Loading...
HomeMy WebLinkAboutSmoke Control Initial Test , i � " . ' i ° � � , e t � e � . • � . . � ... :�� • • - t t• SOLARIS SPECIAL INSPECTION SERVICES SMOKE CONTROL SYSTEM PRELIMINARY Initial Phase INTRODUCTION Special inspection services for the Solaris smoke control system are performed by Thompson LifeSafety Consulting on behalf of Schirmer Engineering Corporation. Schirmer Engineering provided the Smoke Control Rational Analysis for the smoke control system design and retained Thompson LifeSafety Consulting to provide the special inspection and commissioning services for the smoke control system. The Solaris project in Vail, Colorado, is being developed in phases with the Town of Vail. The smoke control system for Solaris, however, is being brought on line for the entire building at the initial phase and will remain in service for the duration of completion of construction and for the life of the building. Consideration is being given to the construction process with the utilization of temporary heat detection in construction areas used for activation of the smoke control system in locations where smoke detection will be provided once construction is complete in those areas. This will prevent false activation of alarms as well as the smoke control system from the dirty and dusty environment of construction. Other than this consideration, the entire smoke control system is permanent in nature at the initial phase. BACKGROUND The Solaris smoke control system is a very simplistic design consisting of pressurization of six stairwell shafts and two elevator hoistway shafts. Each shaft is independently pressurized with a dedicated pressurization fan for each shaft. Smoke control system design detail is provided in the Smoke Control Rational Analysis for the project. This Smoke Control Rational Analysis has been approved and is on file with the Town of Vail. Activation of the smoke control system occurs for each of the pressurized shafts simultaneously upon initiation from specific life safety system devices in the building. Smoke control activation will occur upon initiation of any one of the following: 1. Initiation of an automatic sprinkler system flow switch in the building. 2. Initiation of a fire alarm smoke detector located in close proximity (5— 10 ft) of a pressurized stairwell entrance door on any level of the building. In construction zones (levels) during early phases of the project, these devices may be temporary heat detectors due to the dirty environment and avoidance of false initiation. ._..�.�.a,.�,.����....,y �_�,�. _�. ..,�w.�.,�.� ,.., __M =v�.,��.��.,��m Fire Protectior �r�:�inPerinc� � Code Consulli��� .:: Alternate Means&Methu�i. � Performance Based Dc,r7r� Solaris Speciai Inspection Services Smoke Control System Preliminary 3. Initiation of a fire alarm smoke detector in the elevator lobby of a pressurized elevator hoistway on any level of the building. In construction zones (levels) during early phases of the project, these devices may be temporary heat detectors due to the dirty environment and avoidance of false initiation. There are some locations in the building where a pressurized stairwell entrance door is also a dwelling unit exit door. These dwelling unit exit doors are considered second exits from these dwelling units. In these instances fire alarm detection devices are provided within the dwelling unit within close proximity of the pressurized stairwell entrance door. In most cases these dwelling unit devices are smoke detectors that upon initiation will activate smoke control systems throughout the building as well as activating notification within the specific dwelling unit only. In at least one instance the dwelling unit second exit door is not only an entrance to a pressurized stair but is also residing directly in the dwelling unit kitchen area. To avoid false alarms and false activation of the smoke control system resulting from typical kitchen process generated smoke (burnt food, etc.) in this dwelling unit, the device within close proximity to the pressurized stairwell entrance door is a heat detector instead of a smoke detector. However, activation of this fire alarm heat detector will not only activate the building smoke control system throughout but will also activate the building fire alarm system general alarm. SPECIAL INSPECTION TESTING The testing of the smoke control system was conducted in two phases. The testing of the mechanical features of the smoke control system was conducted on February 16, 2010. The functional or sequence of operation features of the smoke control system was conducted on March 21, 2010. Mechanical Features During the mechanical feature testing of the smoke control system the fire alarm system was not substantially complete. Activation of the smoke control system was performed by manual initiation of a fire alarm system flow switch that was in place. The initial portion of this test consisted of verification of the firefighter smoke control panel (FSCP) being operational by witnessing proper status indication as well as manually controlling each pressurization fan from the FSCP while witnessing proper operation of the outside air damper and starting/stopping of each fan. Times were identified for the process of manually turning a fan on from the FSCP as well as for changing from on status to off status and vice versa. Verification of proper sequence of the position of the outside air damper in relation to the fan status was performed. Also inspected was the manual control of each of the elevator hoistway smoke vents with verification of each vent position. Manual activation of the flow switch results in activation of the entire smoke control system as was the design of this system. Other than through the manual control of individual components via the FSCP, the smoke control system is either entirely on or entirely off through automatic means except when initiation of a smoke detector at the top of any shaft occurs, resulting in that associated fan to shut down. The remainder of this test was a test of the pressure differential across each individual door as well as a test of the door force necessary to open each door while the smoke control system was on. Pressure differentials were measured across each door Page 2 of 2 Solaris Special Inspection Services Smoke Control System Preliminary by use of a pressure differential manometer gauge with rubber hose to pass beneath the door. Door opening force was measured for each door with a pressure force gauge applied at the proper location for opening each door. Pressure differentials were verified to be above the code prescribed minimum of 0.1 inches water column and below the calculated 0.4 inches of water column where these specific doors approach their 30 Ib force opening limit. Door opening force measurements were verified to be less than the 30 Ib opening limit. Sequence of Operation Features At the completion of the fire alarm system installation and approval from the engineer of record for the fire alarm system that the system was installed and tested for this initial phase of the project, the sequence of operations of the fire alarm system and smoke control system were tested. Activation of the smoke control system as a result of initiation of specific fire alarm devices as described above was verified. Sequence of operation of the following was verified: 1. Initiation of the smoke detector in the top of each stairwell shaft to automatically shut down the associated fan once the smoke control system had been activated. 2. Verification that the elevator smoke vent opens upon initiation of the smoke detector in the top of each pressurized elevator hoistway shaft. Manual control of each fan from the FSCP subsequent to initiation of the smoke detector at the top of each shaft was also verified. Visual Inspection The entire smoke control system was also visually inspected. Visual inspections included proper labeling of smoke control associated equipment. Fire alarm devices that are associated with smoke control were verified to be labeled as such. Building automation equipment associated with the smoke control system was verified to be labeled as such. Visual inspections also included inspection of proper construction techniques. Shaft construction was visually inspected to be tight and without obvious leakage points. Fire-resistance rated construction of rooms where smoke control system equipment resides was inspected for proper fire stopping and construction techniques. Emerqency Power Observation The smoke control system was observed to properly operate while transfer of the building normal power to the building emergency generator power takes place. Likewise, it was observed that activation of the smoke control system occurs while the building emergency generator power is on. Allowable times for the system to switch over were observed. TEST RESULTS AND FINDINGS The following items are identified as punch list items that need correction as a result of the special inspection of the smoke control system: 1. The normal (white) LED on the FSCP for Stair 5 is burnt out and needs replaced. Page 3 of 3 Solaris Special Inspection Services Smoke Control System Preliminary 2. It has been discovered that the pre-programmed weekly self test does not latch fault conditions to the FSCP. This is a condition not capable of this system as it was built by the manufacturer. As a result, an initial print out of the pre-programmed weekly self test must be provided. In addition, it is required that the print out of this weekly test be maintained on record in a 3 ring binder in the Fire Command Center for observation by the Town of Vail Fire Department. This was an agreement with Deputy Chief, Mike McGee with the Town of Vail Fire Department. 3. At the time of testing, the fire alarm contractor did not have the ability to change the pre- programmed time at which the weekly self test of the smoke control system occurs. As such, this special inspector was not able to test the weekly self test and verify that this test does not interFere with proper operation of activation of the smoke control system during the weekly self test. This testing remains to be performed by this special inspector. CONCLUSION Special inspection test results of the Solaris smoke control system for this initial phase are considered acceptable. The smoke control system is considered in proper installation and operation for the initial phase of the building construction. This testing and report is considered preliminary as the smoke control system will require subsequent testing and verification at the final phase of construction. Any cause for suspicion that the smoke control system has been modified or changed during the intermediate phases of construction would also be cause for subsequent testing of the smoke control system before the final phase of construction. As special inspector for the Solaris smoke control system I approve the system ready initial phase of the project. �o�,a�� t�c�2s ,.......� . Gd;•�ao•7H02j,o�O :tL �p: i°° 3��6� zs _��:�. . . �°�'•. .•r�� . h.Pn„_""�. ��FSS/ONA����\��. March 23, 2010 Brian O. Thompson, PE Page 4 of 4