Solaris Grage Zamboni entrance detail
Maggie & Christine:
I touched base with Mike McGee this morning to clarify the Level 1
entrance to the Parking Garage where the Zamboni will drive through to
surface the ice on the Plaza skating rink. Since the occupant load from
the back-of-house corridors from the retail space dumps into this
breezeway/passage with a ceiling above it, the entire breezeway must be
rated 2 hours with 90-minute fire-rated doors. The back-of-house
corridors dumping into the 2-hour rated breezeway must also have
90-minute rated doors, but these doors must be side-hinged and swinging
in the direction of egress travel because they are used for egress of
occupants.
The drawing attached shows the condition so everyone is in the same
communication loop and informed the same way. The 2-hour rated
breezeway is the #142 passage shown. The non-egress garage entrance is
shown and the two side corridor doors are shown. Occupants within the
garage space have two independent means of egress out of the garage
space without having to pass through the Zamboni Garage Door for egress.
Please call if you have any questions. Thanks.
David Leiker, P.E.
BCER Engineering, Inc.
5420 Ward Road, Suite 200
Arvada, Colorado 80002-1838
Office: 303.422.7400, Extension 285
Fax: 303.422.7900
Cell: 303.817.2299
Email: dleiker@bcer.com
Mike McGee
SMTP
MMcGee@vailgov.com
MMcGee@vailgov.com
Mike McGee
Christine Rajpal
SMTP
CRajpal@davispartner.com
CRajpal@davispartner.com
Christine Rajpal
Maggie Fitzgerald
SMTP
MFitzgerald@davispartner.com
MFitzgerald@davispartner.com
Maggie Fitzgerald
Solaris Level 1 Zamboni Garage Entrance.pdf