Solaris Pot and Fitness - Deferred Submittal
Plan is not Approved.
Submitted as B07-0275
1. FAFP0000 Detail sketch shows flex sprinkler head. Flex sprinkler heads are not approved.
2. FA 001 Devices shall have weather proof bases and suitable devices for high humidity.
3. Install manual pull station at pool equipment room.
4. Locate devices so they are accessible for repair and maintenance and so LED's are visible.
5. Smoke detectors may not be suitable for wet locations.
6. A 5.01 ADA Restrooms do not appear to be configured to allow wheelchair occupant to close the door once inside the restroom.
7. SP 4.0 Show clearance for stacked heaters.