HomeMy WebLinkAboutUntitled (293) IPM.Note Re: Solaris Fire Sprinkler Permit Re: Mike McGee SMTP MMCGEE@vailgov.com Mike McGee SMTP MMCGEE@vailgov.com dleiker; Fire_Inspectors; Martin Haeberle smartin Solaris Fire Sprinkler Permit The sprinkler portion seems to be fine. I still have a concern on the supply to the fire pump. It appears to violate NFPA 20, 5.14.6.3.1 - 5.14.6.3.2. Both Prof's at OSU seem to agree. Maybe the plans do not reflect the design? If the room needs to be larger, they can move a wall. 80 inches should not be a deal killer. Mike >>> "Steve" <smartin@frontierfireprotection.com> 11/19/08 2:37 PM >>> Mike Have you completed your review on the revised fire sprinkler plans for Solaris? We logged in the revised plans on 11-10-08. We have completed the construction standpipe and need to start installing the fire sprinkler system piping. Wm Steve Martin Frontier FIre Protection 2617 West Holden Place Denver, CO 80204 303-629-0221 fax 303-623-7830 cell 303-669-1665 dleiker SMTP dleiker@bcer.com dleiker@bcer.com dleiker smartin SMTP smartin@frontierfireprotection.com smartin@frontierfireprotection.com smartin Fire_Inspectors SMTP Fire_Inspectors@vailgov.com Fire_Inspectors@vailgov.com Fire_Inspectors Martin Haeberle SMTP MHaeberle@vailgov.com MHaeberle@vailgov.com Martin Haeberle