Temp Office Space - Plaza Level
1. Distance from an operable standpipe shall not be greater than 200 ft "as the hose lays". Closed stair towers do ot receive credit for standpipe coverage.
Demonstrate minimum 500 gpm is avaialble and within range of combustible storage room.
2. Revise Level 1 plan to show exit path from offices. Indicate travel distances. Travel distance up ramps may exceed maximum allowable.
3. Provide updated information on emergency evauation plan to reflect new office spaces.
4. Show location(s) of electrical disconnects for new office areas.
5. Show access route to new office space.
Please do not use red markers for plan notes.