HomeMy WebLinkAboutPhase 9 NFPA 72 Cert FIRE ALARM SYSTEM RECORD OF COMPLETION
To be completed by the system instaUation contractor at the time ot'system acceptance and approval.
1. PROTECTED PROPERTY INFORMATION
Name of SOLARIS—Phase 9=SA-E, SC-E,SE-E,SF-E,SD-E,SE-E Corridor 5 E(SG-E and SE-Penthouse H are
property: excluded from this phase)
Address: 141 EAST MEADOW DRIVE,VAIL CO
Description of MIXED USE—HIGH RISE
property:
Occupancy type: R,M,B,S
Name of property SOLARIS PROPERTY OWNER-SPO
representative:
Address:
Phone: 970.390.6493 Fax: E-mail: DAN.FEENEY@SOLARISVAIL.COM
Authority having jurisdiction over this VAIL FIRE DEPARTMENT
property:
Phone: 970.479.2135 Fax: E-mail: MMCGEE@VAIL.GOV
2. FIRE ALARM SYSTEM INSTALLATION, SERVICE,AND TESTING INFORMATION
Installation contractor for this equipment: ELIGHT ELECTRIC/LEI COMPANIES
Address: LEI—2017 CURTIS STREE3T,DENVER,CO 80205
Phone: 303.934.5631 Fax: E-mail: LEI�a,LEICOMPANIES.COM
Service organization for this equipment: JOHNSON CONTROLS,INC.
Address: 10289 WEST CENTENNIAL ROAD,LITTLETON,CO 80127
Phone: 303.973.5930 Fax: 303.979.6847 E-mail: KENNETH.D.BALL@JCLCOM
Location of as-built drawings: 'FIRE COMMAND
Location of historical test reports: FIRE COMMAND
Location of system operation and maintenance manuals: FIRE COMMAND
A contract for test and inspection in accordance with NFPA standards is in effect as of: TBD—UPON C/O
Contracted testing company: TBD
Address: TBD
Phone: TBD Fax: TBD E-maiL• TBD
Occupancy type: R,B,M,S
Contract expires: TBD Contract number: TBD Frequency of routine inspections: TBD
3.TYPE OF FIRE ALARM SYSTEM OR SERVICE
NFPA 72 Chapter Reference of System Type: CHAPTER 6
Name of organization receiving alarm signals with phone numbers(if applicable):
Alarm: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524
Supervisory: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524
Troubie: REMOTE OPERATIONS CENTER-JCI Phone: 1.800.753.4524
Entity to which alarms are retransmitted: VAIL FIRE DEPARTMENT DISP Phone: 970,479,2246
Method of retransmission of alarms to that organization or location: Phone Centeral Station Dispatch
Record of Compietion form(based on NFPA 72—2007) NFPA�2,1 of 5 NFPA phase 9.doc 5/19/2010 8:55:00 AM R.W.Evans
Reprinted with perrnission from NFAP 72-2007,Netional Fire Alarm Code OO,
Copyright O 2007,National Fire Protection Association,Quincy,MA,02269
3.TYPE OF FIRE ALARM SYSTEM OR SERVICE (continue�
If Chapter 8,note the means of transmission from protected premises to the central station:
❑X Digital alarm communicator � McCulloh � Multiplex � 2-way radio � 1-way radio � N/A
If Chapter 9,note type of connection: � Local energy � Shunt �X N/A
3.1 System Software
Operating system(executive)software revision level: 12.0
Site-specific software revision date: 5.5 Revision completed by: JIM MOREN
4.SIGNALING LINE CIRCUITS
Characteristics of sigraaling line circuits connected to this system (see NFPA 72, Table 6.6.1):
Quantity: 16 Style: 4 Class: B
5.ALARM INITIATING DEVICE CIRCUITS
Characteristics of initiating device circuits connected to this system (see NFPA 72, Table 6.S): TO BE REMOVED PRIOR
TO GO(TEMPORARYRETAIL SEE BELOW)—EACH HEAT IN GARAGE ONINDIVIDUAL IDC
Quantity: 11 Style: 4 Class: B
5.1 Manual Initiating Devices
5.1.1 Manual Pull Stations Number of Manual pull stations: SEE DEVICE CT
SHEET
Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A
5.2 Automatic Initiating Devices
5.2.1 Area Smoke Detectors Number of smoke detectors: SEE DEVICE CT
SHEET
Type of coverage: � Complete area ❑X Partial area � Nonrequired partial area � N/A
Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A
Type of smoke detector sensing technology � Ionization ❑X Photoelectric
5.2.2 Duct Smoke Detectors Number of duct smoke detectars:
Type of coverage:
Type of devices: � Addressable � Conventional � Coded � Transmitter � N/A
Type of smoke detector sensing tecluiology � Ionization � Photoelectric
5.2.3 Heat Detectors Number of heat detectors: SE�DEVICE CT
SHEET
Type of coverage: � Complete area �X Partial area � Nonrequired partial area � N/A
Type of devices: �X Addressable 0 Conventional � Coded � Transmitter � N/A
5.2.4 Sprinkler Waterflow Detectors Number of waterflow detectors: SEE DEVICE CT
SHEET
Type of devices: ❑X Addressable � Conventional � Coded � Transmitter � N/A
Record of Completion form(based on NFPA 72—2007) NFPA 72,2 of 5 NFPA phase 9.doc 5/19/2010 8:55:00 AM R.W.Evans
Reprinted with permission from NFAP 72-2007,National Fire Alarm Code O,
Copyright�O 2007,National Fire Proieclion Association,Quincy,MA,02269
5.2.5 Alarm VeriCcation Number of devices subject to alarm verification:
Alarm verification on this system is: � Enabled ❑X Disabled � Set for seconds
6. SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUITS
6.1 Sprinkler System Number of valve supervisory switches: SEE DEVICE
CT SHEET
Type of devices: �X Addressable � Conventional � Coded � Transmitter � N/A
6.2 Fire Pump
Type of fire pump: � Electric � Diesel
Type of fire pump supervisory devices: � Addressable � Conventional � Coded � Transmitter � N/A
Fire Pump Functions Supervised
� Fire pump power � Fire pump running � Fire pump phase reversal � Selector switch not in auto
� Engine or control panel trouble � Low fuel
Other:
6.3 Engine-Driven Generator
Type of generator supervisory devices: � Addressable � Conventional � Coded � Transmitter � N!A
� Engine or control panel trouble � Generator running � Selector switch not in auto � Low fuel
Other:
7.ANNUNCIATORS
7.1 AnnunCiator 1 � Local ❑X Remote
Type: �X Addressable � Directory � Graphic � N/A Location: ENTRANCE TO STAIR 3
7.2 Annunciator 2 � Local � Remote
Type: ❑X Addressable � Directory � Graphic � N/A Location: ENTRANCE TO STAIR 4
7.3 Annunciator 3 � Local � Remote
Type: � Addressable � Directory � Graphic ❑X N/A Location:
8.ALARM NOTIFICATION DEVICES AND CIRCUITS
8.1 Emergency Voice Alarm Service—CURRENTLY DISABLED AT TOV REQUEST—WHOOP ONLY
Number of single voice alarm channels: 16 Number of multiple voice alarm channels: NONE
Number of speakers: TBD UPON C/O Number of speaker zones: 16 UPON C/O
8.2 Telephone Jacks
Number of telephone jacks installed: N/A Number of telephone handsets stored on site: N/A
Type of telephone system installed: � Electrically powered � Sound powered ❑X N/A
Record of Comple6on form(based on NFPA 72—2007) NFPA 72,3 of 5 NFPA phase 9.doc 5/19/2010 8:55:00 AM R.W.Evans
Reprinted with permission from NFAP 72-2007,National Fire Alarm Code O,
Copyright O 2007,National Fire Protection Associalion,Quincy,MA,02269
8.3 Nonvoice Audibie System
Characteristics of notification device circuits connected to this system(see NFPA 72, Table 6.S):EXTERIOR H/S
Quantity: 3 Style: 4 Class: B
8. ALARM NOTIFICATION DEVICES AND CIRCUITS(continuea�
8.4 Types and Quantities of Nonvoice Notification Appliances installed
Bells: With visual device: Horns: With visual device:
Chimes: With visual device: Speakers: Tbd With visual Tbd upon
upon c/o device: c/o
Visual devices without audible devices: TBD UPON Other(describe): EXTERIOR H/S-3
GO
9. EMERGENCY CONTROL FUNCTIONS ACTIVATED
❑X Hold-open door releasing devices �X Smoke management or smoke control
�X Door unlocking—UPON C/O �X Elevator recall � Other
10. SYSTEM POWER SUPPLY
10.1 Primary Power
Nominal voltage: 277/480 volt 3 phase 4 wire Amps: 2 services ,4000 amps
Overcurrent protection: Type: Fused Switches Amps: 2 services @ 4000 amps
Location(of primary supply panel board): Garage Level South East corner of building
Disconnecting means location: Fused Switches Switchbord MSB has 5 main switches MSA has 1 Main switch
10.2 Secondary Power
Location: FCC Type: BATT Nominal voltage: 12V Current rating: N/A
Number of standby batteries: 2 Amp hour rating: 55 AH
Location of emergency generator: GARAGE
Location of fuel storage: GARAGE
Calculated capacity of secondary power to drive the system
In standby mode: 24 HRS In alarm mode: 5 MIN
11. RECORD OF SYSTEM INSTALLA710N
Fill out after all installation is complete and wiring has been checked for opens, shorts,ground faults, and improper
branching, but before conducting operation acceptance tests.
The system has been installed in accordance with the following NFPA standards(Note any ar all that apply):
❑X NFPA 72 ❑X NFPA 70,National Electrical Code,Article 760
❑X Manufacturer's published instructions � Other(please specify):
System deviations •o referenced NFPA standards:
Signed: e PrintedName: /�,�„N.� ��nQ,ti.1 Date: �' �� �
Organization: ��,G��-���c�?r Title: �,-��,`,,,�� _ Phone: 3/�/���yZ�.
�
Record of Completion form(based on NFPA 72—2007) NFPA 72,4 of 5 NFPA phase 9.doc 5/19/2010 8:55:00 AM R.W.Evans
Reprinted with permission from NFAP 72-2007,National Fire Alarm Code�,
Copyright O 2007,National Fire Protection Association,Quincy,MA,02269
12. RECORD OF SYSTEM OPERATION
All operational features and functions of this system were tested by or in the presence of the signer shown below,on the date
shown below,and were found to be operating properly in accordance with the requirements of
❑X NFPA 72 ❑X NFPA 70,National Electrical Code,Article 760
❑X Manufacturer's published instructions ❑X Other(please specify): RATIONAL ANALYSIS
� Document �on � accordance with Inspection and Testing Form(Figure 10.6.23)is attached
Signed: Printed Name: Kenneth Ball Date: 5/19/10
Organization: Johnson Controls,Inc Title: LSS Phone: 303328.5287
13. CERTIFICATIONS AND APPROVALS
13.1 System Installation Contractor
The system as specified herein has been installed and tested in according to all NFPA standards cited herein.
Signed: ,�1����'``/ Printed Name: �(� �'�b,�/ Date: s"/�q12��U
Organization: ��/y�f�,,� Title: �6,-„-�C,.,,._ Phone: 3����'�z°�
,
13.2 System Service Contractor
The system as specified herein has been installed and tested in according to all NFPA standards cited herein.
Signed: Printed Name: Ken Ball Date: 5/19110
Organization: Johnson Contro s,Inc Title: LSS Phone: 303328.5287
13.3 Central Station
The system as specified herein will be monitored according to all NFPA standards cited herein.
Signe : Printed Name: Ken Ball Date: 5/19/10
Organization: JCI—REMOTE OPERATIONS Title: LSS Phone: 800.753.4524
13.4 Property Representative
I accept t ' sy em ' g been installed and tested to its specifications and all NFPA standards cited herein.
Signed: PrintedName: /�.� ���.. Date: �
Organization: Title: Phone: �— -- y��
13.5 Authority Having Jurisdiction
I have witnessed a satisfactory acceptance test of this system and find it to be installed and operating properly in accordance
with its approved plans and specifications,its approved sequence of operations and with all NFPA standards cited herein.
Signed: Printed Name: Date:
Organization: Title: Phone:
Record of Completion form(based on NFPA 72—2007) NFPA 72,5 of 5 NFPA phase 9.doc 5/19/2010 8:55:00 AM R.W.Evans