PROJECT REVIEW COMMENTS
Second Check comments are shown below original comments in bold italics
DATE: 7/14/10
TO: Geyer Construction
pgeyerconstruction@gmail.com
PERMIT APPLICATION #: B10-0129
PROJECT ADDRESS: 610 W Lionshead #701
OCCUPANCY GROUP: R2
TYPE OF CONSTRUCTION: IB
NUMBER OF STORIES: existing
BUILDING AREA: existing
● Submit two complete sets of revised construction documents containing the requested information with all plan revision items clouded or otherwise identified.
● Please respond in writing to each comment with a response letter addressing each comment.
BUILDING DEPARTMENT COMMENTS
Architectural Comments:
1 Indicate building construction type per IBC ch. 6 on the plans. Town of Vail records indicate IB construction type for the Landmark building. Please include construction type and
code summary on the full size plan sheets
2 Indicate on plans all new framing to be non-combustible construction. Include wall and ceiling construction details. IBC 602.2.
Revise structural plans to provide non-combustible framing per IBC 602.2 for the new loft floor area and stairs. Also include 2 hour floor/ceiling assembly per IBC table 601. Fire
treated wood is not permitted for structural floors, or stairs. IBC 603 item 25
5 Show stairway construction with non-combustible framing per IBC 1009.6
Revise structural plans to provide non-combustible framing per IBC 602.2 for the new floor area and stairs. Also include 2 hour floor/ceiling assembly per IBC table 601. Fire treated
wood is not permitted for structural floors, or stairs. IBC 603 item 25
Structural Comments:
Clarify scope of structural work, include structural sheets in the plan sets
Revise structural plans to provide non-combustible framing per IBC 602.2 for the new floor area and stairs. Also include 2 hour floor/ceiling assembly per IBC table 601. Fire treated
wood is not permitted for structural floors, or stairs. IBC 603 item 25
Special inspection is required for structural steel and welding per IBC ch. 17. Complete the attached Town of Vail special inspection program forms page 3 and 4.