HomeMy WebLinkAboutE10-0162TOWN OF .
ELECTRICAL PERMIT
Job Address: 2399 N FRONTAGE RD W VAIL
Location.......: FIRE STATION #3
Parcel No.....: 210311415019
OWNER TOWN OF VAIL 07/30/2010
75 S FRONTAGE RD
VAIL
CO 81657
APPLICANT DAVE PETERSON ELECTRIC
P.O. BOX 711
EDWARDS
CO 81632
License: 119 -E
CONTRACTOR DAVE PETERSON ELECTRIC
P.O. BOX 711
EDWARDS
CO 81632
License: 119 -E
Permit #...:
E10 -0162
Project #..:
PRJ10 -0196
Issued......:
08/06/2010
07/30/2010 Phone: 970-926-4140
07/30/2010 Phone: 970- 926 -4140
Desciption of Work: NEW COMMERCIAL BUILDING: FIRE STATION #3
Valuation: $266,756.00 Square feet: 10416
CONDITIONS OF APPROVAL
Cond: 12
(BLDG.): FIELD INSPECTIONS ARE REQUIRED TO CHECK FOR CODE COMPLIANCE.
Cond: 42
(BLDG 2009) CARBON MONOXIDE DETECTORS REQUIRED TO BE INSTALLED PER 2009 IRC R315
INSPECTIONS
If more than two inspections are performed an additional inspection fee will be applied for each inspection requested /needed.
All electrical inspections are performed on Tuesdays and Thursdays. Requests must be received the day before and not later
than 4 p.m.
DECLARATIONS
I hereby acknowledge that I have read this application, filled out in full the information required, completed an accurate plot
plan, and state tha all the information as required is correct. I agree to comply with the information and plot plan, to comply
with all Town ordin nces and stat�aws, and to build this structure according to the towns zoning and subdivision codes,
design review appr o ed, I rnation I Bu'Idi g and Residential Codes and other ordinances of the Town applicable thereto.
SIGNATURE: ' / Date
(Master / hom owner / or non - licensed contractor performing work)
PRINTED NAME: h -zl Z"2
Town of Vail Community Development
75 South Frontage Road, Vail, Colorado 81657
p. 970.479.2139 f. 970.479.2452 inspections 970.479.2149
elec _permi 100109
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
TOWN OF VAIL, COLORADO Statement
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Statement Number: R100000997 Amount: $5,260.08 08/06/201001:24 PM
Payment Method: Check Init: LC
Notation: #25879 / DAVE
PETERSON ELECTRIC
-----------------------------------------------------------------------------
Permit No: E10 -0162 Type: ELECTRICAL PERMIT
Parcel No: 2103 - 114 - 1501 -9
Site Address: 2399 N FRONTAGE RD W VAIL
Location: FIRE STATION #3
Total Fees: $5,260.08
This Payment: $5,260.08 Total ALL Pmts: $5,260.08
Balance: $0.00
************************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
ACCOUNT ITEM LIST:
Account Code Description Current Pmts
-------------- - - - - -- ------------------------ - - - - -- ------ - - - - --
00100003111100, GFPO ELEC PERMIT FEES- GFP012 2,355.00
EP 00100003111100 ELECTRICAL PERMIT FEES 830.50
PF 00100003112300 ELEC PLAN REVIEW 2,070.58
WC 00100003112800 WILL CALL INSPECTION FEE 4.00
Department, of Community Development
ELECTRICAL PERMIT
Electrical Permit Submittal Requirements Incl Heat Tape Installation
Floor plan / Site plan showing proposed work
c Building Type
❑ Occupancy Group listed on plans
c Load Calculations and one -line diagram when loads or circuits are being added
NOTE: For Multi - Family and Commercial bulldings —plans and calculations must be prepared by a Colorado Licensed Electrical Engineer
Project Street Address:
Z _ - 31 9 N - Fi _- --
(Number) (Street) (Suite #)
Building /Complex Name:
Contractor Information: [�
Company: �`j2, _tkusan Ua4yIr✓ ,n
Company Address: r JD bov, - 1 t [
City: _F� W6Yi4 S State: Co zoo U '�)2
Contact Name:
Contact Phone:
E -Mail Y 7 . C&A
Tow of it Contractor Re - tion No.: t� '
X �
L "v
Office Use:
p;oj: M K �0 -_
Building Permit #,
Al
Elegy r : Lo` 9 K Subdi
Oe�'ine Scope and Location of Work
use additional sheet if necessary)
Includes Temporary Service: ( ) Yes ( ) No
Cont for Signature (required) work Class:
New Addition ( ) Remodel ( > Repair t )
Property Information -Othey
<
Parcel: IS -c) a
(Fo; parcel #, contact Eagle CountyA_:.essors Office at 970 - 3.8.8640 or Type of Building:
visit www,eaglecounty.us /patie) Sino!e- F=amily ( ) Duplex ( ) Multi - Family { Commercial
Tenant Name: _ Restaurant { ) Other( )
Owner Name: In CAL
Date Peceived:
Provide BOTN square footage of area of work AND Valuation � � � 0 �/ E
(Labor & Materials) r1 - �
Amount of SQ Ft., _4_V� 1 U __..._. JUL 28 2010
Electrical S: to
TOWN OF VA!L
Ui• ?an -IJ
05 -16 -2011 Inspection Request Reporting Page 12
5:22 pm Vail, CO = City pf
Requested Inspect Date:
Site Address:
A/P /D Information
Activity: E10 -0162
Const Type:
Owner: TOWN OF VAIL
Type: B -ELEC
Occupancy:
Contractor: DAVE PETERSON ELECTRIC
Description: NEW COMMERCIAL BUILDING: FIRE STATION #3
Requested Inspection(s)
Item: 190 ELEC -Final
Requestor:
Comments: 390 -1861
Assigned To: fGIER
Action: Time Exp:
Comment: Menerator to be tested
Comment:
Commen :
Sub Type: NCOM
Use:
Phone: 970 - 926 -4140
Status: ISSUED
Insp Area:
Requested Time: 09:00 AM
Phone:
Entered By: MHAEBERLE K
Provide load bank test
Manufacture to provide letter on MDP main Disconnect settings
Need egress lighting walk through
Need to hook up water pipe grounding electrode
need access to all ares in garage after floors dry
GFCI with in 6' of laundry sink
mnk closet to have blank or control for exhaust fan
Cu \O pending generator, load bank test, a ress lighting walk through, VFD's are not accessible check w/
manufacture for solution to move them. We living areas should be regulated by by 210.18 210.60 and
210.52 of the 2008 NEC. Martin H. has made a call to disreguard these areas to comply with the above
code sections
courtesy inspection
Inspection History
Item: 120 ELEC -Rough
** Approved **
12/07/10
Inspector: sgremmer Action: PA PARTIAL APPROVAL
Comment:
1 st floor walls only
12/16110
Inspector: sgremmer Action: PA PARTIAL APPROVAL
Comment:
2nd floor ceiling and walls at bedroom only walls in kitchen only
01/21/11
Inspector: sgremmer Action: PA PARTIAL APPROVAL
Comment:
Cans at soffits and west side 2nd floor
02/25/11
Inspector: mdenney Action: PI PARTIAL INSPECTION
Comment:
Above - ceiling inspection: 1 st floor meeting room, chiefs office, Inspector's office, plan room,
copier room and vestibule for plan room.
03/09/11
Inspector: sgremmer Action: AP APPROVED
Comment:
above ceiling only
Item: 190 ELEC -Final
03/22/11
Inspector; sgremmer Action: PI PARTIAL INSPECTION
Comment:
courtesy inspection
03/31/11
Inspector: sgremmer Action: DN DENIED
Comment:
Generator to be tested
Provide load bank test
Manufacture to provide letter on MDP main Disconnect settings
Need egress lightin walk through
Need to hook up water pipe grounding electrode
need access to all ares in garage after floors dry
GFCI with in 6' of laundry sink
mop sink closet to have blank or control for exhaust fan
04/07/11
Inspector: sgremmer Action: PI PARTIAL INSPECTION
REPT131
Run Id: 13095
Tuesdayy, Mayy 17 2011
2399 N FRONTAGE RD W VAIL
FIRE STATION #3