HomeMy WebLinkAboutA10-0029 Data Sheet 1010 IPF Series VPM SDM Data Sheet 1010 /�l � B u I �t
Engineered Systems
IP Fire SeriesT"' � -�
Intelligent Fire Controls
• VPM
• SDM
�. : ���
Description
�i � �
The architecture of an IP Fire SeriesT"' control network is comprised of a � �
series of IP based distributable modules.These modules include !��` . '" `=:��
alternate configurations of SLC and NAC circuit modules(ALM-xy), �`� '' . ' ����
standard display modules (SDM), annunciator control modules(ACM)
and other specialized modules noted in other documents. �� ��
The first module on every IP FireT"" network is a display module that is Features
designated as the Virtual Panel Module(VPM). Network configuration
and management are initially performed through the VPM. Its terminal . VPM provides the initial gateway to
interface display acts as a gateway to the other modules installed in the other installed modules
network and can interact with any device configured on those modules. . VPM provides module IP address
assignments
A single VPM can interact with up to 50 distributed modules of any type in . VPM Interacts with up to 50
any configuration.As modules are attached to the network, they obtain networked modules per system
their IP address assignments from the VPM managing the modules on . VPM and SDM provide for panel level
the fire control network. All modules are connected via an RTR-1, RTR- configuration
2, RTR-3 or equivalent hub, or directly(by use of a cross-over cable)to . VPM and SDM each provide two built-
the VPM. in USB 2.0 Type A access ports for
upload/download of system
Once connected, SDM's provide identical features/functions as the VPM. programming to/from any standard
SDM's may be installed in any number up to the system maximum of 50 USB Mass Storage Device
modules. SDM can be installed in any number
VPM/SDM modules feature a '/4 VGA graphical user interface, • up to system max of 50
programmable soft keys, system event annunciation, acknowledge, signal • �4 VGA viewing screen
silence, and reset switches along with separate switches for sorting • Programmable soft keys
history logs. Drill and lamp test are also accessible from any VPM/SDM. • View history log of any attached
module
VPM/SDM modules feature two integral USB 2.0, Type A ports for easy • Access limited by locked LexanT"'
system access.The USB ports can be utilized to program/back- door on IPF-XL or key enabled dead
up/restore any or all IPF Series modules located anywhere on the front construction on all other
network to/from any standard USB Mass Storage Device. cabinets
• 3000 event history log per module
A 3000 event history log is available on every IP FireT"' system module. . Modular listing
Any VPM/SDM is capable of retrieving and viewing the history log of any . Green/RoHS Compliant
attached module.The history logs are presented in a retrievable list and
can be easily viewed on the display of any VPM/SDM or downloaded to a
USB Mass Storage Device. Listinas
The VPM and SDM have an optional USB extension module(UXB)that UL File: S24573
provides access to the two built in USB ports at the front of the system CSFM: Pending
cabinet. Port access is limited on IPF-XL systems by a locked LexanT"^ MEA: Pending
door and on IPF systems by a key-activated enable/disable switch
located on the exterior of the cabinet.
Any module on an IP Fire Series control system can be viewed,
interrogated, configured, backed-up/restored or programmed from the
VPM or anv SDM on the svstem reaardless of location.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"' VPM/SDM 1010 1.3/5/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install, where indicated on the plans, a VPM module for access to a distributed fire
protection network.The VPM must be capable of assigning IP addresses on an IP based fire network and supervising up
to 50 distributed modules consisting of analog loop/NAC circuit modules(ALM), standard display modules(SDM)and
annunciator control modules (ACM) in any configuration/mix. The VPM and SDM shall provide 2 integral USB 2.0 Type A
access ports for program upload/download to/from any standard USB Mass Storage Device.The VPM and SDM shall
have a'/VGA graphical viewing screen with programmable soft keys and shall utilize the IPF Series built in QWERTY
keypad or be capable of working with any standard IBM compatible USB wired or wireless keyboard.VPM and SDM
modules shall be capable of retrieving and viewing any history log of any connected module. VPM and SDM modules
shall be protected by a key-activated enable/disable access switch or otherwise located behind a locked LexanT"" door.
The VPM and SDM shall have multiple levels of password protection. Each VPM/SDM shall maintain an integral 3000
event history log.The VPM, SDM and combination of networked modules must be UL listed and UL listed as compatible
with the AsBuilt IP Fire Series network fire controls.The VPM and SDM modules shall be As Built Engineered Systems
part numbers VPM and SDM.
Technical Data
Quiescent Power Draw: 165 mA Access Ports
Alarm Power Draw: 185 mA
USB 2.0 Type A: 2
RS-232 Serial Interface: 1
Connection Pins Event Port: 1
Masterbox Connection/Line Reversal: (MBLR) Maximum Modules
Common Control Relays (CCR)
QWERTY Keypad (KPD) VPM: 1
SDM: Up to system maximum of 50
Orderinq Information
Part Number Data Sheet Description
VPM 1010 VPM Module for System Management
SDM 1010 Standard Display Module
SDM-NY 1010 Standard Display Module NYC Enclosure
Related Modules, Accessory Cards and Cabinets
ALM 1020 Analog SLC and NAC circuits
MBLR 1051 Optional Masterbox/Line Reversal card
CCR 1051 Optional Common Control Relay Card
KPD 1053 Optional QWERTY Keypad
UXB 1052 Optional USB Extension Card
UXB-KS 1052 Optional USB Extension Card/Key Activated
RTR, EPROT 1030 Optional Routers and Ethernet Protection Cards
RTR-3 1030 Fiber-Optic Long Haul Routers
Cabinets 1045 IPF-xy, IPF-XL and REM-Cabinet Options
IPF/IPF-XL 1050 IPF-xy, IPF-XL Pre-Configured Systems
iView 1055 Graphical Display Software
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"" VPM/SDM 1010 1.3/ 1/1/2009 iPFiReseRies°
As Built Engineered Systems, Inc. Phone: (508)788-8333 �
1451 Concord Street Fax: (508)788-8334 �� � � � I�
Framingham, MA 01701-7782 Contact: info@asbuiltes.com
USA Visit: www.asbuiltes.com Engineered Systems
O Copyright 2008 AsBuilt Engineered Systems, Inc.