B09-010 Solaris Spa
Resubmittal required.
1. Plans indicate 2 burner residential stove top. No ducting provided. Question intent and use of residential stove top. M0.02
2. FCU and return appear insufficient if stove top is intended for melting wax. Based on similar code required installations, provide minimum six air changes. M0.02
3. Smoke detectors are not suitable in rooms with non-ducted stove top, laundry rooms, and rooms with high moisture. FAFP0001 Rm 229 and 230
4. Detail for fire sprinkler head indicates "flex head" but comments indicate cast iron fittings. Flex heads are not approved without additional justification and installation details.
FAFP0000