Loading...
HomeMy WebLinkAboutUntitled (189) IPM.Note Fwd: B07-0275 Solaris Vol 2 Revisions Fwd: Mike McGee SMTP MMcGee@vailgov.com Mike McGee SMTP MMcGee@vailgov.com John Plano B07-0275 Solaris Vol 2 Revisions >>> Mike McGee 03/26/2009 5:09 PM >>> Vail Fire & Emergency Services has reviewed the plans submitted for the above project. Findings and comments are as follows: Life Safety sheet LS - LC plan notes include “options” related to CO2 ventilation and fuel storage. The applicant must select the desired option and submit plans accordingly. VT01 - VT05 do not indicate ventilation elements for pressurization, graphics, control sequencing or alarm and detection. Recommend developing an “elevator package” that includes the foregoing. A5 Vertical Circulation - Plans must be coordinated with smoke control system. The FPE should place a Review Stamp on these sheets. A separate smoke control “package” is required but it is reasonable they review the A5 plans to avoid potential conflict. John Plano SMTP JPlano@vailgov.com JPlano@vailgov.com John Plano