HomeMy WebLinkAboutUntitled (328)
IPM.Note
Fwd: Solaris Temp Heat
Fwd:
Mike McGee
SMTP
MMcGee@vailgov.com
Mike McGee
SMTP
MMcGee@vailgov.com
Chris Gunion
Solaris Temp Heat
Chirs,
Can you make this call?
Mike
376-0738
>>> Mike McGee 11/03/2008 9:09 AM >>>
The permit app for the Temp heat plan is shown as M08-0080. The description is shown as:
"The 4 PIPE HEATING AND COOLING SYSTEMS INCLUDING RADIANT FLOOR HEATING IN CONDO UNITS AND SNOWMELT PIPING IN CONDO BALCONIES AND DRIVEWAYS. STAIRWELL AND ELEVATOR PRESURIZATION FANS
AND ASSOCIATED DUCTWORK. CORE AND SHELL HVAC CONNECTIONS FOR RETAIL SPACE"
Should this be a separate permit?
The temp heat is not part of the original scope of M08-0080.
They have apparently installed the temp heat piping anyway.
The plans I have do not show the equipment, the valves, the heaters, the hose, nor the means of securing the 6 inch pipe to the retaining wall at the riser or the methods proposed to
secure the 6 inch pipe to the "back of curb."
They initially indicated they wanted to pour flowfill over the steel pipe. I explained there is a reason we sleeve steel pipe through concrete.
I will enter my comments and deny the permit once I know for sure what permit number to use.
Thanks,
Mike
Chris Gunion
SMTP
CGunion@vailgov.com
CGunion@vailgov.com
Chris Gunion