Brian,
You could send the sheets electronically in a pdf if they are too large. I think we have a 5 mb limit on incoming email.
We could also post to an fpt site.
I would not expect you to stamp plans you did not design but a stamped review letter would be fine.
I think the smoke control "package" should include the HVAC portion, initiation devices, power, and any elements directly connected to or essential to the function of the system.
A copy of the control matrix on the FA plans might be a good idea as well.
Let me know if this does not answer your question in sufficient detail.
Our goal is to establish a record for use in the future wherein a knowledgeable person (FPE) might be able to take the "package" and witness a test. The package would also be useful
to evaluate any proposed changes that might affect the performance of the system.
Thank you,
Mike McGee
Deputy Chief
Vail Fire & Emergency Services
http://www.vailgov.com/docs/dl_forms/smoke_control_commissioning_9_07.pdf.
>>> "Brian Thompson" <brian.thompson@q.com> 06/18/2009 5:34 AM >>>
Mike,
In an attempt to coordinate with the Solaris team on establishing the smoke
control submittal package for Solaris, I wanted to obtain from you the TOV
requirements for such a package.
The package will contain the shop design for the Building Automation System
as well as the Fire Alarm System.
I am currently reviewing the Building Automation System (for smoke control)
and I have it as half size sheets. Does TOV want full size sheets? How does
TOV want documentation of my review? I am not the Engineer of Record (EOR)
for the Building Automation System, so I do not want to stamp the
drawings/cut sheets. But I could provide my review letter with the submittal
package relative to the Smoke Control Rational Analysis and I could even
stamp the letter.
The Fire Alarm System consists of two sets of documents, Fire Alarm sheets
and Smoke Control sheets. Typically these two sets of sheets are one package
making up the Fire Alarm System but as you are aware, Solaris wanted to get
their FA permit and the Smoke Control sheets have not been sent to TOV. I am
in the process of reviewing both sets of sheets. Does TOV want full size
sheets? TOV has already reviewed and, I believe, approved the Fire Alarm
sheets. What about documentation of my review? Again, I am not the Engineer
of Record for the Fire Alarm System, so I do not want to stamp the
drawings/cut sheets. But I could provide a review letter with the submittal
package relative to the Smoke Control Rational Analysis and I could stamp
the letter.
Thanks Mike for your input on this as I attempt to bring this all together.
Regards,
Brian
Fire_Inspectors
SMTP
Fire_Inspectors@vailgov.com
Fire_Inspectors@vailgov.com
Fire_Inspectors
Martin Haeberle
SMTP
MHaeberle@vailgov.com
MHaeberle@vailgov.com
Martin Haeberle
Brian Thompson
SMTP
brian.thompson@q.com
brian.thompson@q.com
Brian Thompson
Dan Feeney
SMTP
dan.feeney@solarisvail.com
dan.feeney@solarisvail.com
Dan Feeney