Loading...
HomeMy WebLinkAboutUntitled (251) IPM.Note Solaris Bowling Alley B08-0287 Mike McGee SMTP MMcGee@vailgov.com Mike McGee SMTP MMcGee@vailgov.com Chris Gunion; Fire_Inspectors; Martin Haeberle michael@mahaharch.com Solaris Bowling Alley B08-0287 Vail Fire has competed their review of the plans submitted for the Bowling Alley under Permit B08-0287. 1. The raised stage/platform. Is the foam combustible? 2. The sound system must have a shunt for sound amplification per the fire alarm code amendments. 3. Note 20 on your 01/06/09 review is of concern re: panic hardware on Sheet A0.4. The panic hardware should be installed. 4. Note 37 of 01/06/09 re the grease ducts must also be addressed in the fire suppression system and clean outs for the grease duct. 5. Being an Assembly occupancy, they must also supply an Emergency Plan per Chapter 4 of the IFC. 6. Sheet FS1.0 - Fryers must have a minimum 18 inches clearance to open flame. We have accepted 18 in. vertical splash guards in the past. Michael McGee Deputy Chief Vail Fire & Emergency Services 970 479-2135 michael@mahaharch.com SMTP michael@mahaharch.com michael@mahaharch.com michael@mahaharch.com Chris Gunion SMTP CGunion@vailgov.com CGunion@vailgov.com Chris Gunion Fire_Inspectors SMTP Fire_Inspectors@vailgov.com Fire_Inspectors@vailgov.com Fire_Inspectors Martin Haeberle SMTP MHaeberle@vailgov.com MHaeberle@vailgov.com Martin Haeberle