Loading...
HomeMy WebLinkAboutPhase 5 and 6 NFPA 72 Cert FIRE ALARM SYSTEM RECORD OF COMPLETION To be complefed by the system instailation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY INFORMATION Name of SOLARIS—Phase 5&6—7`h floar units Pent B, Pent D, Pent G,Pent F, Pent C,7A,&7E...8�1 floor units property: Pent D, Pent E, and associated corridors on floors 7&8 Address: 141 EAST MEADOW DRIVE,VAIL CO Description of MIXED USE—HIGH RISE property: Occupancy type: R,M,B,S Name of property SOLARIS PROPERTY OWNER-SPO representative: Address: Phone: 970.390.6493 Fax: E-mail: DAN.FEENEY@SOLARISVAIL.COM Authority having jurisdiction over this VAIL FIRE DEPARTMENT property: Phone: 970.4792135 Fax: E-mail: MMCGEE@VAIL.GOV 2. FIRE ALARM SYSTEM INSTALLATION, SERVICE, AND TESTING INFORMATION Installation contractor for this equipment: ELIGHT ELECTRIC/LEl COMPAMES Address: LEI—2017 CURTIS STREE3T, DENVER,CO 8020� Phone: 303.934.5631 Fax: E-maiL- LEI@LEICOMPANIES.COM Service organization for this equipment: JOHNSON CONTROLS, INC. Address: 10289 WEST CENTENMAL ROAD, LITTLETON,CO 80127 Phone: 303.973.5930 Fax: 303.979.6847 E-maiL• KENNETH.D.BALL@JCI.COM Location of as-built drawings: FIRE COMMAND Location of historicat test reports: FIRE COMMAND Location of system operation and maintenance manuals: FIRE COMMAND A conn•act for test and inspection in accordance with NFPA standards is in effect as of: TBD—UPON C/O Contracted testing company: TBD Address: TBD Phone: TBD Fax: TBD E-mail: TBD Occupancy type: R,B,M,S Contract expires: TBD Contract number: TBD Frequency of routine inspections: TBD 3.TYPE OF FIRE ALARM SYSTEM OR SERVICE NFPA 72 Chapter Reference of System Type: CHAPTER 6 Name of organization receiving alarm signals with phone numbers(rf applicable): Alarm: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524 Supervisory: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524 Trouble: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524 Entiry to�vhich a(arms are retransmitted: VAIL FIRE DEPARTMENT DISP Phone: 970,479,2246 Method of retransmission of alarms to that organization or location: Phone Centeral Station Dispatch Record of Comptetion form(based on NFPA 72—2007) NFPA 72,1 of 5 NFPA phase 5&6.doc 6/22/2010 920:00 AM R.W.Evans Repdnted with permission from NFAP 72-2007,National Fire Alarm Code O, Copyright�2007,National Fire Protection Association,Quincy,MA,02269 3. TYPE OF FIRE ALARM SYSTEM OR SERVICE(continuec� If Chapter 8,note the means of transmission from protected premises to the central station: ❑X Digital alarm communicator � McCulloh � Multiplex � 2-wav radio � 1-way radio � N/A If Chapter 9, note type of connection: � Local energy � Shunt �X N/A 3.1 System Software Operatin;system(executive)software revision level: 12.0 Site-specific soft�vare revision date: 5.5 Revision completed by: J[M MOREN 4. SIGNALING LINE CIRCUITS Characteristics of signaling line circz�its connected to this systern (see NFFA 72, Table 6.6.1): Quantity: 16 Style: 4 Class: B 5. ALARM INITIATING DEVICE CIRCUITS Character•istics of rnitiating device circzrits connected to this systena (see NFPA 72, Table 6.�): TD BE REMOVED PRIOR TO C/O(TEtLIPORARY RETAIL SEE BELON�—EACH HEAT IN GARAGE ON INDIVIDUAL IDC Quantity: ll Style: 4 Class: B 5.1 Manual Initiating Devices 5.1.1 Manua(Pull Stations Number of Manual pull stations: SEE DEV[CE CT SHEET Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A 5.2 Automatic Initiating Devices 5.2.1 Area Smoke Detectors Number of smoke detectors: SEE DEVICE CT SHEE1' Type of coverage: � Complete area �X Partial area � Nonrequired partial area � N/A Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A Type of smoke detector sensing technology � Ionization ❑X Photoelectric 5.2.2 Duct Smoke Detectors Number of duct smoke detectors: Type of coverage: Type of devices: � Addressable � Conventional � Coded � Transmitter � N/A Type of smoke detector sensing technology � Ionization � Photoelectric 5.2.3 Heat Detectors Number of heat detectors: � RSEE DEVICE CT SHEET Type of coverage: � Complete area �X Partial area � Nonrequired partial area � N/A Type of devices: �X Addressable ❑X Conventional � Coded � Transmitter � N/A 5.2.4 Sprinkler Waterflow Detectors Number of waterflow detectors: SEE DEVICE CT SHEET Type of devices: ❑X Addressab(e � Conventionai � Coded � Transmitter � N/A Record of Compfetion form(based on NFPA 72—2007) NFPA 72,2 of 5 NFPA phase 586.doc 6/22/2010 9:08:00 AM R.W.Evans Reprinted�,vith permission from NFAP 72-2007,National Fire Alarm Code O4, Copynght O 2007,National fire Protection Association,Quincy,MA,02269 5.2.5 Alarm Verification Number of devices subject to alarm verification: Alarm verification on this system is: � Enabled ❑X Disabled � Set for seconds 6. SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUITS 6.1 Sprinkler System Nmnber of valve supervisory switches: SEE DEVICE CTSHEET Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A 6.2 Fire Pump Type of fire pump: � Electric � Diesel Type of fire pump supervisory devices: � Addressab(e � Conventional � Coded � Transmitter � N/A Fire Pump Functions Supervised � Fire pump power � Fire pump running � Fire pump phase reversal � Selector switch not in auto � Engine or control panel trouble � Low fuel Other: 6.3 Engine-Driven Generator Type of generator supervisory devices: � Addressable � Conventional � Coded � Transmitter � N/A � Engine or control panel h-ouble � Generator running � Selector switch not in auto � Low fue( Other: 7. ANNUNCIATORS 7.1 Annunciator 1 � Local �X Remote Type: �X Addressable � Directory � Graphic � N/A Locatian: ENTRANCE TO STA[R 3 7.2 Annunciator 2 � Local �X Remote Type: �X Addressable � Directory � Graphic � N/A Location: ENTRANCE TO STAIR 4 7.3 Annunciator 3 � Local � Remote Type: � Addressable � Directory � Graphic ❑X N/A Location: 8. ALARM NOTIFICATION DEVICES AND CIRCUITS 8.1 Emergency Voice Alarm Service—CURRENTLY DISABLED AT TOV REQUEST—WHOOP ONLY Number of single voice alarm channels: 16 Number of multiple voice alarm channels: NONE Number of speakers: TBD UPON C/O Number of speaker zones: 16 UPON C/O 8.2 Telephone Jacks Number of telephone jacks installed: N/A Number of telephone handsets stored on site: N/A Type oftelephone system instalied: � Electrically powered � Sound po�vered ❑X N/A Record of Completion form(based on NFPA 72—2007) NFPA 72,3 of 5 NFPA phase 5&6.doc 6/22/2010 9:06:00 AM R.W.Evans Reprinted with permission from NFAP 72-2007,National Fire Alarm Code O, Copyright��2007,National Fire Protection Association,Quincy,MA,02269 8.3 Nonvoice Audible System Characteristics of notification device circuits connected to this system (see NFP�1 72, Table 6.S): EXTERIOR K/S Quantity: 3 Sryle: 4 Class: B 8.ALARM NOTIFICATION DEVICES AND CIRCUITS (continuea� 8.4 Types and Quantities of Nonvoice Notification Appliances Installed Bells: With visual device: Horns: With visual device: Chimes: With visual device: Speakers: Tbd With visual Tbd upon upon c/o device: c/o Visual devices without audible devices: TBD UPON Other(describe): EXTERIOR H/S -3 cio 9. EMERGENCY CONTROL FUNCT{ONS ACTIVATED � Hold-open door releasing devices a Smoke mana�ement or smoke control � Door unlocking-UPON C/O � Elevator recal( � Other 10. SYSTEM POWER SUPPLY 10.1 Primary Power Nominal voltage: 277/480 volt 3 phase 4 wire Amps: 2 services na,4000 amps Overcurrent protection: Type: Fused Switches Amps: 2 services cr,4000 amps Location(of primary supply panel board): Garage Levet South East corner of building Disconnecting means location: Fused Switches Switchbord MSB has 5 main switches MSA has 1 Main switch 10.2 Secondary Power Location: FCC Type: BATT Nominal voltage: 12V Current ratin�: N/A Number of standby batteries: 2 Amp hour rating: 55 AH Location of emergency generator: GARAGE Location of fuel storage: GARAGE Calculated capacity of secondary power to drive the system In standby mode: 24 HRS In a(arm mode: � MIN 11. RECORD OF SYSTEM INSTALLATION Fill out after all installation is complete and wiring has been checked for open.s, shorts,grotrnd faults, and improper branching, ba�t before conducting operation acceptance tests. The system has been installed in accordance with the following NFPA standards(Note any or all that apply): ❑X NFPA 72 ❑X NFPA 70,National Electricaf Code, Article 760 ❑X Manufacriirer's published instructions � Other(p(ease specify): System deviations from referenced NFPA standards: Signed: `�.�....�"�� Printed Name: /'�(N°c��` /u���--4't-f Date: � 2��r<a Organization: j-/c_'zik��'�� �°�+i �< «%°�5��-- Title: �1"-3s�"i. Phone: ���' -�1°`?'>s.`.z���, Rewrd of Compfetion form(based on NFPA 72—2007) NFPA 72,4 of 5 NFPA phase 5&6.doc 6/22/2010 9 08 00 AM R.W.Evans Reprinted with permission from NFAP 72-2007,National Fire Alarm Code O, Copyright�2007,National Fire Protection Association,Quincy,MA,02269 12. RECORD OF SYSTEM OPERATtON All operational features and functions of this system�vere tested by or in the presence of the si�ner shown below,on the date shown below, and were found to be operating properly in accordance with the requirements of ❑X NFPA 72 ❑X NFPA 70,Nationcrl Elecn-ical Code,Article 760 ❑X Manufacturer's published instructions ❑X Other(please specify): RATIONAL ANALYSIS � Do Jmentati�n in aecordance with Inspection and Testing Form(Figure 10.6.2.3) is attached .f ;:, Signecl:� ��-�� _ ______—- -- Printed Name: Kenneth Bal( Date: 6/22/10 f Organizafion: Johnson Controls, Inc Title: LSS Phone: 303.328.5287 13. CERTIFICATIONS AND APPROVALS 13.1 System installation Contractor The system as specified herein has been installed and tested in according to all NFPA standards cited herein. Signed: `����.�' �7�7� Printed Name: � ( K c N��-�t r..J Date: � / Z-��� Organization: �1�t--�k � �=�-��`�T ��-��-'t'��c� Title: s-��n T• Phone: �' �' S��� "2-�i`� �, 13.2 System Service Contractor The system as sp�eifi��Y��}erein has been instaVled and tested in according to all NFPA standards cited herein. %� '� '� Signed: _,;- i""�� -�--�°�"�"�"`�°A°��_`._�rintedName: Ken Ball Date: 6/22/10 Organiz t n: Johnson Conh-ols, Inc Title: LSS Phone: 303328.5287 13.3 Central Station The system as specified herein will be monitored accordin;to all NFPA standards cited herein. � ,��r�..�°- . Sign- : _.'�-�,�.// --=�-- _ Printed Name: Ken Ball Date: 6/22/10 y� Organization: JCI-REMOTE OPERATIONS Title: LSS Phone: 800.753.4524 13.4 Property Representative I accept t ' s ste�� as having been installed and tested to its specifications and all NFPA standards cited herein. Signed: Printed Name: /V Date: �� Organization: p� � Title: � Phone: � � 13.5 Authority Having Jurisdiction [have wimessed a satisfactory acceptance test of this system and find it to be installed and operating properly in accordance with its approved plans and specifications, its approved sequence of operations and with all NFPA standards cited herein. Signed: Printed Name: Date: Organization: Title: Phone: Record of Completion form(based on NFPA 72—2407) NFPA 72,5 of 5 NFPA phase 5&6.doc 6122/2010 9:08:00 AM R.W.Evans Reprinted with permission from NFAP 72-2007,National Fire Alarm Code�, Copyright O 2�07,National Fire Protection Association,Quincy,MA,02269