Loading...
HomeMy WebLinkAboutPhase 1 BCER Marc E.Espinosa David B.Robinson,P.E. Richard D.Matthies,P.E. E N G I N E E R 1 N G Stephen C.Rondinelfi,AIA teu<fei:siirtr tfrroutth 7.'n£rn«erin�t Robftl(t�.°Mike"Corde%P.E.LEED"P March 22,2010 Mr.Martin Haeberle Chief Buitding Official Town of Vail 75 S�rontage Road Vait,CO 81657 Chief Mike McGee,Deputy Fire Chief Town of Vail Fire Department 75. 5 Frontage Road Vail,CO$t657 SOLARIS—Phase 1 �ire Protection System Corntnissioning Dear Martin: In accordance with the approved September I l, 2008, Phase Occupancy Plan for Solaris as prepared by Schirmer Engineering, BCER has performed and witnessed the inspections of the fire alarm system and sprinkler system for the areas included in the Phase I Occupancy at Solaris. These areas are shown as the highlighted areas on the attached drawings. This letter serves as the documentation of that testing and provides an overview of the inspection procedures and findings. Automatic Sprinkler Svstem Inspections of the sprinkler system began on January 19, 2010 with the witnessing of the operational test of the fire pump. Further visual inspections of the system were conducted over subsequent weeks and included operational tests of all valves and flow switches, within the Phase 1 Occupancy areas, concurrent with the fire alarm system testing as well as visual inspection of final installation of sprinklers.4ur inspections indicate that the system is operational and installed in accordance with NFPA 13 within the Phase 1 Occupaney Areas, with tl�e exception of the following items: I. Green Parking Area a) Bay 1: Southwest corner of garage 1 head is sprayed with monocoat and needs to be replaced. b) Bay 1: Storage area for the Merino Tile,right of entry 1 head is sprayed with monocoat and needs to be replaced. c) Bay 1: Merino area back storage(grout area) 1 head is sprayed with monocoat and needs to be replaced. d) .Bay 1: In the area near heat detector NO1-LO1-M7, 1 head is sprayed with monocoat and needs to be replaced. e) Bay 1: Southeast area by the exit sign, l head is sprayed with monocoat and needs to be replaced. t� Three bays east of item(e), 1 head is sprayed with monocoat and needs to be replaced. g) One bay east of item(fl, 1 head is sprayed with monocoat and needs to be replaced. C:IDOCUMF:NTS AND SETTING5ISCR\DESKTOP\SOLARIS TCO PHASE I 3.22.IO.DOC 5420 WARD ROAD,SUITE Z00,ARVADA,CO�ORADO 80002-1838•T[�EPHONE: 303-422-7400•fAx: 303-422-7900 h) Bay 1: Paver storage area,�heads are sprayed with monocoat and need to be replaced. i} Bay I: Main Electrical Room, 1 head�s sprayed with manocoa�and needs to be replaced. j) �ay 2: Within the E-Light Fenced area, al the soutl7west end,2 heads are sprayed with mo�ocaat and need to be replaced. k} Bay 2: In the unfe�iced area by ducts, I pendant is sprayed with monocoat and needs to be replaced. 1) Bay 2: In-line with the sewage ejector box, 1 pendant is sprayed wiEh monocoat and needs to be reptaced. m} Bay 2: In the area near FPI's tool Iock«p, 1 head is sprayed with tnanocoat and needs to be replaced. n) Bay 2: Above the exit sign in this area, 1 head is s�rayed with monocoat and needs to be replaced. o) One bay ta the west of Item(n), 1 head is sprayed with monocoat and needs to be replaced. p) Bay 2: Near the eIectrical rc�om and Stir Fan GSF-1, I head is sprayed with mot�ocoat and needs to be replaced. q) Bay 2: A sprinkler needs ta be added by ceiling mounteci box labeled ELPH_CAM_SW 1 #I,2, 3). r) Bay 2: A sprinkler needs to be added in the drive lane near Item(q). 2. Orange Parking Area a) Bay 3: In the area west of the Service Elevator,near the heat cail,there are two heads within 6 feet of each other.The spcinklers need to be relocated. b) Bay 3: Near Stair 5 and the exit sign, 1 head is sprayed with monocoat and needs to be replaced. c) Bay 3: Near Stair 5, 1 head is sprayed with monocoat and needs to be replaced. 3. Yellow Parking Area a) Several pendants in the ramp area were obstructed by hanging lights. 4. On Level 1,at the Zamboni entrance, within the service coiridor,the cover plate for the sprinkler was damaged and needs to be replaced. 5. Generai: The pressure relief valves on the sprinkler risers need to be replaced with valves rated at a higher pressure to prevent them from constantly leaking. 6. General: Sprinkler escutcheons throughoat the Phase 1 Oceupancy areas will need to be visuatly inspected periodically to ensure that they remain properly installed throughout the constiuction process. Fire Alarm Svstem The fire alarm system was inspected, and operational tests, were performed over the course of several weeks, beginning March 11, 2010. All fire alarm devices within the Phase 1 Occupancy area were inspected and tested. Additionally, temporary heat detectors installed on the West Retail Areas on Level 1 and Level 2 were inspected. All initiating devices, cun•ently installed, for the activation of smoke control were inspected. All elevator recall and shunt t►•ip functions were inspected. Our inspections indicate that the fire alarm system is operational and installed in accordance with NFPA 72 within the Phase 1 Occupancy Areas, with the exception of the following items: 1. Speakers installed within the exit passageways activate on a general alarm condition. Speakers within the exit passageways should only activate when the associated stair speakers are activated. 2. The visual notification appliances within the west service corridor on Level 2 are not synchronized. In this area there are more than two groups of strobes that flash at different rates.NFPA 72 states that no more than two groups of strobes within the same field of view shall have different flash cates. 3. A heak detectar��eeds to be added in the Pool Equipment Room in the Loading Dock on Level 3. 4. At the request of the Fire Marshal,the speaker within the Fire Pump Room needs to be removed. A visual only notification appliance is to be installed in the Fire Pump Room. 5. The manual pull station located within the front desk in the Lobby on Leve] 3 needs to be relocated to tl�e wall behind the front desk. 6. All visual notification appliances installed on the ceiling need to be replaced with appliances listed for ceiling installation. C:\DOCUMF..NTS AND SETTINGS\SCR\DESKTOP\SOLARIS TCO PHASE 13.22.1Q.DQC 5420 WARD ROAD,SUIT[200,ARVADA,COLORADO 80002-1�i3E3•T�i.FrHONE: 303-422-740n•Fnx: 303-422-7900 7. The visuai notificatio�� a�pliance toc�ted cn the service corridoi�ocitsic3e of t�1e Lob�y Restaurant or� �,evel 2 is mounted too high.The�ppli�nce needs to(�e��elocated. �. The"Normal"LED on the Firefighter's Smoke Contral Pa�tel for�tair 6 needs ta be replaced. 9. The fire alarm co���r�l panel indECat�s a trotible condition mon�ecttaril.y(A�lnttnciato��2Q Trouble},after being reset.This iss�ie needs to be caneeted. 10.Stair 4 and Stair 6 are an the same�mat�ual paging zane at the fire alarm control paneL Each stair is required to have its awn manual.paging zo�te. 11.Ti�e man€�al paging zone labels shauld be updated to show only the aetive ma��uat paging zones. As ai7 example,West Blevator 4A is the ai��y elevator with active manual p�ging. 12.Operational Instructiot�s for the fire alarin control panel are to be placed iiz the fire command roon�. At the request of the Fire Department,inst�ctions showing how ta disable a device should be placed near the fire alarm control panel. 13.The na�•rative description far the t►�ouble eondition that occurs when a switch is manua[ly activated on the firefighter's smoke control panel needs to be updated ta iE�tdicate"Man€�al Sinoke Control Mode", or simitar. 14.The narrative descri.ption for all fire alarrn in[tiating deviees needs to be co�Ytiz�ually reviewed throughout the construction process to ensure accuracy and consistency. I5.When instructed to do so by the Fire Departme��t,all protective covers on the smoke detectors are to be removed, within the Phase I Occupancy Areas. 16.Fire Alarm cievices that are marked for replacement,due to eosmetic damage de�ring the construction process, should be replaced as soon as possible. 17.At the time of our inspection,the fire alarm system was reporting to the Central Station,however was not reporting to the Town of Vail. Whe��instructed to do so by the Fire Depat-tment,Che fire alarm system monitoring needs to be placed on-line with the Town of Vail. Smoke Control S,stem The final commissioning of the srnoke control system was performed by Schirmer Engineering. BCER was present to witness the final functionai testing that occurred on Macch 20, 201Q. 5chirmer Engineering has prepared a report outlining their findings. That report is attached ta this document for reference. BCER's inspections were limited ta the fire alarm devices associated with the smoke control system, only. Other Life Safetv Tssues During the course of our inspections related to the fire alar�n and sprinkler• systerns, we noted other fire protection and life safety issues within the building, although such observations were not part of our commissioning and testing responsibility BCER did perform a cursory inspection of the building for building code compliance. These items were generally related to exit signage, door ratings, fire rated penetrations and storage of construction materials. BCER reported those �ndings to the Weitz Company for investigation and correction.The Weitz Company generally con•ected any deficiencies immediately. The Phase I as described in the approved phase occupancy plan for fire alarm and sprinkler systems are complete and functional for the Phase 1 Occupancy areas.The deficiencies listed within this document will not affect the ability of the systems to provide the required level of protection to the occupants within the Phase 1 Occupancy areas; however,correetive action should be taken to complete these items as soon as possible. I know both of you are aware that this is Phase I of the Phased Occupancy Plan with additional testing and commissioning occurring throughout the remaining phases. C:\DOCUMENTS AND SETTINGS\SCR\DESKTOP\SOLARIS TCO PHASE I 3.22.10.DOC 5420 W�1RD ROAD,5UITE 20Q ARVADA,Co�oRnr>n fl0002-1838•TfLEPHOUE: 3D"3-422-7400•FAX: 303-422-7900 Prepared hy: BCER Engineering,Inc. . .�`- ,e��'M� �. ��(� Jason Miller, Fire Pratection ConsultanE i�fri�f.r.�,,r�`^ Reviewed by: ��to�Q�Q�T1Q RF�,,�s�_ �o,��/c,�—� -3- �'3-/d h�4�G ;�q�' �.Q�,�`��=,� a ;�o �" Q� ,a, 361¢� �c : Todd Gardner FPE ` -�: ' : > � g. � 4 Fire Protection Engineer �o,i+fi•., .;1���44e� � �-�`�NAt E�'�G �� ,..°�"°"' ��.a.�i r�{!A Ste en Rondinelli, AIA Prin 'pal, Director Fire Protection and Life Safety c: Dan Feeney, Solaris C:\DOCUMF,NTS AND SETTINGS\SCR\DESKTOP\SOLARIS TCO PHASI:I 3.22.�O.DOC 5420 WnrtD ROnD,SUITE 200,ARVADA,COI C)RADO 80002-1 83 8�TELEPI IoNE: 303-422-7400•F�x: 303-422-7900