Re: Solaris B07-0275 Temp Offices Level 1
Re:
Mike McGee
SMTP
MMcGee@vailgov.com
Mike McGee
SMTP
MMcGee@vailgov.com
Building_Division; Fire_Inspectors; Fire_Officers
Rick Pusch
Solaris B07-0275 Temp Offices Level 1
Rick,
Thank you for the copies of the revisions.
The Temp Office plan is approved as submitted.
The Emergency Access / Egress plan is approved as submitted.
Note: There is no permit fee required for the Emergency / Access plan review. Thank you for keeping us updated.
Thank you,
Michael McGee
Deputy Chief
Vail Fire & Emergency Services
>>> "Rick Pusch" <Rick.Pusch@weitz.com> 03/31/2009 9:35 AM >>>
Mike see attached for the floor plan indicating the routing of egress identified for the Weitz office per our discussion yesterday. I will copy Jen over at the Building dept. with this
information as well.
Let me know if you have any other concerns that I can address.
Thanks for your time.
Rick Pusch
Senior Project Superintendent
The Weitz Co. LLC
143 E. Meadows Drive
Vail, CO. 81657
1-970-478-0201 ext. 307 jobsite phone
1-970-478-1766 fax
303-910-7769 Mobile
rick.pusch@weitz.com
www.weitz.com
BUILD IN GOOD COMPANY
>>> "Mike McGee" <MMcGee@vailgov.com> 3/27/2009 4:01 PM >>>
I have a meeting at 11 AM and a meeting at 1 PM.
You are welcome to come to the Fire Station about 10 AM if that works for your schedule.
Mike
>>> "Rick Pusch" <Rick.Pusch@weitz.com> 03/27/2009 3:11 PM >>>
Mike, can we meet sometime on Monday to review the plan and your requests. Want to make sure we are on the same page.
Thanks
Rick Pusch
Senior Project Superintendent
The Weitz Co. LLC
143 E. Meadows Drive
Vail, CO. 81657
1-970-478-0201 ext. 307 jobsite phone
1-970-478-1766 fax
303-910-7769 Mobile
rick.pusch@weitz.com
www.weitz.com
BUILD IN GOOD COMPANY
>>> "Mike McGee" <MMcGee@vailgov.com> 3/25/2009 3:07 PM >>>
Temp Office Space - Plaza Level
1. Distance from an operable standpipe shall not be greater than 200 ft "as the hose lays". Closed stair towers do ot receive credit for standpipe coverage.
Demonstrate minimum 500 gpm is avaialble and within range of combustible storage room.
2. Revise Level 1 plan to show exit path from offices. Indicate travel distances. Travel distance up ramps may exceed maximum allowable.
3. Provide updated information on emergency evauation plan to reflect new office spaces.
4. Show location(s) of electrical disconnects for new office areas.
5. Show access route to new office space.
Please do not use red markers for plan notes.
Building_Division
SMTP
Building_Division@vailgov.com
Building_Division@vailgov.com
Building_Division
Fire_Inspectors
SMTP
Fire_Inspectors@vailgov.com
Fire_Inspectors@vailgov.com
Fire_Inspectors
Fire_Officers
SMTP
Fire_Officers@vailgov.com
Fire_Officers@vailgov.com
Fire_Officers
Rick Pusch
SMTP
Rick.Pusch@weitz.com
Rick.Pusch@weitz.com
Rick Pusch