HomeMy WebLinkAboutNetwork Automation Engine Code No. LIT-1900195
• �
, � Issued October 6, 2008
MS-NAE35xx-x, MS-NAE45xx-x, MS-NAE55xx-x, NAE8500-x
Network Automation Engine (NAE)
Description Refer to the Network Automation Engine
The Network Automation Engine(NAE)brings �'roduct Bulletin(LIT-1201160)for important
product application information.
an entirely new generation of technology into ( �,
the Metasys0 Building Automation System Features ���"''• � � �
(BAS).The NAE is an automation engine that "�'--__ _
manages facilities using information and • communication using commonly accepted
•
Internet technology. IT standards at the automation and � <«t R���,�
The NAE uses the communication enterprise level ��M �+�""
technologies of the building automation ' Web-based user interface _
industry,induding BACnetO protocol; • Site Director function
LoNWoRKSO network;the N2 Bus to monitor; ' support for Web services at the automation
supervise Heating,Ventilating,and Air network level
Conditioning(HVAC)equipment;and lighting, • user interFace and online system NAE35/NAE45
security,fire,and access control.The NAE55 configuration software embedded in NAE
supports a comprehensive set of supervisory • supervision of field controller networks
features and functions for large facilities and including N2 Bus,LorvWoRKS network, ' �6'*`^ �-�; .��
technically advanced buildings and BACnet MS/TP,and BACnet IP devices � � "' �'� L'�"`y'}��
complexes.The NAE35 and NAE45 extend • multiple connection options for data ` �+`
the power of the NAE to smaller buildings and access �
enable the wider distribution of supervisory �
functions in larger facilities.The NAE85 is a Applications ►�
high-capacity NAE.This device allows the w
The NAE software is specifically designed to #
integration of large BACnet Internet Protocol meet the needs of building owners and �• , ,"",
(IP)systems and can take the place of multiple managers to efficiently monitor and control all �
NAEs. the mechanical and electrical systems in a
A single NAE or a network of multiple NAE typical building such as:
devices within a building provide monitoring . HVAC units
and control,alarm and event management, NAE55
data exchange,trending,energy ' central equipment including chillers and
management,scheduling,and data storage. boilers Repair Information
• lighting and electrical distribution
The NAE has an embedded Site Management . po�n,er generation and energy monitoring If the NAE fails to operate within its
Portal user interface and supports equipment specifications,refer to the Network
concurrently connected Web browsers with . intertaces to security and fire detection Automation Engine(NAE)Product Bulletin
password access control and the security (LIT-1201160)for a list of repair parts
protection technology of the Information systems available.
Technology(IT)industry. The NAE monitors equipment by collecting
data from the field control devices,then
coordinating the required commands and
sending them to the equipment at the required
priority.
Selection Charts
NAE35 (Part 1 of 2)
Product Code Description
Number�
MS-NAE35xx-x NAE35 Network Automation Engines:Requires a 24 VAC power supply.Each model includes one RS-232-C serial port,one USB serial port,
(Base Features of one Ethernet port,and an MS-BAT1020-0 Data Protection Battery.
Each NAE35)
MS-NAE3510-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an additional RS-232-C serial port for optional external modem;supports up to
50 devices on the N2 or BACnet MS/TP trunk.
MS-NAE3510-2U Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an additional RS-232-C serial port for optional external modem;supports up to
50 devices on the N2 or BACnet MS/TP trunk.
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-NAE3511-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an internal modem;supports up to 50 devices on the N2 or BACnet MS/TP trunk.
MS-NAE3514-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;features Basic Access support;includes an additional RS-232-C serial port for optional
external modem;supports up to 50 devices on the N2 or BACnet MS/TP trunk.
MS-NAE3515-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;features Basic Access support;includes an internal modem;supports up to 50 devices on
the N2 or BACnet MS/TP trunk.
MS-NAE3520-2 Supports one LONWORKS trunk,includes an additional RS-232-C serial port for optional external modem.Supports up to 64 devices on the
LoNWORKS port.
MS-NAE3520-2U Supports one LONWORKS trunk,includes an additional RS-232-C serial port for optional external modem.Supports up to 64 devices on the
LoNWORKS port.
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
1 of 5
• �
• �
Network Automation Engine (NAE) (Continued)
NAE35 (Part 2 of 2)
Product Code Description
Number�
MS-NAE3521-2 Supports one LoNWORKS trunk,includes an internal modem.Supports up to 64 devices on the LONWORKS port.
MS-NAE3524-2 Supports one LorvWORKS trunk,features Basic Access support,and includes an additional RS-232-C serial port for optional external modem.
Supports up to 64 devices on the LoNWORKS trunks.
MS-NAE3525-2 Supports one LoNWORKS trunk,features Basic Access support,and includes an internal modem.Supports up to 64 devices on the
LONWORKS trunks.
1. All models are also available in a Buy American version(add a G after the code number).For the European version,add an E after the code number.For repair
parts,add-702 after the code number.
NAE45
Product Code Description
Number�
MS-NAE45xx-x NAE45 Network Automation Engines:Requires a 24 VAC power supply.Each model includes one RS-232-C serial port,one USB serial port,
(Base features of one Ethernet port,and an MS-BAT1020-0 Data Protection Battery.
each NAE45)
MS-NAE4510-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an additional RS-232-C serial port for optional external modem;supports up to
100 devices on the N2 or BACnet MS/TP trunk.
MS-NAE4510-2U Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an additional RS-232-C serial port for optional external modem;supports up to
100 devices on the N2 or BACnet MS/TP trunk.
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-NAE4511-2 Supports one N2 or BACnet MS/TP(RS-485)trunk;includes an internal modem;supports up to 100 devices on the N2 or BACnet MS/TP
trunk.
MS-NAE4520-2 Supports one LONWORKS trunk,includes an additional RS-232-C serial port for optional external modem;supports up to 127 devices on the
LoNWORKS port.
MS-NAE4520-2U Supports one LoNWORKS trunk,includes an additional RS-232-C serial port for optional external modem;supports up to 127 devices on the
LONWORKS pOrt.
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-NAE4521-2 Supports one LoNWORKS trunk,includes an internal modem;supports up to 127 devices on the LoNWORKS port.
1. All models are also available in a Buy American version(add a G after the code number).For the European version,add an E after the code number.For repair
parts,add-702 after the code number.
NAE55
Product Code Description
Number�
MS-NAESSxx-x NAE55 Network Automation Engines:Requires a 24 VAC power supply.Each model includes two RS-232-C serial ports,two USB serial ports,
(Base features of two RS-485 ports,one Ethernet port,and one MS-BAT1010-0 Data Protection Battery.Supports up to 100 devices on each N2 or
each NAE55) BACnet MS/TP trunk.
MS-NAE5510-1 Supports two N2 or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk).
MS-NAE5510-OU Supports two N2 or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk).
Note; This model is UL Listed,UUKL 864 8th Edition Smoke Control Equipment and is available for replacement in or expansion of existing
UUKL 864 8th Edition Metasys smoke control applications only.
MS-NAE5510-1 U Supports two N2 or two BACnet MS/TP trunks(or one N2 trunk and one BACnet MS/TP trunk).
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-NAE5511-1 Supports two N2 or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk);includes an internal modem.
MS-NAE5512-1 Supports two N2 or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk).
Note: MS-NAE5512-1 models support N2 tunneling on N2 trunks(only).
MS-NAE5513-1 Supports two N2 or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk);includes an internal modem.
Note: MS-NAE5513-1 models support N2 tunneling on N2 trunks(only).
MS-NAE5520-1 Supports a LONWORKS trunk,and two N2 trunks or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk).
Supports up to 255 devices on the LoNWORKS trunk.
MS-NAE5520-1 U Supports a LoNWORKS trunk,and two N2 trunks or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk).
Supports up to 255 devices on the LoNWORKS trunk.
Note: This model is UL Listed,File S4977,UUKL 864-9th Edition,Smoke Control Equipment.
MS-NAE5521-1 Supports a LOrvWORKS trunk,and iwo N2 trunks or two BACnet MS/TP(RS-485)trunks(or one N2 trunk and one BACnet MS/TP trunk);
includes an internal modem.Supports up to 255 devices on the LONWORKS trunk.
1. All models are also available in a Buy American version(add a G after the code number).For the European version,add an E after the code number.For repair
parts,add-701 after the code number.
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
2 of 5
• �
• �
Network Automation Engine (NAE) (Continued)
NAE85
Product Code Description
Number
MS-NIE8500-0� NxE85 model with 1 U chassis for mounting in a server rack
Note: The NAE85 models ship as MS-NIE8500-0 models.Use the ChangeModel utility in the NxE85 Metasys software to change an NIE85 to
an NAE85.
MS-NxE85SW-0 NxE85 software for 10,000 objects(new projects only software)
1. Standard NxE85 models supports 10,000 objects;an upgrade is available to support an additional 15,000 objects.
Accessories
Product Code Description
Number
MS-BAT1010-0 Replacement data protection battery for NAE55 and NIE55.Rechargeable gel cell battery:12 V, 12 Ah,with a typical life of 3 to 5 years at
21°C(70°F)
MS-BAT1020-0 Replacement data protection battery for NAE35,NAE45,and NCE25.Rechargeable NiMH battery:3.6 V 500 mAh,with a typical life of
10 years at 21°C(70°F)
MS-15KUPG-0 15,000 object upgrade for NxE85
MS-NAETUNL-8 ToggleTunnel utility for converting an NAE55/NIE55 to an NAE55 model with the N2 Tunneling and Wireless N2 Field Bus features enabled.
Not for use with MS-NAE5510-OU or MS-NIE5510-OU.
MS-RAP-O Ready Access Portal Server provides a user intertace that is a natural,complementary extension of the Metasys Site Management Portal user
interface.
Note: This option is not necessary for sites that have an ADS/ADX that is the Site Director because Ready Access Portal Server is provided
with the ADS/ADX solution.
MS-EXPORT-0 Export Utility extracts historical trend,alarm,and audit data from the system and presents the historical data in a variety of formats.
Note: This option is not necessary for sites that have an ADS/ADX that is the Site Director because Export Utility is provided with the ADS/
ADX solution.
AS-XFR100-1 Power transformer(Class 2,24 VAC,92 VA maximum output),with enclosure
AS•XFR010-1 Power transformer(Class 2,24 VAC,92 VA maximum output),no enclosure
SC450RM1U Recommended Uninterruptable Power Supply(UPS)for NxE85 Models:American Power Conversion(APCRO)Smart-UPS SC 450VA,280 W
(OEM Part No.) 120 VAC inpuUoutput with NEMA 5-15R output connections
Technical Specifications
NAE35 and NAE45(Part 1 of 2)
Power Requirement Dedicated nominal 24 VAC,Class 2 power supply(North America),Safety Extra-Low Voltage(SELV)power supply(Europe),
at 50/60 Hz(20 VAC minimum to 30 VAC maximum)
Power Consumption 25 VA maximum
Ambient Opereting Conditions 0 to 50°C(32 to 122°F);10 to 90%RH,30°C(86°F)maximum dew point
Ambient Storage Conditions -40 to 70°C(-40 to 158°F);5 to 95%RH,30°C(86°F)maximum dew point
Data Protection Supports data protection on power failure.Rechargeable NiMH battery:3.6 VDC 500 mAh,with a typical life of 5 to 7 years at
21°C(70°F);Product Code Number:MS-BAT1020-0
Processor 192 MHz RenesasT""SH4 7760 RISC processor
Memory 128 MB Flash nonvolatile memory for operating system,configuration data,and operations data storage and backup
128 MB Synchronous Dynamic Random Access Memory(DRAM)for operations data dynamic memory
Opereting System Microsoft0 Windows0 CE embedded
Network and Serial Interfaces One Ethernet port;10/100 Mbps;8-pin RJ-45 connector
One optically isolated RS-485 port;9600,19.2k,38.4k,or 76.8k baud(depending on protocol);with a pluggable and keyed
4-position terminal block(FC Bus available on NAE351x and NAE451x models only)
One LONWORKS port;FTT10 78 Kbps;pluggable,keyed 3-position terminal block(LONWORKS port available on NAE352x-x
and NAE452x models only)
One RS-232-C serial port with standard 9-pin sub-D connector that supports standard baud rates.
A second serial port,on models without an internal modem,that supports an optional,user-supplied external modem.
One USB serial port with standard USB connector that supports an optional,user-supplied external modem.
Option:One telephone port for internal modem;up to 56 Kbps;6-pin RJ-11 connector(NAE models with an optional internal
modem have one RS-232-C serial port only.)
Housing Plastic housing material:ABS+polycarbonate UL94-5VB
Protection:IP20(IEC 60529)
Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail
Dimensions 131 x 270 x 62 mm(5.2 x 10.6 x 2.5 in.)
(Height x Width x Depth) Minimum space for mounting NAE35 and NAE45:210 x 350 x 110 mm(8.3 x 13.8 x 4.3 in.)
Shipping Weight 1.2 kg(2.7 Ib)
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
3 of 5
• �
• �
Network Automation Engine (NAE) (Continued)
NAE35 and NAE45(Part 2 of 2)
Compliance United States
UL Listed,File E107041,CCN PAZX,UL 916,Energy Management Equipment
UL Listed,Flle S4977,UUKL 864-9th Edition,Smoke Control Equipment(MS-NAE35x0-2U and MS-NAE45x0-2U models
only)
FCC Compliant to CFR47,Part 15,Subpart B,Class A
Canada
UL Listed,File E107041,CCN PAZX7,CAN/CSA C22.2 No.205,Signal Equipment
Industry Canada Compliant,ICES-003
Europe
CE Mark,EMC Directive 89/336/EEC,in accordance with EN 61000-6-3(2001)Generic Emission Standard for Residential and
Light Industry and EN 61000-6-2(2001)Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zealand
C-Tick Mark,Australia/NZ Emissions Compliant
BACnet International
BACnet Testing LaboratoriesT"^(BTL)135-2004 Listed BACnet Building Controller(B-BC)
NAE55
Power Requirement Dedicated nominal 24 VAC,Class 2 power supply(North America),Safety Extra-Low Voltage(SELV)power supply(Europe),at
50/60 Hz(20 VAC minimum to 30 VAC maximum)
Power Consumption 50 VA maximum
Ambient Operating Conditions 0 to 50°C(32 to 122°F);10 to 90%RH,30°C(86°F)maximum dew point
Ambient Storage Conditions -40 to 70°C(-40 to 158°F);5 to 95%RH,30°C(86°F)maximum dew point
Data Protection Battery Supports data protection on power failure.Rechargeable gel cell battery:12 V,12 Ah,with a typical life of 3 to 5 years at 21°C
(70°F);Product Code Number:MS-BAT1010-0
Clock Battery Maintains real-time clock through a power failure.Onboard cell;typical life 10 years at 21°C(70°F)
Processor 300 MHz Pentium0 class GeodeO GX1 MMX enhanced processor for MS-NAE5510-OU
400 MHz Geode GX533 processor for MS-NAE55xx-1 models
Memory 256 MB Flash nonvolatile memory for operating system,configuration data,and operations
data storage and backup for MS-NAE5510-OUmodel
512 MB Flash nonvolatile memory for operating system,configuration data,and operations
data storage and backup for MS-NAE55xx-1 models.
256 MB Synchronous Dynamic Random Access Memory(DRAM)for operations data
dynamic memory for all models
Operating System Microsoft Windows XPOO embedded
Network and Serial Interfaces One Ethernet port;10/100 Mb;8-pin RJ-45 connector
Two optically isolated RS-485 ports;9600,19.2K,or 38.4K baud;pluggable and keyed 4 position terminal blocks(RS-485 ports
available on NAE55 models only)
Two RS-232-C serial ports,with standard 9-pin sub-D connectors,that support all standard baud rates
Two USB serial ports,standard USB connectors support an optional,user-supplied external modem
Options:One telephone port for internal modem;up to 56 Kbps;6-pin RJ-11 connector One LONWORKS port;FTT10 78 Kbps;
pluggable,keyed 3-position terminal block(LONWORKS port available on NAE552x-xxx models only)
Housing Plastic housing with internal metal shield Plastic material:ABS+polycarbonate UL94-5V6
Protection:IP20(IEC 60529)
Mounting On flat surface with screws on four mounting feet or on dual DIN rail
Dimensions 226 x 332 x 96.5 mm(8.9 x 13.1 x 3.8 in.)including mounting feet
(Height x Width x Depth) Minimum space for mounting:303 x 408 x 148 mm(12.0 x 16.1 x 5.8 in.)
Shipping Weight 2.9 kg(6.4 Ib)
Compliance United States
UL Listed,File E107041,CCN PAZX,UL 916,Energy Management Equipment
UL Listed,Flle S4977,UUKL 864-9th Edition,Smoke Control Equipment(MS-NAE55x0-1 U models only)
UL Listed,UUKL 864-8th Edition,Smoke Control Equipment(MS-NAE5510-0 model only)
FCC Compliant to CFR47,Part 15,Subpart B,Class A
Canada
UL Listed,File E107041,CCN PAZX7,CAN/CSA C22.2 No.205,Signal Equipment
Industry Canada Compliant,ICES-003
Europe
CE Mark,EMC Directive 89/336/EEC,in accordance with EN 61000-6-3(2001)Generic Emission Standard for Residential and
Light Industry and EN 61000-6-2(2001)Generic Immunity Standard for Heavy Industrial Environment
Australia and New Zealand
C-Tick Mark,Australia/NZ Emissions Compliant
BACnet International
BACnet Testing Laboratories�"'(BTL)135-2004 Listed BACnet Building Controller(B-BC)
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
4of5
• �
• �
Network Automation Engine (NAE) (Continued)
NAE85
Computer Type DeIIT"^PowerEdge�""R300
Power Requirement 120/240 VAC 50/60 Hz
Power Supply 400 W
Ambient Operating Conditions 10 to 35°C(50 to 95°F);20 to 80%RH(noncondensing twmax=29°C)
Ambient Storege Conditions -40 to 65°C(-40 to 149°F);5 to 95%RH(noncondensing twmax=38°C)
Data Protection Recommended Uninterruptible Power Supply(UPS):American Power Conversion(APCO)Smart-UPS SC 450VA,
280 W,120 VAC input/output,NEMA 5-15R output connections,OEM Part No.SC450RM1 U
Processor Single Dual-Core IntelO Core 2 Duo Processor E6405 at up to 2.13GHz,2MB Cache,1066 MHz
Memory 1 GB DDR2,667 MHZ,1x1GB,Single Ranked DIMMs
Hard Disk 160 GB Serial ATA,72K RPM,3 Gbps
Operating System Microsoft0 Windows0 2003 Server R2 Web Edition
Network and Serial Interfaces Two RJ45 1 Gbps Ethernet Ports:
Port 1:For communicating with the BAS network
Port 2:For communicating with an enterprise network
Two Video ports for monitor;one front,one back
One 9-pin Serial port
Four USB ports(two on front,two on back)
Dimensions 4.2 x 42.6 x 66 cm(1.7 x 16.8 x 26 in.)
(Height x Width x Depth)
Housing Metal
Mounting Mount in an EIA-310D compatible server cabinet
Shipping Weight 13.5 kg(23 Ib)
Compliance Europe:CE Mark
BACnet International
BACnet Testing LaboratoriesT""(BTL)135-2004 Listed BACnet Building Controller(B-BC)
Minimum Computer Requirements for NxE85 Software
Product Code MS-NxE85SW-0 NxE85 software for 10,000 objects(new projects only software)
Recommended Computer Platform Quad-Core IntelO XeonO L5410 processor at 2.33 GHz,12 MB cache,1333 MHz recommended minimum
2x250 GB RAID1 hard disk
DVD-RW drive
Memory 1 GB RAM minimum
Operating System Microsoft Windows 2003 Server R2 Web Edition
Web Browser Microsoft Internet ExplorerRO Version 6.x or Version 7.0 and JRE 1.6.0 07
Communication Network Interface
Single 1 Gbps Ethernet network intertace card 10/100/1000 Mbps(100 Mbps or better recommended)
Data Protection Recommended Uninterruptible Power Supply(UPS):American Power Conversion(APC RO)Smart-UPS SC 450VA,
280 W,120 VAC input/output,NEMA 5-15R output connections,OEM Part No.SC450RM1U
The performance specifications are nominal and conform to acceptable industry standards.For applications at conditions beyond these specifications,consult the local Johnson Controls office.
Johnson Controls,Inc.shall not be liable for damages resulting from misapplication or misuse of its products.O 2008 Johnson Controls,Inc. www.johnsoncontrols.com
5of5