B09-010 Solaris Spa
Steve Rondinelli:
Please address these comments with Maggie Fitzgerald and get back to me.
FYI, the Flex Head brand device has recently receive UL listing approval
via a new UL standard. Please research the Flex Head site for the press
release on this approval. When you have a re-submittal plan, let me
know so I can review it with you. Thanks.
Dave Leiker
-----Original Message-----
From: Mike McGee [mailto:MMcGee@vailgov.com]
Sent: Monday, February 09, 2009 2:40 PM
To: maggie.Fitzgerald@davispartnership.com
Cc: Dave Leiker; Chris Gunion; David Rhoades; JR Mondragon; JR
Rulapaugh; Mike McGee; Mark Miller; Mike Vaughan
Subject: B09-010 Solaris Spa
Resubmittal required.
1. Plans indicate 2 burner residential stove top. No ducting provided.
Question intent and use of residential stove top. M0.02
2. FCU and return appear insufficient if stove top is intended for
melting wax. Based on similar code required installations, provide
minimum six air changes. M0.02
3. Smoke detectors are not suitable in rooms with non-ducted stove top,
laundry rooms, and rooms with high moisture. FAFP0001 Rm 229 and 230
4. Detail for fire sprinkler head indicates "flex head" but comments
indicate cast iron fittings. Flex heads are not approved without
additional justification and installation details. FAFP0000
Mike McGee