HomeMy WebLinkAboutField Equipment Controller Code No. LIT-1900346
• �
, � Issued October 6, 2008
Field Equipment Controller (FEC) Series
Description • Writable flash memory allows you to
The FEC is a programmable digital controller download standard or customized ` -_��y��,;�,��-�-;;�-_�.._��l��� ���
that communicates via BACnetO applications from the Controller �
Master-Slave/Token Passing(MS/TP) Configuration Tool(CCT)software.
protocol.The controllers featured in this family ' Removable base allows the base to be
ordered,mounted,and pre-wired without �'mm^ '
are the 10-point FEC16x0 and the 17-point �'_ ° '��
FEC26x0.Some models also feature a built-in the controller electronics. �un� � �
Liquid Crystal Display(LCD)screen that • Universal and configurable inputs and , .
serves as a local user interface to the outputs support multiple signal options and � � 0
application in the device. increase controller application flexibility. ��� ______ ���.....��
A full range of FEC models combined with the ' Different models provide a wide range of ��,�^"�
In ut/Out ut Module IOM models can be point mix to meet application requirements
p p � � and allow for the addition of one or more FEC2620
applied to a wide variety of building Input/Output Modules(IOMs)and/or
applications ranging from simple fan coil or Network Sensors to provide even more • Wireless capabilities via ZFR1800 Series
heat pump control,to advanced central plant application capacity. Wireless Field Bus System enable wireless
management.
• Ability to be automatically discovered by mesh connectivity between FECs to WRZ
Refer to the Metasys System Field Equipment Network Automation Engines(NAEs)and Series Wireless Room Temperature
Controllers, Network Sensors, and Related Network Control Engines(NCEs)allowsfor Sensors,and to NAE/NCE devices.This
Products Product Bulletin(LIT-12011042)for easy controller integration. facilitates easy initial location and
important product application information. • Local user intertace display option(integral relocation.
display or stand-alone display) Repair Information
Features
• Continuous loop tuning provided by If the Field Equipment Controller fails to
patented proportional adaptive control operate within its specifications,replace the
(P-Adaptive)and Pattern Recognition unit. For a replacement FEC,contact the
Adaptive Control(PRAC)technologies. nearest Johnson Controls0 representative.
• BACnet MS/TP communication provides
open system compatibility.
Selection Charts
Point Type Counts per Model
Point Types Signals Accepted FEC1610 FEC2610
FEC1620 FEC2620
Universal Input(UI) Analog Input,Voltage Mode,0-10 VDC;Analog Input,Current Mode,4-20 mA;Analog Input,Resistive 2 6
Mode,0-2k ohm,RTD(1k NI[Johnson Controls],1k PT,A996 SI),NTC(10k Type L,2252k Type 2);
Binary Input,Dry Contact Maintained Mode
Binary Input(BI) Dry Contact Maintained Mode;Pulse Counter Mode(High Speed),100 Hz 1 2
Analog Output(AO) Analog Output,Voltage Mode,0-10 VDC;Analog Output,Current Mode,4-20 mA 0 2
Binary Output(BO) 24 VAC Triac 3 3
Configurable Output(CO) Analog Output,Voltage Mode,0-10 VDC;Binary Output Mode,24 VAC Triac 4 4
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
1 of 3
• �
• �
Field Equipment Controller (FEC) Series (Continued)
The FEC(MS-FEUx610-0)consists of two parts,which are also available separately:mounting base(MS-FEBx610-0)and the controller cover
(MS-FECx6x0-0). FEU=FEB+FEC.
Ordering Information
Product Code Description
Number
MS-FEU1610-0 10-Point Field Equipment Controller with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus;Mounting Base
MS-FEU1610-OU 10-Point Field Equipment Controller with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus;Mounting Base
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-FEC1610-0 Field Equipment Controller Cover with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus
MS-FEB1610-0 Triac Mounting Base for FEC16x0
MS-FEU1620-0 10-Point Field Equipment Controller with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus;Mounting Base;Integral Display
MS-FEU1620-OU 10-Point Field Equipment Controller with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus;Mounting Base;Integral Display
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-FEC1620-0 Field Equipment Controller Cover with 2 UI,1 BI,3 BO,and 4 CO;24 VAC;SA Bus;Integral Display
MS-FEU2610-0 17-Point Field Equipment Controller with 6 UI,2 BI,3 BO,2 AO,and 4 CO;24 VAC;SA Bus;Mounting Base
MS-FEU2610-OU 17-Point Field Equipment Controller with 6 UI,2 BI,3 BO,2 AO,and 4 CO;24 VAC;SA Bus;Mounting Base
Nate: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-FEC2610-0 Field Equipment Controller Cover with 6 UI,2 BI,3 BO,2 AO,and 4 CO;24 VAC;SA Bus
MS-FEB2610-0 Triac Mounting Base for FEC26x0
MS-FEC2620-0 17-Point Field Equipment Controller with 6 UI,2 BI,3 BO,2 AO and 4 CO;24 VAC;SA Bus;Integral Display
MS-FEU2620-0 Field Equipment Controller Cover with 6 UI,2 BI,3 BO,2 AO,and 4 CO;24 VAC;SA Bus;Mounting Base;Integral Display
MS-FEU2620-OU Field Equipment Controller Cover with 6 UI,2 BI,3 BO,2 AO,and 4 CO;24 VAC;SA Bus;Mounting Base;Integral Display
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
Accessories
Product Code Description
Number
Y64T15-0 Transformer,120/208/240 VAC Primary to 24 VAC Secondary,92 VA,Foot Mount,30 in.Primary Leads and 30 in.Secondary Leads,
Class 2
Y65A13-0 Transformer,120 VAC Primary to 24 VAC Secondary,40 VA,Foot Mount[Y65AS],8 in.Primary Leads and 30 in.Secondary Leads,Class 2
Y65T42-0 Transformer,120/208/240 VAC Primary to 24 VAC Secondary,40 VA,Hub Mount[Y65SP+],g in.Primary Leads and Secondary Screw
Terminals,Class 2
Y65T31-0 Transformer,120/208/240 VAC Primary to 24 VAC Secondary,40 VA,Foot Mount[Y65AR+],S in.Primary Leads and Secondary Screw
Terminals,Class 2
AP-TBK4SA-0 Replacement MS/TP SA Bus Terminal,4 Position Connector,Brown,Bulk Pack
AP-TBK4FC-0 Replacement MS/TP FC Bus Terminal,4 Position Connector,Blue,Bulk Pack
AP-TBK3PW-0 Replacement Power Terminal,3 Position Connector,Gray,Bulk Pack
MS-BTCVTCBL-700 Cable replacement Set for the MS-BTCVT-1 or the NS-ATV7003-0;includes one 5-foot retractable cable.
MS-DIS1710-0 Local Controller Display for FEC1610 and FEC2610 Models
MS-ZFR1810-0 Wireless Field Bus Coordinator,10 mW Transmission Power.Functions with NAE35xx,NAE45xx,NAE55xx,and NCE25xx models.
MS-ZFR1811-0 Wireless Field Bus Router,10 mW Transmission Power.Functions with Metasys BACnet FECs,VMA1600s,and WRZ-TTx Series Wireless
Mesh Room Temperature Sensors.
MS-ZFRCBL-0 Wire Harness for use with MS-ZFR1811-0 Wireless Field Bus Router.Allows ZFR1811 Router to function with FEC1620;and with FEC1610,
VMA1610,or VMA1620 controllers in conjunction with NS Series Sensors.Wireless Commissioning Converter,or DIS1710 Local Controller
Display.
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
2 of 3
• �
• �
Field Equipment Controller (FEC) Series (Continued)
Technical Specifications
Field Equipment Controller(FEC)Series
Product Code Numbers MS-FEC1610-0-Cover
MS-FEB1610-0-Triac Mounting Base
MS-FEU1610-0-Cover and Triac Mounting Base
MS-FEC2610-0-Cover
MS-FEB2610-0-Triac Mounting Base
MS-FEU2610-0-Cover and Triac Mounting Base
MS-FEC1620-0-Cover with Integral Display
MS-FEU1620-0-Cover with Integral Display and Triac Mounting Base
MS-FEC2620-0-Cover with Integral Display
MS-FEU2620-0-Cover with Integral Display and Triac Mounting Base
Supply Voltage 20-30 VAC at 50 or 60 Hz,Class 2 or Safety Extra-Low Voltage(SELV)
Power Consumption 10 VA typical,14 VA maximum,plus all BO and Configurable Output loads
Ambient Conditions Operating:0 to 50°C(32 to 122°F);10 to 90%RH noncondensing
Storage:-40 to 70°C(-40 to 158°F);10 to 90%RH noncondensing
Terminations Screw Terminals and Screw Terminal Pluggable Blocks
Controller Addressing DIP switch set(4-127).Addresses 0-3,128-255 are reserved.
Communications Bus BACnet MS/TP;3-wire FC Bus between the NAE/NCE and other devices.4-wire SA Bus between network sensors and other
devices.�
Analog InpuUAnalog Output Analog Input:16-bit resolution(15 bit on FEx1610)
Resolution and Accuracy Analog Output:16-bit resolution and±200 mV in 0-10 VDC applications
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail
Compliance United States:
UL Listed,File E107041,CCN PAZX,UL 916,Energy Management Equipment;
UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment(MS-FEU16x0-OU and MS-FEU26x0-OU models
only)
FCC Compliant to CFR47,Part 15,Subpart B,Class A
Canada:
UL Listed,File E107041,CCN PAZX7,CAN/CSA C22.2 No.205,Signal Equipment;
Industry Canada Compliant,ICES-003
Europe:
CE Mark,EMC Directive 89/336/EEC,in accordance with EN 61000-6-3(2001)Generic Emission Standard for Residential
and Light Industry and EN 61000-6-2(2001)Generic Immunity Standard for Heavy Industrial Environment and the Low
Voltage Directive
73/23/EEC in accordance with EN 60730-1 (1999)Automatic electrical controls for household and similar use.
Australia and New Zealand:
C-Tick Mark,Australia/NZ Emissions Compliant
BACnet International:
BACnet Testing LaboratoriesT"^(BTL)135-2004 Listed BACnet Application Specific Controller(B-ASC)
Weight FEC16x0 Models:0.5 kg(1.10 Ib)
FEC26x0 Models:0.68 kg(1.5 Ib)
Dimensions FEC16x0 Models:144 x 127 x 58 mm(5-11/16 x 5 x 2-1/4 in.)
(Height x Width x Depth) FEC26x0 Models:180 x 127 x 58 mm(7-1/16 x 5 x 2-1/4 in.)
Housing Plastic housing
Plastic material:ABS+polycarbonate UL 94-5VB
Protection:IP20(IEC 60529)
1. For more information,refer to the MS/TP Communications Bus Technical Bulletin(LIT-12011034).
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
3 of 3