxide Detector Specifications
Carbon monoxide detector shall be a System Sensor model number C01224T,listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and
Sensors.The detector shall be equipped with a sounder and a trouble relay.The detector's base shall be able to mount to a single-gang electrical box or direct
(surface)mount to the wall or ceiling.Wiring connections shall be made by means of SEMS screws.The detector shall provide dual color LED indication,which
blinks to indicate normal standby,alarm,or end-of-Iife.When the sensor supervision is in a trouble condition,the detector shall send a trouble signal to the
panel.When the detector gives a trouble or end-of-life signal,the detector shall be replaced.The detector shall provide a means to test CO gas entry into the CO
sensing cell.The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.
Operating Voltage 12/24 VDC
Audible Signal 85 dB in alarm
Standby Current 20 mA
Alarm Current 40 mA(75 mA test)
Alarm Contact Ratings 0.5 A@ 30 VDC
Trouble Contact Ratings 0.5 A@ 30 VDC
Size Length:5.1 in,Width: 33 in,Height:13 in
Approximate Weight 7 oz
Operating Temperature Range 32°F to 104°F(0°C to 40°C)
Operating Humidity Range 22 to 90%RH
InputTerminals 14 to 22 AWG
Mounting Single gang back box;surface mount to wall or ceiling
Operation Modes
.. - � - �
Normal(standby) Blink 1 per minute — —
Alarm — Blink in temp 4 pattem Sound in temp 4 pattern
RealTest""Feature: The System Sensor C01�24T carbon monoxide detector with RealTest` can evaluate the functionality of the CO sensing cell using
canned tcst agent.
- . . <�
_ �� �_ \
^ • • � �- i�� r � I�
� �:
� �
Push and hold theTest/Hush button for Spray canned CO agent Into the detector. Verify CO sensing at the control panel.The
two seconds to enter RealTest mode.The detector will automatically exit RealTest
green LED will flash once every second to alarm mode after about 20 60 seconds.
indicate RealTest mode has started.
NOTE:Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an Installation.
Hush Feature: Pushing theTest/Hush button will silence the sounder for S minutes(except in RealTest mode).
Trouble Feature: When the detector is in a trouble condition,it will send a trouble signal to the panel.
End of IifeTimer: After the detector's internal sensor has reached the end of its life,a trouble signal will be sent to the panel.This will indicate that it is
time to replace the detector.An electrochemical carbon monoxide detector lifespan is approximately six years,and the detector must
be replaced by the date marked on the inside of the product.
Ordering Information
�-
C01224T 12/24 volt,4 wire system monitored carbon monoxide detector with RealTest""Technology