The sprinkler portion seems to be fine.
I still have a concern on the supply to the fire pump.
It appears to violate NFPA 20, 5.14.6.3.1 - 5.14.6.3.2.
Both Prof's at OSU seem to agree.
Maybe the plans do not reflect the design?
If the room needs to be larger, they can move a wall. 80 inches should not be a deal killer.
Mike
>>> "Steve" <smartin@frontierfireprotection.com> 11/19/08 2:37 PM >>>
Mike
Have you completed your review on the revised fire sprinkler plans for
Solaris? We logged in the revised plans on 11-10-08.
We have completed the construction standpipe and need to start installing
the fire sprinkler system piping.
Wm Steve Martin
Frontier FIre Protection