>>> "Steve" <smartin@frontierfireprotection.com> 11/06/08 4:51 PM >>>
Mike
The reduced pressure principle backflow preventer I suggested in the pump is
not rated for pressures greater than 175 PSI. In fact there are no backflow
preventers rated for pressures in excess of 175 PSI. Therefore we are left
with the two 8" reduced pressure backflow preventers in the water entry
rooms.
Tom Ogg will make sure we have a floor drain, heater, and lighting in these
rooms.
Wm Steve Martin