B07-0275 Solaris Lobby
Plans are denied for due cause as follows:
1. A08 Leather ceiling tiles not specified as to flame spread, ticking, backing, and method of attachment. Review and resub,it with FPE review.
2. Wood latice work on walls does not show fire protection, flame spread or other means of protection.
3. Details are not clear as to whether concealed combustible construction is present.
4. Recessed light fixtures extend down below place of ceiling. Possible fire sprinkler obstructions.
5. Details indicate plywood is attached to metal studs without drywall backing.
6. Lighting plan in Fire Command center appears to present glare problem with panels.
7. Fire sprinkler densities are not shown. Interior furnishings, treatment of walls and ceilnigs with combustible materials and configurations appear to pose sever threat.
8. All fire protection plans should be on RCP's.
Resubmital is required.
Steve Rondinelli
SMTP
Srondinelli@bcer.com
Srondinelli@bcer.com
Steve Rondinelli
maggie.Fitzgerald@davispartnership.com
SMTP
Maggie.Fitzgerald@davispartnership.com
Maggie.Fitzgerald@davispartnership.com
maggie.Fitzgerald@davispartnership.com
dan.feeney@solarisvail.com
SMTP
dan.feeney@solarisvail.com
dan.feeney@solarisvail.com
dan.feeney@solarisvail.com
Chris Gunion
SMTP
CGunion@vailgov.com
CGunion@vailgov.com
Chris Gunion
Fire_Inspectors
SMTP
Fire_Inspectors@vailgov.com
Fire_Inspectors@vailgov.com
Fire_Inspectors
Martin Haeberle
SMTP
MHaeberle@vailgov.com
MHaeberle@vailgov.com
Martin Haeberle