HomeMy WebLinkAboutUntitled (213)
IPM.Note
Fwd: RE: RE: Solaris - Roof Decking Anchor for Fire Sprinkler
Fwd:
Mike McGee
SMTP
MMcGee@vailgov.com
Mike McGee
SMTP
MMcGee@vailgov.com
Dave Leiker; Steve Rondinelli; smartin@frontierfireprotection.com; Fire_Inspectors
RE: RE: Solaris - Roof Decking Anchor for Fire Sprinkler
>>> Mike McGee 03/24/2009 9:47 AM >>>
Shane,
Please re-review NFPA 13, 2002 edition, Section 9.1.1.2, specifically the "hangers certified by a registered professional engineer to include all the following..."
If you want to use the hangers outside of their listing and/or manufacturer's specifications / recommendations, the code requires certification (stamped plan and calculations) by a P.E..
I agree your math seems to work, but I am an AHJ, not your reviewing P.E..
Send be a stamped plan and calc's and I'll likely approve it.
Mike
>>> "Shane" <sparriott@frontierfireprotection.com> 03/24/2009 6:13 AM >>>
You are absolutely correct no one is approving this until you make your
decision on the issue they are just in agreement with the math and we are
all pending your approval. Thank You.
please contact me with any questions or concerns.
Shane Parriott
Designer / Project Manager
Frontier Fire Protection Inc.
phone:(303) 629-0221
fax:(303 623-7830
-----Original Message-----
From: Mike McGee [mailto:MMcGee@vailgov.com]
Sent: Monday, March 23, 2009 10:30 AM
To: Shane
Cc: David Rhoades; JR Mondragon; JR Rulapaugh; Mike McGee; Mark Miller; Mike
Vaughan
Subject: FW: RE: Solaris - Roof Decking Anchor for Fire Sprinkler
Shane,
Maybe I missed it but all I saw was a stamp that indicated it had been
"Reviewed" by "LAR".
I did not see anything that said "Approved."
Mike McGee
Deputy Chief
Vail Fire & Emergency Services
970 479-2135
>>> "Shane" <sparriott@frontierfireprotection.com> 03/23/2009 8:06 AM >>>
Good morning Mr. Mike McGee
Please see the attached documents foe the structural engineers
coments.
please contact me with any questions or concerns.
Shane Parriott
Designer / Project Manager
Frontier Fire Protection Inc.
phone:(303) 629-0221
fax:(303 623-7830
-----Original Message-----
From: Jared Quillen [mailto:Jared.Quillen@weitz.com]
Sent: Friday, March 20, 2009 3:02 PM
To: sparriott@frontierfireprotection.com
Subject: Fwd: RE: Solaris - Roof Decking Anchor for Fire Sprinkler
Shane,
The engineer agrees with your method. Please send me something from Mike V.
when you get his approval.
Thanks,
Jared
Dave Leiker
SMTP
dleiker@bcer.com
dleiker@bcer.com
Dave Leiker
Steve Rondinelli
SMTP
Srondinelli@bcer.com
Srondinelli@bcer.com
Steve Rondinelli
smartin@frontierfireprotection.com
SMTP
smartin@frontierfireprotection.com
smartin@frontierfireprotection.com
smartin@frontierfireprotection.com
Fire_Inspectors
SMTP
Fire_Inspectors@vailgov.com
Fire_Inspectors@vailgov.com
Fire_Inspectors