RE: Bol - Bowling Alley Tenant Finish/Improvement Plans 3rd Submittal for Solaris
Development (Bol Building Permit#B08-0287)—Project Address: Unit 112, 143 E.
Meadow Drive, Vail, CO 81657
Dear Mr. Haeberle,
We are pleased to transmit with this letter the Bowling Alley Tenant Finish/Improvement
Plans Submittal for Building Permit. Bol is a ten lane bowling alley tenant improvement
is located on the east side of Solaris, on Level 1.
Included with this letter are:
1. Five Plan Review Comment Response Letters dated 12-31-08.
2. Five Planning Comment/Response attachments dated 11-25-08 and 12-31-08.
3. Five full size stamped and signed Plans, dated 12-19-08.
4. Two half size copies of the Plans, dated 12-19-08,
Please note, the following sheets have been revised for this submittal: A0.0, A0.4, M0.1,
M0.2, M1.0, Ml.l, M2.0, E0.1, E3.1, E4.1, E6.1, E7.1, E9.1, P0.1, P0.2, P1.0, P2.0,
P3.0, and P4.0. All other sheets did not require revisions and remained as submitted in
our 2"d Bol Permit submittal.
Please communicate all TOV Plan Review comments to Michael Hunsinger of MAH
Architectural Group at michael c(r�e,maharch.com. Please call Tom Ogg of Solaris at 970-
479-7138 with any questions.
Sincerely,
�'o,�., �',ri ���.��n�•,�. �
Tom o [� �� C�: Il \U/ �_', �
gg D I� �
Project Manager
Solaris Development ' �ns� �, �` �� 6"���� ��,�.� �
� C L., I_> Y
� f,j�01v��•� �:.�m�'� b`�1�C�h _
Attachments _._ �",:�, ,��_.r.,.._. � .
2211 NorP.h Frontage Rd � Suite � � Vail, Colorado 81657 � Phone 970.�79.7566 ( Fax 970.�+�79.6666 � solarisvail.com
i
�
������ �
Department ofCommunity Deve%pment
Building SaFety and Inspection Services
75 South Frontage Road
�ail, Co%rado 81657
970-479-2138
FAX 970-479-2452
www,vailgov.com
Second Check
Second check plan review comments are shown below original comments in bo/d ita/ics
BUILDING SAFETY AND INSPECTION SERVICES PLAN REVIEW COMMENTS:
TO: Contractor/Applicant Architect
Weitz Company MAH
Chris Keran proj# none
FAX/Email #: Chris.Keran@weitz.com Michael@maharch.com
NUMBER OF PAGES: 2 `
FROM: Chris Gunion, Building Plans Examiner
DATE: 12/04/2008
BUILDING PERMIT #: B08-0287
OWNERS NAME: Solaris Property Owner LLC
SITE ADDRESS: 143 E Meadow Drive
OCCUPANCY GROUP: A-2/A-3
TYPE OF CONSTRUCTION: I-A
NUMBER OF STORIES: existing
BUILDING AREA: existing
The documents submitted for this project have been reviewed for compliance with the 2003
International Building Code, 2003 International Residential Code, 2003 International Mechanical
Code, 2003 International Fuel Gas Code, 2003 International Plumbing Code, 2003 International
Energy Conservation Code and 2008 National Electrical Code as modified and adopted by the Town of
Vail.
The fo/%wing comments wi//need to be addressed prior to issuance of a bui/ding permit;
For processing:
• Please submit four complete sets of revised construction documents containing the requested
information with all plan revision items clouded or otherwise identified. Partial plan sets or
loose plan sheets are not accepted.
. Please respond in writing to each comment by marking the attached list or creatin_q a response
letter. Indicate which �lan sheet, detail, specification, or calculation shows the requested
information. Please send revisions to the attention of the plans examiner with the building
permit application number noted.
• Please be sure to include on the resubmittal the engineer's or architect's'�wet"stamp, signature�
registration number and date on the cover page of any structural calculations, all structural
details and structural sheets of the plans. For commercial or multi-family projects all sheets of
the plans must be stamped.
Note: Solaris/Bol Design Team 12-31-08 responses are shown in Green text below each TOV
comment.
Architectural Comments:
14 Include structural plans for the portion of the bowling lounge area floor to be built up 20" per note on
sheet A1.1
Structura/sheets indicate the base bui/ding structura/engineer is to verify existing floor
is capab/e of supporting the/oads indicated on sheet S2,0, P/ease inc/ude wriiten
documentation from the base bui/ding st�uctura/engineer,
Please see the attached 12/23/08 letter from Structural Consultants Incorporated (SCI), the base
building structural engineer verifying the existing floor is capable of supporting the loads indicated
on sheet S2.0.
19 Revise all floor plans to label all doors to the corresponding door schedule on sheet A0.4. Additional
comments may be necessary, plan review could not be completed.
90 minute door ratings are required on a//doors into the 2 hour exit passageways
Revise doors E00, D24, D25, D26, D13 to 90 minute, IBC table 715,3
Please see revised Sheet A0.4. Doors E00, D24, D25, D26, D13 have been revised on door
schedule of sheet A0.4 to indicate a 90 minute rating, in accordance with IBC table 715.3.
20 Revise sheet A0.4 to provide panic hardware on all exit doors serving 100 occupant load.
Revise DOO and D23 to provide panic hara/ware. The occupant/oad exceeds 300, section
1008,1.8,3 item 2 does not app/y,panic hardware is required,
Doors D00 and D23 are noted on the door schedule of Sheet A0.4 with keyed note #5 to have
panic hardware provided.
37 Revise plans to include the roof plan where the new grease duct exhaust will terminate. Show fixed
ladder, working platForms and catwalks per IMC 306.5 and guards per IBC 1012.5 The area of the
roof where the grease duct is shown to terminate is shown as 11/12 pitch on the Solaris core/shell
plans sheet A2.51
P/ease submit p/ans sheets showing the requested information, The TOV permit set for
, So/aris does not contain sheets A2,53,A2,54 orA5,26 as referenced in the response,
Please see attached Core and Shell Sheets A2.56, A5.09A - Detail 4, and A5.09B - Details 1, 2,
and 4. These three reference sheets are included at the back of the submittal sets.
Structural Comments:
41 Include structural plans for the portion of the bowling lounge area floor to be built up 20" per note on
sheet A1.1
Structura/sheets indicate the base bui/ding structura/engineer is to verify existing floor
is capab/e of supporting the/oads indicated on sheet S2,0, P/ease inc/ude written
documentation from the base bui/ding structura/engineer,
Please see the attached 12/23/08 letter from SCI, the base building structural engineer verifying
the existing floor is capable of supporting the loads indicated on sheet S2.0.
Plumbing Comments:
45 Waste piping from the bar area and other fixtures or areas that do not require grease separation
shall not be routed to the grease waste. IPC 1003.2. Revise plans.
P/ease review piping p/ans and coordinate with the kitchen�xture p/ans For examp/e,
ice machine and hand sinks shou/d not be connected to the grease waste, IPC i003,
The hand sinks, ice machine, and floor sink for the refrigerator/freezer are
connected to the sanitary waste system and no longer connect to the grease waste
system.
Mechanical Comments:
46 Amend plans to include a rooftop mechanical layout plan showing kitchen exhaust duct fan and duct
termination. Coordinate with architectural plans for equipment access per IMC 306.5
P/ease submit p/ans sheets showing the requested information, The TOV permit set for
So/aris does not contain sheets A2,53,A2,54 orA5,26 as referenced in the response
Please see attached Core and Shell Sheets A2.56, A5.09A — Detail 4, and A5.09B — Details 1, 2,
and 4. These three reference sheets are included at the back of the submittal sets.
Please refer to the cover sheet for information on resubmitting plans. in order to avoid delays in issuance of
a permit, please check all requested information is included with the resubmitted plans. Please submit
revised plans as a complete set. Partial plan resubmittals will not be reviewed.
F:\cdev\CHRIS\PERMIT.COMMENTS\608-0287\608-0287.secondcheck.DOC
�= - . - .�_-----`— ----`- -- -� --
�,�I � _ iI �_- _
(� �,I l� � i 'q 1 " -_ ° , t I _. --
_� _ ���t I":� I �-
�_ , �
J� S �."'i'a'', ' ,. ��,
December 23, 2008
Mr. Tom Ogg
SOLARIS PROPERTY OWNER, LLC
2211 N. Frontage Road, Suite A
Vail, CO 8165?
Re: Solaris
SCI #04-187
Dear Tom:
In response to the TOV comment number 14 for the bowling alley area and the built up floor, SCI
can confirm that the 20" built up fiooring has been accounted for in our structural design. We
have designed for 60 psf of superimposed dead load for this area. The topping slab will be
supported by light weight geo-foam. This system is less than the allotted dead load allowance
and is structurally acceptable.
If you have further question please contact us.
Sincerely,
STR CTURAL CONSULTANTS, INC.
J.R. Barker, P.E., S.E.
Principal
r.�= ,,, , �.._.
_ , _. � _. ._. _ .
11/25/08 Solaris Planning Coinmeut Responses shown in Greenbelow.
12/31/08 Solaris Planning Comment Responses shown in Blue below.
-----Original Message-----
From: Warren Campbell [mailto:WCampbell@vailgov.com]
Sent: Wednesday, August 27, 2008 7 : 19 AM
To: Michael Suman; Chris.Keran@wietz.com
Subject: Solaris Bowling Alley Tenant Improvements
Chris and Michael,
I have performed my review of the bowling alley tenant improvements. I
have two issues that need to be addressed, prior to my being able to
sign off on the permit.
1) I do not see the provision of a live music venue within the bowling
alley. During the review process there were statements that a live
music venue, similar to 8150, would be provided in this space. There
was originally proposed a sunken stage, then an at finished floor (or
slightly elevated stage) was proposed. Other than a DJ booth I do not
see the ability to have a stage or live music venue. Please provide
details on how this is accomplished.
11/25/08 Response: The Furniture Plan on Sheet A10.0 illustrates a stage in the Dining 105 room. While
there is no"live music venue"requireinent,this stage represents the opporhiniry for live inusic to be
performed in the space.
2) I was unable to find any detail on the proposed fence around the
outdoor dining area. Please provide details on the fence and
dimensions on the site plan for it's layout.
11/25/08 Response: Please see Details 2 and 3 on Sheet A2.1 for the railing description.
Regards,
Warren Campbell
Chief of Planning.
-----Original Message-----
From: Warren Campbell [mailto:WCampbell@vailgov.com]
Sent: Sunday, December 07, 2008 3:07 PM
To: michael@maharch.com; tom.ogg@solarisvail.com; Michael Suman
Cc: Chris Gunion
Subject: Solaris Bo1 Plan review comment
Michael, Mike, and Tom,
I have completed my review of the Solaris Bol and I have only remaining
comments. The proposed railing detail on Sheet A2.1 needs to be
reviewed by the Design Review Board. I have signed off on the Permit
with the exception of the railing which will need DRB approval. Mike
S. lets begin preparing a packet for DRB with lots of little things
like this that we take through periodically. Some photos or
manufacture cut sheets should be provided for the railing in
conjunction with the Design Review application.
12/31/08 Response: Solaris will provide additional infonnation and photos for DRB approval in early 2009.
Thanks
Warren
2211 North Frontage Rd � Suite A � Vail, Colorado 81657 ( Phone 970.479.7566 � Fax 970.479.6666 � solarisvaiLcom
� (04/19/2010) Mike McGee- RE: Fwd: Solaris Phase 2 Page 1 '
From: "Dan Feeney" <dan.feeney@solarisvail.com>
To: "'Mike McGee"' <MMcGee@vailgov.com>, "'Rick Pusch"' <Rick.Pusch@weitz.com>
CC: "'Mark Miller"' <MMiller@vailgov.com>
Date: 04/12/2010 5:13 PM
Subject: RE: Fwd: Solaris Phase 2
Mike: I spoke to Jason Mil�er about an hour ago. I should have BCER's
testing report for Phase 2 conducted last Friday by Wednesday. I'll forward
it as soon as I receive.
-----Original Message-----
From: Mike McGee [maiito:MMcGee@vaiigov.com]
Sent: Monday, April 12, 2010 5:00 PM
To: Rick Pusch
Cc: dan.feeney@solarisvail.com; Mark Miller
Subject: Re: Fwd: Solaris Phase 2
You are pushing the schedule thing a bit.
I expect the Fire Dept would have more than 24 hours for a TCO inspection.
In fact, maybe Weitz needs to re-submit each Phase on the schedule with
specific dates?
Tues is booked, Wed AM is booked, and I am not sure what you even have on
the 2nd TCO list.
Maybe we need some better communication.
I have not heard from Frontier or JCI, or Jason Miller.
Let's start there.
Mike McGee
Deputy Chief
»>"Rick Pusch" <Rick.Pusch@weitz.com> 04/12/2010 4:46 PM »>
»> Rick Pusch 4/12/2010 3:22 PM »>
Mike; last Friday Jason Miller was on site to perform the Life Safety
Inspection which he completed for Phase 2 as Smoke head testing and Phase 3
for Heat detection.
Do I need to schedule you in for a Life Safety inspection as well, or are
you accepting Jason's release?
I would like to call in for the TCO inspection with SafeBuilt by this
Wednesday.
Let me know if you would please so I can schedule the TCO insepction.
Thank you
Phase 2 units include U401, 402, 403, 404, 413, 414, 415, 416, 417 & level 4
west corridor
�,(04/19/2010) Mike McGee-RE: Fwd: Solaris Phase 2 Page 2
Phase 3 units include U501, 502, 503LL, 503UL, 512, 513, 514, 515, 516 &
level 5 west corridor
Information from ESET Smart Security, version of virus signature
database 5023 (20100412)
The message was checked by ESET Smart Security.
http://www.eset.com
Information from ESET Smart Security, version of virus signature
database 5023 (20100412)
The message was checked by ESET Smart Security.
http://www.eset.com
� (05/05/2010) Mike McGee-Solaris TC0 Fire Inspections Page 1
From: Mike McGee
To: Martin Haeberle
CC: dan.feeney@solarisvail.com; rick.pusch@weitz.com; tom.ogg@solarisvail.com
Date: 05/05/2010 12:43 PM
Subject: Solaris TCO Fire Inspections
Martin,
Here is a copy of my comments in Permits Plus.
I plan on trying to do some follow up this afternoon.
Mike
**************************************�**�*****��*********************************�
Phase 1
Item number 1, the NFPA 72 Certificate of Completion, is expected by the end of the day and I have
received verbal confirmation from JCI that all concerns have been met.
Item numbers 2, the BCER report and 5, the Smoke Control Test Report have been accepted and
approved.
�
Item numbers 3, Emergency Operatio s Plan and 4, Imp�irment Permit, have been discussed with
Solaris ownership and are expected by March 24, 2010. �
Item number 6, lack of radio coverage in stairwells, is being addresses by the BDA contractor but take a
few days.
� --—�
Item number 7, elevator phones, is in progress and expected to be completed 3/24/2010.
� Item number 8, emergency lighting, has been reported to have been addressed by the electrical
contractor.
Item 9, General Conditions, appears to have been addressed by BCER. General Conditions will
reassessed during each inspection as part of the on-going inspection and compliance program.
I anticipate the fire alarm system will be monitored by JCl,et.al. and transmission of alarms to Vail
Dispatch will commence on 03/24/2010.
Vail Fire& Emergency Services does not object to the issuance of a Certificate of Occupancy for Phase
1.
Michael McGee
Deputy Chief
Vail Fire & Emergency Services
»> Mike McGee 03/22/2010 10:06 AM »>
**************************************�*�******************************************�
The status of the Solaris project relative to the request for a Temporary Certificate of Occupancy is as
follows:
1. We do not have a copy of the NFPA 72 Certificate of Completion, with or without exceptions.
2. We do not have a copy of BCER's inspection report.
(05/05/2010) Mike McGee-Solaris TCO Fire Inspections Page 2,
3. We do not have a copy of the Emergency Operations Plan as required by IFC Chapter 4.
4. We do not have an application or a plan in support of an Impairment Permit required under IFC 903.1
that would permit locking of the main exit doors from the inside.
5. We do not have a copy of the Smoke Control Test from Brian Thompson. It is noted Brian
communicated the weekly test function has not been tested because it was not programmed into the Fire
Control Panel.
6. The BDA system does not function in the lower levels of the main stairs.
7. The elevator phones have not been tested.
8. We have not re-inspected the lighting for operation under generator power.
9. We have not walked the job site for general conditions (obstructions of exits, fire extinguishers with
current inspection tags, and the rest of the conditions enumerated in the IFC.
Upon receipt of such documentation and completion of the items listed above, the Fire Department will
notify the Building Department.
Michael McGee
Deputy Chief
Vail Fire& Emergency Services
**�«**�****�********�****************************************�********�****�*********�
Phase 2
April 19, 2010
Solaris Project
Phase II TCO Inspection
Notes:
Fourth Floor West Trash Room
" Room not labeled
" No lock on door(finger opening)
" Trash Chute not done
" Sprinkler head not trimmed
" Exit sign to stairs missing
" Light trims missing
Unit 4A West
" Electrical sub-panel still has lock on it
� Stair 3, between levels 3 &4
Indicator valve not visible (originally turned up, was turned down but is now a clearance issue
�
� Keys to fireplaces need to be secured near the shut-offs and accessible
Level 4 West mechanical chase/room
" Room not labeled
" Door closer was disconnected
�(05/05/2010) Mike McGee-Solaris TCO Fire Inspections Page 3'
Unit 4F West
" Sprinkler trim missing
" Mechanical access cover missing
Grease duct access panel missing
Unit 4H West
" Workers in unit, unable to test
" Detectors were bagged
Unit 4A West
" Missing escutcheon in the entry hall
" Trash chute door not functioning properly
" Trash room ceiling has a penetration that has not been fire caulked
" Trash room damper motor access doors don't close correctly due to paint and the lack of closing
springs.
Stair 1
" No light in vestibule
" Sprinkler head loaded at top of stairs
Phase 2. Concern with grease duct clean outs (per MM).
Units 401-404, 413-417, Corridor
�****�*�**********�******�************************�***�***�************��*�****�*�**�
Phase 3 (5 West) and Phase 8 (4 East).
Items to be addressed:
5B (503) Lower Level -Obstructed sprinkler heads in closets.
Elevator graphcs and labels required throughout.
5 F-Sprinkler head in kitchen too close to cabinet.
Stair 6 -5 1/2 level - loose wiring to tamper.
6th floor Electrical Room - Excessive heat. HVAC inoperable.
3 E Electrical Room - Excessive Heat. HVAC inoperable. relocate fire sprinkler head.
Stair 5, 3 1/2 level, Loose wiring to tamper.
Level 2 -Access to remote FACP is impeaded by Main Electrical Switch gear.