Loading...
HomeMy WebLinkAboutA10-0053 Heat Detectors �� SYSTEM � ��� SENSOR° �` -___.� � , '� BI 5600 Series Mechanical � ` Heat Detectors ��� � � + _� � . _ ...s. � � �, System Sensor's 5600 series mechanical heat detectors '� offer a low-cost means for property protection against ; � � fire, and for non-life-safety installations where smoke �` � ,,� detectors are inappropriate. `__ ?�,������� �':-` - , Features Multiple configurations.The 5600 series offers a full-line of •Multiple configurations for installations configurations to accommodate a broad range of applications.Both —Single-and dual-circuit models single-and dual-circuit models are available for low-and high- —Fixed temp and combination fixed-temp/rate-of-rise temperature ratings with either fixed temperature or combination 135°F or 194°F ratings. fixed temperature/rate-of-rise(ROR)activation.The ROR element of the fixed/ROR models is restorable to accommodate field-testing. •Plain housing for residential installations(Model 5601 P) •Easy-to use terminal screws Installation flexibility.To satisfy a variety of installation needs, •A broad range of back box mounting options: the 5600 series easily mounts to single-gang and octagonal back —Single gang boxes.And these models accommodate four-square back boxes, —3.5""and 4"Octagonal when used with a square to round plaster ring.The reversible —4""square with square to round plaster ring mounting bracket permits both flush-and surface-mount back box installations. •Reversible mounting bracket Visual identification.The 5600 series provides dear markings on the exterior of the unit to ensure that the proper detector is being used.Alphanumeric characters identify the activation method,as well as the temperature rating,in Fahrenheit and Celsius degrees. Fixed temperature models are identified FX,while combination fixed/rate of-rise units are marked FX/ROR.The 5600 series also provides a post-activation indicator in the form of a collector.When the detector is activated,the collector drops from the unit,making it easy to identify the unit in alarm. Agency Listings � u� F M MEA «(�� a roved ��'°°'° LISTED APPROVED pp s_,oi io,aoce i.�-os-e ;zio-;zo���zz, Specifications Mechanical heat detector shall be a System Sensor 5600 series model number ,listed to Underwriters Laboratories UL 521 for Heat Detectors for Fire Protective Signaling Systems.The detector shall be either a single circuit or a dual-circuit type,normally open.The detector shall be rated for activation at either 135°F(57°C)or 194°F(90°C),and shall activate by means of a fixed temperature thermal sensor,or a combination fixed temperature/rate-of-rise thermal sensor. The rate of rise element shall be activated by a rapid rise in temperature,approximately 15°F(83°C)per minute.The detector shall indude a reversible mounting bracket for mounting to 3'/z-inch and 4-inch octagonal,single gang,and 4-inch square back boxes with a square to round plaster ring.Wiring connections shall be made by means of SEMS screws that shall accommodate 14-22AWG wire.The detector shall contain alphanumeric markings on the exterlor of the housing to identify its temperature rating and activation method.The rate of rise element of combination fixed temperature/rate of rise models shall be restorable,to allow for field-testing.The detectors shall indude an external collector that shall drop upon activation to identify the unit in alarm. •. Maximum Installation Temperature 5601 P,5603,5621,and 5623:100°F(38°C) 5602,5604,5622,and 5624:150°F(65.6°Q Operating Humidity Range 5 to 95%RH non-condensing Dimensions with mounting bracket Diameter:4.57 inches(11.6cm) Height: 1.69 inches(43cm) Alarm Temperature 5601 P,5603,5621,and 5623:135°F(57°C) 5602,5604,5622,and 5624:194°F(90°C) Weight 6 oz(170 grams) Rate-of-RiseThreshold 15°F(83°Q rise per minute(models 5601 P,5602,5621,and 5622 only) Mounting 3Yrinch octagonal back box 4 inch octagonal back box Single gang back box 4-inch square back box with a square to round plaster ring . . Operating Voltage/Contact Ratings 6-125VAC/3A 6-28VDC/1 A 125VDC/03A 250VDC/O.IA InputTerminals 14-22 AWG eoai� xi xi aoaixi O O O O O �4� � � o � � i � i- � 5607P 5602,5622 5603,5623 5604,5624 5621 Ordering Information - - � 5601 P Single None 135°F(57°C) Fixed Temperature/Rate of Rise 50 feet x 50 feet(15.24m x 15.2m) 5602 Single Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 152m) 5603 Single Lettering 135°F(57°Q Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5604 Single Lettering 194°F(90°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5621 Dual Lettering 135°F(57°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 152m) 5622 Dual Lettering 194°F(90°C) Fixed Temperature/Rate-of-Rise 50 feet x 50 feet(1524m x 15Zm) 5623 Dual Lettering 135°F(57°C) Fixed Temperature 25 feet x 25 feet(7.62m x 7.62m) 5624 Dual Lettering 194°F(90°Q Fixed Temperature 25 feet x 25 feet(7.62m x 7b2m) *NOTE:Refer to NFPA72 guidelines for spacing reductions when ceiling heights exceed 10 feet. l\��� �\��� �ZOCE �_tc n Sen� �� �� 3825 Ohio Avenue•St.Charles,IL 60174 ��a��rspe<�fi��o�ss�u,��<<o�rz ge �mou�,���<e.u�s��sys�emsenso�-�omro� ��� �����R� PhOIl2:80�-SENS�RZ•FdX:63�-3��-6495 currenrproduainformation,�mdudingthelares[verslonofthlsdatasheet. A05-0351-002•11/06•i31676