HomeMy WebLinkAboutUntitled (347)
IPM.Note
Fwd: RE: F08-0081 Solaris Temp Standpipe
Fwd:
Shelley Bellm
SMTP
SBellm@vailgov.com
Shelley Bellm
SMTP
SBellm@vailgov.com
Mike McGee
RE: F08-0081 Solaris Temp Standpipe
This has been printed and is in your box here in Com Dev
>>> Mike McGee 10/22/2008 9:25 AM >>>
Can you have someone print off a copy of this sheet?
Thanks,
Mike
>>> "Steve" <smartin@frontierfireprotection.com> 10/21/2008 5:02 PM >>>
Mike
Here is what I think you want to see. Let me know what you think and how
many copies would you like. We will install a construction standpipe in
Stair #2 and Stair #4 which will give you the cover you are looking for. I
added a fire dept connection on the frontage road to comply with the fire
department requirements.
Wm Steve Martin
Frontier FIre Protection
2617 West Holden Place
Denver, CO 80204
303-629-0221
fax 303-623-7830
cell 303-669-1665
-----Original Message-----
From: Mike McGee [mailto:MMcGee@vailgov.com]
Sent: Monday, October 20, 2008 3:00 PM
To: smartin@frontierfireprotection.com
Cc: Dave Leiker
Subject: F08-0081 Solaris Temp Standpipe
Steve,
Here are my initial comments on the Temp Standpipe Plan.
Do you want me to issue these or do you have any additional information?
Thanks,
Mike McGee
Sheet 10 of 16 Does not appear to provide coverage from Stair 9 or any
adjacent stair within range.
Sheet 11 of 16 No standpipe in Stair 6
Sheet 12 of 16 No coverage shown.
Sheet 14 of 16 No coverage.
Sheet 15 of 16 Inadequate coverage. No standpipe in Stair 3.
Sheet 16 of 16 FHV's shown on Sheet 16 do not all appear on floor plans.
Install a second FDC. The site is too large and the potential for
obstruction of a single FDC is too great.
Specify materials.
Mike McGee
SMTP
MMcGee@vailgov.com
MMcGee@vailgov.com
Mike McGee