HomeMy WebLinkAboutSurge Suppressor Tripp Lite ISOBAR 12 Ultra Surge Suppressor
Tripp Lite's ISOBARI2ULTRA offers network-grade surge and noise suppression in a versatile
all-metal multi-mount cabinet. Detachable mounting flanges are configurable for rackmount,
wallmount and under-counter installation. Uses only 1 rack space (lU) when installed in any 19
inch EIA standard rack.Features the highest level of AC surge and EMURFI noise suppression of
all Tripp Lite rackmount surge suppressors. Outlets are arranged in exclusive isolated filter banks
to limit noise interaction among connected items. Includes 12 outlets (2 front/ 10 rear), 15 ft AC
power cord and guarded power switch to reduce the risk of accidental shutoff. Diagnostic LEDs
indicate AC present, line fault and protection status.
Front View
•... � +
Fiear Vi�w
, a a � a
a a a a
�� o 0 0 �
�
Figure 22: Tripp Lite Isobar 12 Ultra Surge Suppressor
Metasys0 System ULO 864 UUKL Ninth Edition Smoke Control System Technical Bulletin 43
Specifications
Table 6: Tripp Lite Isobar 12 Ultra Surge Suppressor Specifications
Category Specification
Voltage compatibility 120 VAC
Frequency compatibility 60 Hz
Output volt amp capacity 15 Amps
Output watt capacity 1800 watts
Outlet quantity/type 12 NEMA 5-15R output duplex style receptacles, 2 front/10 rear
Transformer accommodation Supports up to 4 large transformer plug accessories without
covering remaining outlets
Input connection type NEMA 5-15P input plug
Input cord length 15 ft(4.6 m)
Recommended electrical service 120V 15A
Diagnostic LEDs PROTECTION PRESENT(green)
LINE FAULT(red)
LINE OK(green)
Switches Two-position red illuminated on/off power switch to all outlets
Protection modes Includes full normal mode(H-N)and common mode(N-G/H-G)
line surge suppression
AC suppression joule rating 1280 joules
Clamping voltage(RMS) 140V
AC suppression response time NM =0 ns, CM =<1 ns
AC suppression surge current rating 96,000 amps
AC suppression components used Metal oxide varistors, toroidal balanced chokes, and VHF
capacitors.
Safe thermal fusing Prevents unsafe conditions during extreme extended overvoltages
and catastrophic occurrences
UL1499 let through rating 330V-UL Verified
EMI/RFI filtering 40-80 dB
Unit Weight 4.6 Ibs(2.1 kg)
Dimensions(Height x Width x Depth) 2.5 x 9 x 3.5 in (6.4 x 22.9 x 8.9 cm)
Compliance UL1449 (UR status)
UL 1449 1998 Rev. (AC Suppression)
UL 1283 (EMI Filter) UL 1283
cUL/CSA(Canada) cUL
Approvals Exceeds IEEE 587 category A&B specifications
UL Label Placement
UL Listing labels are not required for this product.
44 Metasys0 System ULO 864 UUKL Ninth Edition Smoke Control System Technical Bulletin