HomeMy WebLinkAboutM02-0200 PlansMECHANICAL EQUIPMENT SPECIFICTIONS: AHU -1, H & V UNIT HORIZONTAL CONFIGURATION HOT WATER HEATING COIL INSULATED STEEL CASINGS, REINFORCED AND BRACED WITH STRUCTURAL HOT WATER COIL SHALL BE ARI CERTIFIED. STEEL FRAMEWORK, FACTORY ASSEMBLED WITH BAKED ENAMEL OR HOT RETURN AIR AND OUTSIDE AIR DAMPERS SHALL BE DIPPED GALVANIZED FINISH. FAN AND COIL CASINGS INSULATED INSIDE THE COIL SHALL BE OF EXTENDED SURFACE, STAGGERED TUBE, RIPPLE — WITH 1 ", 1 -1/2 POUND, MAT FACED GLASS —FIBER INSULATION. PROVIDE CORRUGATED ALUMINUM PLATE FIN TYPE, INCLUDING, BUT NOT LIMITED ACCESS DOORS IN CABINET SO THAT THE FAN AND COIL COMPARTMENTS MAY TO, NON— FERROUS HEADERS, SEAMLESS COPPER TUBING, COOPER ALLOY BE INSPECTED. BRAZED JOINTS, HEAVY GAUGE GALVANIZED STEEL CASING AND COILS WITH RETURN AIR DAMPER SHALL OPEN WHENEVER THE SUPPLY NO EXPOSED COPPER BETWEEN FINS. COMPLETE COILS SHALL BE TESTED DWDI CENTRIFUGAL FANS WITH FC WHEELS, STATICALLY AND DYNAMICALLY AND GUARANTEED FOR 250 PSIG WORKING PRESSURES AND SHALL BE BALANCED AND TESTED AFTER UNIT ASSEMBLY. GREASE LUBRICATED BALL ENCLOSED IN A BAKED ENAMEL — COATED HOUSING SERVICEABLE THROUGH A BEARINGS WITH EXTENDED FITTINGS, SELECTED FOR 200,000 HOUR LIFE. LIFT —OUT ACCESS DOOR WITH ALUMINUM TWIST LATCHES. UNIT PERFORMANCE TO BE RATED IN ACCORDANCE WITH ARI STANDARDS. HEATING COIL SHALL BE SUPPLIED AS AN INTEGRAL PART OF THE FAN C. THE HEATING COIL CONTROL VALVE SHALL BE PACKAGE. ALL PIPING AND CONTROLS SHALL BE FURNISHED BY THE ALUMINUM PLATE FIN, COPPER TUBE COILS WITH GALVANIZED STEEL CONTRACTOR. CASING AND CAST IRON OR COPPER TUBE HEADER. ENCLOSE COIL HEADER POSITIONED TO FULL FLOW FROM HEAT SOURCE THROUGH AND U —BENDS IN INSULATED COIL CASING. EVAPORATIVE COOLING SECTION MEDIUM CAPACITY COMBINATION FILTER/MIXING BOX WITH 2" THICK GALVANIZED STEEL CASTING, BAKED ENAMEL EXTERIOR FINISH, FOR DISPOSABLE FILTERS AND PARALLEL BLADE DAMPERS AND DUCT CONNECTION (DOWN) (HORIZONTAL) DISCHARGE. FILTER PADS TO BE REPLACEABLE FLANGES. COTTON MESH WITH 3X3 PER INCH OUTSIDE SURFACE MESH AND 16X20 PER DISCHARGE PIPING SENSING WATER FLOW FROM THE INCH INSIDE SURFACE MESH AND ASPEN AND REDWOOD FIBER FILL. EACH 18 GAUGE GALVANIZED STEEL CHANNEL OR 1/8" EXTRUDED ALUMINUM FILTER CARTRIDGE SHALL HAVE WATER TROUGH WITH VISIBLE OUTSIDE DAMPER FRAMES WITH REINFORCED CORNER BRACING. DAMPER BLADES ADJUSTMENT. ADJUSTABLE V —BELT DRIVE. MOTOR AND BLOWER WHEEL TO SUITABLE FOR HIGH VELOCITY PERFORMANCE AND SHALL NOT EXCEED SIX BE ISOLATED WITH RUBBER CUSHIONS. F.G. GALVANIZED STEEL, CEN (6) INCHES IN WIDTH. NYLON OR TEFLON DAMPER BUSHING. PROVIDE TRIFUGAL BLOWER WHEEL WITH SELF ALIGNING PERMANENTLY LUBRICATED ALL EDGES OF THE BLADES AND TOP, BOTTOM AND SIDES OF THE FRAME AND SEALED BALL BEARINGS. WITH REPLACEABLE, SYNTHETIC RUBBER OR P.V.C. SEALS; SIDE SEALS ALARM AND THIS FAN INTERLOCK WHEN PUMP IS OFF FROM MAY BE SPRING GRADE STAINLESS STEEL. THE SEALS SHALL PROVIDE A HEAVY DUTY WATER RECIRCULATING PUMP AND MOTOR WITH PLASTIC SUC MAXIMUM LEAKAGE OF 10 CFM /SQ.FT. 0 1" PRESSURE DIFFERENTIAL TION SCREEN, AND NECESSARY INTERNAL DISTRIBUTION PIPING. MAKE UP ACROSS THE DAMPER AT 4 INCH — LB /SQ.FT. TORQUE. THE DAMPER LINK VALVE WITH ADJUSTABLE FLOAT ASSEMBLY. OVERFLOW PIPE TO EXTERIOR AGE SHALL PROVIDE LINEAR FLOW OF NEARLY EQUAL PERCENTAGE CHARAC OF UNIT. GALVANIZED STEEL SUMP WITH WATERPROOF ASPHALTIC BASE TERISTICS. MECHANICAL CONTRACTOR TO PROVIDE DUCT DETECTOR IN SA DUCT. UNDER COAT AND SEPARATE OVERFLOW AND DRAIN CONNECTIONS. ADJUSTABLE V —BELT DRIVE AND GUARD WITH MOTOR OUTSIDE OF THE AIR CONTROLS: PROVIDE A 6 POSITION REMOTE WALL MOUNTED CONTROL STREAM AND MAGNETIC STARTER AS DETAILED IN SCHEDULE ON DRAWINGS. SWITCH WHICH SHALL BE CAPABLE OF THE FOLLOWING POSITION; OFF, SENSED, ALL FANS SHALL BE OFF, AND THE HEATING PUMP ONLY, HIGH COOL, LOW COOL, HIGH VENT, OR LOW VENT OPERATING INSTALL THE UNIT ON INERTIA BASE WHERE CALLED FOR, ON SPRING FOR COOLING, VENTILATING OR PRE — WETTING OF THE PADS FROM A SINGLE VIBRATION ISOLATORS AND NECESSARY SUPPORTING STRUCTURE. SWITCH. CU -1, REMOTE AIR COOLED CONDENSER PROVIDE A FILL AND DRAIN KIT WHICH WILL AUTOMATICALLY DRAIN THE 2. CONTROL SUMP AND SUPPLY LINES WHEN THE OUTSIDE AIR TEMPERATURE DROPS THE CONDENSER SHALL HAVE A BELT DRIVE, CENTRIFUGAL TYPE FAN. FAN BELOW 400F. THE KIT SHALL AUTOMATICALLY REFILL THE SUMP WHEN THE MOTOR SHALL BE PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH TEMPERATURE RISES ABOVE 550F. THE KIT SHALL INCLUDE A THREE —WAY INHERENT THERMAL OVERLOAD PROTECTION. PROVIDE FACE AND BYPASS WATER SUPPLY VALVE AND A TWO —WAY SUMP DRAIN DRIVE. DAMPERS, MEDIUM CAPACITY FILTER AND BOTTOM FILTER AND COIL PULL. THERMOMETER THE CONDENSER COIL SHALL BE COPPER TUBE ALUMINUM PLATE FIN CON PROVIDE A 12 OZ /YARD CANVAS COVER TO OWNER FOR WINTER USE. STRUCTION WITH COIL GUARDS. A LIQUID RECEIVER SHALL BE PROVIDED THERMOSTAT FOR REFRIGERANT CIRCUITS. THE CONDENSER COIL AND RECEIVER SHALL EF -1, GREASE EXHAUST FAN HAVE STORAGE CAPACITY TO PROVIDE SYSTEM PUMP DOWN. AMBIENT AIR CONDITIONS: 85OF E.D.B. ALUMINUM, WATERTIGHT, REMOVABLE HOUSING FOR UPBLAST DISCHARGE D. WITH ALUMINUM BLADES, AND ALUMINUM OR GALVANIZED STEEL BIRD MUA -1, MAKE —UP AIR UNIT SCREEN ON DISCHARGE. RESIDUE TROUGH AND DRAIN. B.I. CENTRIFUGAL --II TYPE FAN WHEEL, STATICALLY AND DYNAMICALLY BALANCED. V —BELT THE SUPPLY FAN UNIT SHALL BE OF THE BELT — DRIVEN, DOUBLE WIDTH, DRIVE WITH ADJUSTABLE MOTOR SHEAVE. MOTOR AND FAN MOUNTED ON DOUBLE INLET, FORWARD CURVED CENTRIFUGAL BLOWER TYPE. THE BLOWER VIBRATION ISOLATORS. MOTOR AND STARTER AS DETAILED IN SCHEDULE. ASSEMBLY SHALL BE MOUNTED ON VIBRATION ISOLATORS. DRIVES SHALL MOTOR AND DRIVE COMPARTMENT TO BE OUT OF EXHAUST STREAM WITH BE SIZED FOR A MINIMUM OF 165% OF DRIVEN HORSEPOWER. ALL VENTILATION OF OUTSIDE AIR THRU MOTOR COMPARTMENT. MOUNT ON EXTERIOR HOUSING COMPONENTS OF THE SUPPLY UNIT SHALL BE NECESSARY CURB. CONSTRUCTED OF MINIMUM 18 GAUGE GALVANEAL STEEL, PAINTED WITH A SETTING" UNTIL THE SPACE TEMPERATURE IS BROUGHT WEATHERPROOF FINISH THAT HAS BEEN BAKED FOR DURABILITY. HEAVY WITH THE SWITCH IN THE "DAY" POSITION, THE GAUGE ADJUSTABLE ANGLE IRON SUPPORT LEGS SHALL BE FURNISHED AS EF -2, EXHAUST FAN REQUIRED. THE INLET OF THE UNIT SHALL CONTAIN BIRDSCREEN AND A ALUMINUM, WATER TIGHT, REMOVABLE HOUSING WITH GALVANIZED STEEL OR BANK OF WASHABLE, REMOVABLE AIR FILTERS. FILTERS SHALL BE OF ONE— ALUMINUM BIRD SCREEN AND ALUMINUM BLADE, SELF ACTING, SOUND INCH ALUMINUM MESH TYPE, COATED WITH FILTER ADHESIVE COMPOUND AND DAMPENED, BACKDRAFT DAMPER. B.I. CENTRIFUGAL TYPE FAN WHEEL SHALL BE U.L. CLASSIFIED. THE TOTAL FAN PACKAGE SHALL BE STATICALLY AND DYNAMICALLY BALANCED. V —BELT DRIVE WITH FURNISHED WITH A PREWIRED CONTROL CENTER WHICH SHALL INCLUDE, BUT ADJUSTABLE MOTOR SHEAVE. MOTOR AND FAN MOUNTED ON VIBRATION NOT BE LIMITED TO, A MASTER —FUSED DISCONNECT FOR MAIN POWER ISOLATORS. CONNECTION, MAGNETIC MOTOR STARTERS WITH THERMAL OVERLOADS AND SWITCH IS TURNED TO THE SETTING ", EF -1, EF AND MUA -1 SHALL MANUAL RESET, FUSED 24 —VOLT CONTROL TRANSFORMER AND DISTRIBUTION BUILDING WILL REMAIN ON NIGHT SETBACK, 24 HOURS A TERMINAL STRIP FOR CONTROL WIRING CONNECTION. ALL ELECTRICAL CONDENSER SUPPLY COMPONENTS SHALL BE U.L. LISTED, APPROVED OR CLASSIFIED WHERE OPEN. THE THREE —WAY HEATING WATER VALVE APPLICABLE AND WIRED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL THE "AUTO" POSITION PROVIDES AUTOMATIC CODE, WIRING SHALL BE COMPLETE, REQUIRING ONLY ONE —POINT FIELD POINT OF DISCONNECTION CONNECTION FOR POWER SERVICE AND ONE —POINT FIELD CONNECTION FOR N A SEQUENCE TO MAINTAIN SUPPLY AIR TEMPERATURE OF 60' (A DJ.). WHEN THE LOW — VOLTAGE CONTROL HARNESS. MC TO PROVIDE DUCT DETECTOR. TEMPERATURES. IN THE AUTO POSITION, THE PILOT FURNISH MOTORIZED BACKDRAFT DAMPER AS INTEGRAL PART OF SUPPLY MEDIUM PRESSURE NATURAL GAS UNIT. DAMPER UNIT SHALL OPEN UPON ENERGIZATION OF SUPPLY FAN AND SETTING ", EF -1, EF -2, AND MUA -1 SHALL CLOSE UPON SHUT —OFF OF SUPPLY FAN. OPERATION, AS FOLLOWS: DEENERGIZE, AND THE OUTSIDE AIR DAMPER cE QV SHALL CLOSE. °" f (. I i-tAiAL SALjwcE P_fA5)9_-r pp-lbf-' In 6cL6pfq1VcV HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY COOL DOWN. THE SUPPLY FAN IS TO RUN CONTINUOUSLY. �-- -10 gffft OF AS51m A ROOM THERMOSTAT WITH AUTOMATIC CHANGE — THE UNIT CONTROL PANEL SHALL BE TIED INTO THE EXISTING (BAS). THE BUILDING AUTOMATION SYSTEM SEQUENCE OF CONTROL: A. AIR HANDLING UNIT (AHU -1) B. MAKE —UP AIR UNIT (MUA -1), EXHAUST FANS (EF -1 & EF -2) 1. GENERAL 1. GENERAL A. RETURN AIR AND OUTSIDE AIR DAMPERS SHALL BE A. OUTSIDE AIR DAMPER SHALL BE PROVIDED WITH THE ARE NOT NECESSARILY USED. PROVIDED WITH THE FAN SYSTEM EQUIPMENT. FAN SYSTEM EQUIPMENT. B. THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE B. THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER /-\ SUPPLY RETURN AIR DAMPER SHALL OPEN WHENEVER THE SUPPLY THE SUPPLY FAN STOPS UNDER ANY CONDITIONS, ABOVE FINISHED GRADE FAN STOPS UNDER ANY CONDITIONS EXCEPT FROM FIRE INCLUDING FIRE CONTROLS STOPPING THE FAN. BFG CONTROLS. WHEN FIRE CONTROLS STOP THE FAN, ALL MBH PIPE UNION DAMPERS GO TO CLOSED, AND ALL FANS SHALL TURN OFF. C. THE HEATING COIL CONTROL VALVE SHALL BE C. THE HEATING COIL CONTROL VALVE SHALL BE POSITIONED TO FULL FLOW FROM HEAT SOURCE THROUGH CUBIC FEET PER MINUTE POSITIONED TO FULL FLOW FROM HEAT SOURCE THROUGH COIL WHENEVER THE SUPPLY FAN GOES OFF. CLG COIL WHENEVER THE SUPPLY FAN GOES OFF. D. PROVIDE A FLOW SWITCH LOCATED IN THE COIL D. PROVIDE A FLOW SWITCH LOCATED IN THE COIL DISCHARGE PIPING SENSING WATER FLOW FROM THE �� DIFFUSER DISCHARGE PIPING SENSING WATER FLOW FROM THE HEATING COIL THAT SHALL SOUND AN ALARM AND TURN ON CLEAN OUT TO GRADE HEATING COIL THAT SHALL SOUND AN ALARM AND TURN ON A RED WARNING LIGHT AT THE CONTROL PANEL AND STOP DN A RED WARNING LIGHT AT THE CONTROL PANEL AND STOP THE SUPPLY AIR FAN WHEN A NO FLOW CONDITION IS PIPE ANCHOR THE SUPPLY AIR FAN WHEN A NO FLOW CONDITION IS SENSED. PROVIDE AN ALARM SILENCER. LOCK OUT THIS GRILLE SENSED. PROVIDE AN ALARM SILENCER. LOCK OUT THIS ALARM AND THIS FAN INTERLOCK WHEN PUMP IS OFF FROM ENTERING AIR TEMPERATURE ALARM AND THIS FAN INTERLOCK WHEN PUMP IS OFF FROM THE OUTSIDE AIR SENSOR WHICH NORMALLY CONTROLS THE EXH THE OUTSIDE AIR SENSOR WHICH NORMALLY CONTROLS THE OPERATION. A COIL AIR DISCHARGE FREEZE —STAT IS FLEXIBLE CONNECTOR OPERATION. A COIL AIR DISCHARGE FREEZE —STAT IS ALSO TO BE PROVIDED. WHEN A FREEZE CONDITION ALSO TO BE PROVIDED. WHEN A FREEZE CONDITION IS OCCURS, ALL FANS SHALL BE OFF, AND THE HEATING FURNISHED BY OWNER SENSED, ALL FANS SHALL BE OFF, AND THE HEATING WATER VALVE SHALL DIVERT ALL FLOW THRU THE COIL. LAT WATER COIL SHALL DIVERT ALL FLOW THRU THE COIL. 2. CONTROL PANEL SHALL BE PROVIDED AND SHALL ALL OSA DAMPERS SHALL BE CLOSED. INCLUDE: 2. CONTROL PANEL SHALL BE PROVIDED AND SHALL A. OUTSIDE AIR TEMPERATURE SENSOR. INCLUDE: (v+- -I A. OUTSIDE AIR TEMPERATURE SENSOR. B. MANUAL ON /OFF SWITCH LOCATED IN THE KITCHEN. ice}- THERMOMETER C. PILOT LIGHT INDICATING ON /OFF SWITCH POSITION B. A SEVEN DAY CLOCK WITH BACK —UP BATTERY. THERMOSTAT C. "DAY— NIGHT —AUTO" SWITCH (1) OFF SETTING: WHEN THE UNIT IS IN THE "OFF ", TYP. SETTING EF -1, EF -2, AND MUA -1 SHALL BE OFF. THE D. PILOT LIGHTS FOR EACH OF THE FOLLOWING: THREE —WAY HEATING WATER VALVE SHALL DIVERT FLOW TO UNLESS NOTED OTHERWISE --II THE COIL. A SPACE MOUNTED THERMOSTAT SHALL — SMS — 1) DAY OVERRIDE THE MANUAL SWITCH SETTING WHEN THE SPACE VERTICAL CLEANOUT — SMR — TEMPERATURE DROPS BELOW 50'F(ADJ.). WHEN THE 2 NIGHT 3� AUTO SWITCH IS OVERRIDDEN, THE SYSTEM SHALL ENTER THE "ON HEATING WATER SUPPLY SETTING" UNTIL THE SPACE TEMPERATURE IS BROUGHT E. WITH THE SWITCH IN THE "DAY" POSITION, THE UP TO 70'F(ADJ.). AT THIS TIME, THE SYSTEM FLOOR SINK UNIT PROVIDES A NORMAL DAY CYCLE OPERATION AT ALL OVERRIDE SHALL STOP, AND THE SYSTEM SHALL BE UNDER fOi TIMES, 24 HOURS A DAY. THE DAY PILOT LIGHT WILL BE THE CONTROL OF THE MANUAL SWITCH. CHILLED WATER RETURN ON. FIRE /SMOKE DAMPER F. WHEN THE SWITCH IS IN THE "NIGHT" POSITION, (2) ON SETTING: WHEN THE MANUAL "ON FIRE DAMPER THE NIGHT LIGHT WILL BE ON CONTINUOUSLY, AND THE SWITCH IS TURNED TO THE SETTING ", EF -1, EF AND MUA -1 SHALL BUILDING WILL REMAIN ON NIGHT SETBACK, 24 HOURS A ENERGIZE. THE OUTSIDE AIR DAMPER SHALL CONDENSER SUPPLY DAY. OPEN. THE THREE —WAY HEATING WATER VALVE G. THE "AUTO" POSITION PROVIDES AUTOMATIC AND EVAPORATIVE COOLER SHALL MODULATE IN POINT OF DISCONNECTION OPERATION WITH CHANGEOVER FROM NIGHT SETBACK TO DAY N A SEQUENCE TO MAINTAIN SUPPLY AIR TEMPERATURE OF 60' (A DJ.). WHEN THE CU -1 TEMPERATURES. IN THE AUTO POSITION, THE PILOT MANUAL SWITCH IS TURNED TO THE "OFF MEDIUM PRESSURE NATURAL GAS LIGHTS WILL INDICATE WHERE IN THE CYCLE THE UNIT IS SETTING ", EF -1, EF -2, AND MUA -1 SHALL - D - OPERATION, AS FOLLOWS: DEENERGIZE, AND THE OUTSIDE AIR DAMPER 80 (1) DAY CYCLE: THE DAY CYCLE IS TO START ONE HOUR SHALL CLOSE. 160 BEFORE THE BUILDING IS OPEN TO ALLOW FOR WARM —UP OR 3, BUILDING AUTOMATION SYSTEM INTERFACE (BAS) HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY COOL DOWN. THE SUPPLY FAN IS TO RUN CONTINUOUSLY. 0.1 - LPR - A ROOM THERMOSTAT WITH AUTOMATIC CHANGE — THE UNIT CONTROL PANEL SHALL BE TIED INTO THE EXISTING (BAS). THE BUILDING AUTOMATION SYSTEM SHOCK ABSORBER OVER FROM THE HEATING TO COOLING MODES (BAS) SHALL BE H +H AND A PANEL MOUNTED CONTROLLER SHALL ABLE TO OVERRIDE THE AHU DISCHARGE AIR TEMPERATURE FUEL OIL VENT MODULATE THE THREE WAY HEATING WATER COIL SETPOINT. THE BAS SHALL ALSO BE ABLE TO OVERRIDE ROOM - FOF - FUEL OIL FILL TEMPERATURE SET POINT, TIME OVERRIDE, STARTUP, CONTROL VALVE TO MAINTAIN ROOM THERMOSTAT COASTDOWN, TIME SCHEDULES, AND PRIORITY SHUTDOWN SETTING DURING THE HEATING MODE. THE COMMANDS. IF COMMUNICATION WITH THE BAS IS LOST, THE REFRIGERANT SUCTION CONDENSING UNIT CU -1 IS LOCKED OUT IN THE AHU SHALL USE ITS DEFAULT SETPOINT TO OPERATE IN THE - RL - HEATING MODE. UPON A CALL FOR COOLING, OCCUPIED MODE AND AN ALARM WILL BE SENT TO THE BAS THE CONDENSING UNIT CU -1 SHALL CYCLE IT'S INDICATING A COMMUNICATION FAILURE RESULTING IN AN COMPRESSORS TO MAINTAIN ROOM THERMOSTAT OPERATING MODE OVERRIDE SETTING. THE HEATING WATER VALVE SHALL BE SET TO THE BYPASS MODE. (2) NIGHT CYCLE: DURING THE "NIGHT CYCLE" THE SUPPLY AIR FAN SHALL BE OFF. THE OUTSIDE AIR DAMPERS SHALL BE CLOSED AND THE RETURN AIR DAMPER SHALL BE OPEN. THE HEATING COIL CONTROL VALVE SHALL BE POSITIONED FOR FULL FLOW FROM THE HEAT SOURCE THRU THE COIL. A NIGHT THERMOSTAT SHALL CYCLE FAN TO MAINTAIN 657 MINIMUM TEMPERATURE, WITH O.A. DAMPER CLOSED, R.A. DAMPER OPEN. THE CONDENSING UNIT SHALL BE LOCKED OUT DURING THE NIGHT CYCLE. 3. BUILDING AUTOMATION SYSTEM INTERFACE (SAS) THE UNIT CONTROL PANEL SHALL BE TIED INTO THE EXISTING (BAS). THE BUILDING AUTOMATION SYSTEM (BAS) SHALL BE ABLE TO OVERRIDE THE AHU DISCHARGE AIR TEMPERATURE SETPOINT THE BAS SHALL ALSO BE ABLE TO OVERRIDE ROOM MECHANICALLEGEND SYMBOL USE NOTE: ALL SYMBOLS SHOWN ON LEGEND I FINISH MANUFACTURER & * E REMARKS ARE NOT NECESSARILY USED. AFF ABOVE FINISHED FLOOR MODEL NO. V /tA /-\ SUPPLY 15' DEFL. AFG ABOVE FINISHED GRADE PUMP do EQUIPMENT CONNECTOR BFG BELOW FINISHED GRADE MBH PIPE UNION BOP BOTTOM OF PIPE FROM FINISHED FLOOR �Qy� j�¢ DOUBLE CHECK BACKFLOW PREVENTER CFM CUBIC FEET PER MINUTE ® STEAM TRAP CLG CEILING OBD FT -FLOAT do THERMOSTATIC CONN CONNECT �� DIFFUSER TD-THERMODYNAMIC COTG CLEAN OUT TO GRADE TMS IB- INVERTED BUCKET DN DOWN - X PIPE ANCHOR (E) EXISTING GRILLE 15' DEFL. EAT ENTERING AIR TEMPERATURE -CMM- PIPE EXPANSION JOINT EXH EXHAUST -} - FLEXIBLE CONNECTOR EWT ENTERING WATER TEMPERATURE SAFETY RELIEF VALVE FBO FURNISHED BY OWNER AIR VENT LAT LEAVING AIR TEMPERATURE HP LINT LEAVING WATER TEMPERATURE PRESSURE -TEMP. TAP NIC NOT IN CONTRACT (v+- -I PRESSURE GAUGE W/ PIC TAIL & COCK OBD OPPOSED BLADE VOLUME DAMPER ice}- THERMOMETER O.C. ON CENTER ,_, (} THERMOSTAT OSA OUTSIDE AIR ��i� TYP. TYPICAL - - VACUUM BREAKER UNO UNLESS NOTED OTHERWISE --II HORIZONTAL CLEANOUT — SMS — SNOWMELT SUPPLY VERTICAL CLEANOUT — SMR — SNOWMELT RETURN FLOOR DRAIN — HWS — HEATING WATER SUPPLY — HWR — HEATING WATER RETURN ® FLOOR SINK — CHS — CHILLED WATER SUPPLY fOi ROOF DRAIN —CHR— CHILLED WATER RETURN (6)F /S FIRE /SMOKE DAMPER —RMS— RADIANT MANIFOLD SUPPLY ® FIRE DAMPER —RMR— RADIANT MANIFOLD RETURN 1200 - CS - CONDENSER SUPPLY i@1 EXHAUST FAN ON ROOF W / DUCT THRU ROOF. - CR - CONDENSER RETURN 5 POINT OF DISCONNECTION - G - NATURAL GAS CU -1 POINT OF NEW CONNECTION - MG - MEDIUM PRESSURE NATURAL GAS F' FIRE ALARM HORN /STROBE - D - DRAIN PIPE 38 80 - HPS - HIGH PRESSURE STEAM SUPPLY 160 STRAINER W/ BLOW -OFF VALVE - HPR - - LPS - HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY 0.1 - LPR - LOW PRESSURE STEAM RETURN _tJ SHOCK ABSORBER - PC - PUMPED CONDENSATE H +H HOSE BIBS / WALL HYDRANT - FOV - FUEL OIL VENT - FOF - FUEL OIL FILL - CF - GLYCOL FEED FLOW SWITCH - RS - REFRIGERANT SUCTION - RL - REFRIGERANT LIQUID - RD -- REFRIGERANT DISCHARGE SMOKE DETECTOR - - - DOMESTIC COLD WATER - RO - REVERSE OSMOSIS WATER Tc - DOMESTIC HOT WATER 0.80 TEMPERATURE CONTROLLER - -- 140'- DOMESTIC HOT WATER ( TEMP. SHOWN ) 1 979 - - - - - HOT WATER CIRCULATING ® ACCESS PANEL - F - FIRE LINE — SUPPLY DUCT DOWN - PW - PRESSURIZED WASTE 110 - V - PLUMBING VENT PIPE 460 RETURN/EXHAUST DUCT DOWN - CV - CHEMICAL VENT PIPE 2Yri" 12.3 TURNING VANES SHOWN IN 90- ELBOW. - W - WASTE PIPE 2" THROW— 1RANE EVAPORATIVE COOLER /SPRAY WASHER — AIREX SIZE 12 OR EQUAL - OW - GREASE WASTE PIPE SINGLE BLADE DAMPER ( S.B.D. ), MOTORIZED - CW - CHEMICAL WASTE PIPE i i DAMPER, OPPOSED BLADE DAMPER (O.B,D. ) S - SANITARY SEWER PIPE - ST - STORM DRAIN PIPE - ST(OF) - STORM DRAIN OVERFLOW PIPE AIR EXTRACTOR - VAC - VACUUM PIPE DUCT SIZES ARE OUTSIDE SHEET METAL ---CA- COMPRESSED AIR PIPE u 2 DIMENSIONS. 1ST NO. IS SIZE OF SURFACE -MA- MEDICAL AIR PIPE AWAY SHOWN. 2ND NO. IS DUCT DEPTH. 0 --- OXYGEN PIPE SUPPLY REGISTER N - NITROGEN PIPE s� -N20•- NITROUS OXIDE PIPE ----{- VENTURI/FLOW INDICATER �9'L! c�t��� RETURN AIR OR EXHAUST AIR REGISTER, BUTTERFLY VALVE - -pc1- SHUT OFF VALVE (BALL, GATE, BUTTERFLY) �j 9 SUPPLY DIFFUSER; ARROWS INDICATE -- -t�r4- GLOBE VALVE DIRECTION OF THROW. -{�- CHECK VALVE DOOR GRILLE _0-J FLOW CONTROL VALVE SECTION THRU SUPPLY AIR DUCT. -- BALL VALVE SECTION THRU OUTSIDE AIR INTAKE, RETURN AIR OR EXHAUST DUCT. --�} -- PLUG OR BALANCING VALVE �� (A) SECTION CUT LETTER. ---(- CIRCUIT SETTER VALVE � (B) SPIFFY SHOWN ON. - '- PLUG VALVE IN RISER�p GATE OR CLOSE VALVE IN RISER ti: ! PLUMBING RISER -� DRAIN VALVE W/ HOSE END <> HEATING WATER RISER TEMPERATURE CONTROL VALVE n CHILLED WATER RISER -ix7 -- PRESSURE REDUCING VALVE (D FIRE RISER SOLENOID VALVE HVAC RISER GRILLE, REGISTER, DIFFUSER, & LOUVER SCHEDULE SYMBOL USE PATTERN ACCESSORIES FINISH MANUFACTURER & * E REMARKS MARK MODEL NO. V /tA /-\ SUPPLY 15' DEFL. OBD BY ARCH. AIR CONDITIONS — DIFFUSER AIR CONDITIONS MBH TYPE CT-581 WATER CONDITIONS / \ SUPPLY CFM CFM OSA E. P. @ L IT FAN DIA. WHEEL LOUVERED OBD BY ARCH. E A T. — �� DIFFUSER CONEDENSER IN. A MAX. AIR TMS L T. MBH T.L.W.T. GPM PIPE IN. ARE GRILLE 15' DEFL. OBD BY ARCH. 350 RL — `—' & MODEL NO. TEMPERATURE SET POINT, START —UP, OCCUPIED, MORNING WARM — GNU LQUIVALEN 1: KRUEGER, METALLAIRE, HART & COOLEY, ANEMOSTAT UP HEATING, TIME OVERRIDE, STARTUP, COASTDOWN, NIGHT SETBACK, TIME SCHEDULES, AND PRIORITY SHUTDOWN COMMANDS. IF COMMUNICATION WITH THE BAS IS LOST, THE AHU SHALL USE ITS DEFAULT SETPOINT TO OPERATE IN THE OCCUPIED MODE AND AN ALARM WILL BE SENT TO THE BAS INDICATING A COMMUNICATION FAILURE RESULTING IN AN OPERATING MODE OVERRIDE. CONDENSING UNIT SCHEDULE ELECTRICAL EVAPORATOR CONDENSOR MARK AIR HANDLER MANUFACTURER SERVED VOLTAGE /PHASE MCA EAT SENSIBL EAT ('F) & MODEL NO. REMARKS DB 'F WB "F (MBH) DB CU -1 AHU -1 208/3 52.6 78 58 132 82 TRANE 10 TON DUAL COMPRESSOR UNIT TTA120B -4 * CARRIER, YORK EQUIVALENT * ILG, EXHAUST FAN SCHEDULE FAN MOTOR MANUFACTURER & MARK TYPE CFM S.P.@ SL S.P.@ ALT. HP /WATT VOLTAGE] MODEL NO. ACCESSORIES REMARKS IN W.C. IN W.G. PHASE UPBLAST PENN VENTILATION EF -1 ROOF 6300 1.5 1.25 3 HP 208/3 — — EXHAUSTER FX24BH DOWNBLAST PENN VENTILATION EF -2 ROOF 900 0.4 0.37 V4 HP 120/1 — — EXHAUSTER I I I DX08B SREENHECK, COOK, ACME EQUIVALENT AIR HANDLING UNIT SCHEDULE AIR DELIVERY CAPACITY DX COOLING COIL EVAPORATIVE COOLER I HEATING COIL MARK AREA SERVED V /tA FILTER MANUFACTURER* REMARKS SUPPLY FAN AIR CONDITIONS COIL AIR CONDITIONS MBH TYPE AIR CONDITIONS WATER CONDITIONS COIL CFM CFM OSA E. P. @ L FAN DIA. WHEEL CLASS R.P.M. MOTOR E A T. L.A.T. MBH CONEDENSER IN. A MAX. AIR E A.T. L T. MBH T.L.W.T. GPM PIPE IN. ARE MAX. WT MAX. AI E A.T. W B T. L.A.T 'F 'F & MODEL NO. IN W G IN W.C. TYPE HP S FT. 1 .F SIZE S FT. P.D. FT. AHU -1 BAR/LOUNGE 5800 1200 0.80 0.75 15" FC 1 1089 5 82 54 132 CU -1 12.3 0.25 — — — — — 38 80 200 180 160 21 M" 12.4 1.3 0.1 208/3 2" THROW- TRANE AWAY MCCB MUA -1 KITCHEN MAKE —UP 5675 5675 0.80 0.75 15" FC 1 979 5 — — — — — — 82 60 63 110 12" IREC —19 76 460 180 160 50 2Yri" 12.3 3 0.1 208/3 2" THROW— 1RANE EVAPORATIVE COOLER /SPRAY WASHER — AIREX SIZE 12 OR EQUAL FILL AWAY MCCB ,PROVIDE FACTORY INSTALLED DRAIN —DOWN KIT *CARRIER. YORK EQUIVALENT BEAUDIN GANZE Consulting Engineers, Inc. V0/ LB Tobeg() 55L 5300 -7334 Denver: (303)276 -3820 RESORT DESIGN ASSOCIATES EMU 2 " a ffd%dfff 3,ti�`'"a Sheep M1.1 DEMO EXISTING DUCTS AT 90' E AT FLOOR AND FOR RECONNECT 2 PARTIAL FIRST FLOOR DEMOLITION PLAN SCALE: 1 /8" = 1'-0" �..f• j 10 11 12 13 • • ♦ • Jill • , • %J SCALE :1l8" = 1' -0" DEMO ALL EXISTING FANS, DUCTWORK, AND MECHANICAL EQUIPMENT IN THIS AREA, U.N.A. TOILET ( SPA{ � I EXISTING DUCT AND DIFFUSERS TO EXISTING DUCT AND DIFFUSERS TO REMAIN EXISTING DUCTS UNDERGROUND AND--- - CONTINUED UP INTO SHAFT. ___0 DISCONNECT DUCT AS SHOWN. CAP EXISTING TAKE —OFF ON 28x28 DUCT. EXISTING 20 "0 DUCT UP `EXISTING 26 "0 DUCT UP - E6ISMNG 20.0 DUCT UNDER FLOOR XIS nN6 PIPING TO REMAIN �1STING '26 "0 DUCT UNDER FLOOR -EXIST UCT TO REMAIN EXISTING 18"0 RUNOUT UNDER FLOOR EXISTING 18 "0 DUCT STUBBED UP AT CEILING OF FLOOR BELOW 1 SCALE: 1/8 " = 1' -0" 60Ij E_ 0 ■ i 11 I Go EXISTING 16x22 SA DUCT EXISTING 26x22 MUA DUCT EXISTING 2002 SA DUCT PARTIAL SECOND FLOOR DEMOLITION PLAN SCALE: 1/8" = 1'-0" ii — E� EXISTING 28x16 GREASE AND 1 Ox10 EXHAUST RISERS TO REMAIN. got SCALE: 1/8" = 1' -0" NOTES: 1. ALL DUCTWORK, DIFFUSERS, ETC. SHOWN AS LIGHT LINE WEIGHT IS EXISTING TO REMAIN U.N.O. 2. ALL DUCTWORK, DIFFUSERS, ETC. SHOWN AS LIGHT LINE WEIGHT AND IS HATCHED IS TO BE REMOVED. 3. ALL DUCTWORKIN CHASES SHOWN AS DEMOED MAY BE ABANDONED IF NECESSARY. IF DUCTS ARE ABANDONED, CAP AS REQUIRED. RESORT DESIGN ASSOCIATES ARCHITECTURE, PLANNING, INTERIOR DESIGN San Francisco Office 388 Market St., Suite *380 Stun Francisco, CA 94111 Tel: 415.392.4433 I= 415.392.4454 Boulder Office 1434 Spruce Street, Suite 110 &wider, CO 80302 Tel: 303.4451.4433 Fax 303.449.3366 McCall Office 1002 First Street McCall, ID 83638 Tel: 208.634.4540 Fax: 208.634,5498 111,11111, . .. r Revisions: ap oubmi"Ton A49.15/02 Drawing Title: MECHANICAL DEMOLITION PLAN& I to a z ca � U X W I ENTRY 334 I s i i I I i iRANSF4Rt;?F2r v I ITMTflT ROUTE NEW DlJC-T. WEOFF BETWEEN NEW ROOF JOISTS. RUN 32x10 SA DUG BELOW NEW ROOF T USSES AS HIGH AS POSSI%E ROUTE SA DUCT BETWEEN ROOF TRUSSES AND SLOPE WITH ROOF. r\ 2 PARTIAL FIRST FLOOR MECHANICAL PLAN "v, _4D RA GRILLES LOCATED AT TOP OF 32x10 RA SHAFT (TYP. 2) CONNECT 34x12 RA DUCT TO EXISTING 34x12 DN. E= I JI EXISTING 28x28 DUCT TO REMAIN ia( 18x18 SA OF EXISTING DUCT AND— DIFFUSERS TO REMAIN *' m IASSOCIATESI (1 18x18 SA DUCT DN. TEE DUCT AT TOP AND I I ( SPLIT TO DUCT SIZES SHOWN. r NEW 18x12 DUCT ROUTED INTERIOR DESIGN sl IN JOIST SPACE. SEE ARCH — DRAWINGS FOR FIRE RATINGS 3818 Market St, Suite 18380 _ El AND DETAILS. DIFFUSERS OUT Sari Francisco, CA 94111 OF BOTTOM OF DUCT. Tel: 415.392.4433 l Fax: 415.392.4454 j i ' " Boulder Office 1434 Spruce Stree4 Sum 110 t D V_ $ .» I \� de- „ Fa)a 303.449.3366 CONNECT NEW 18x12 DUCT TO EXISTING McCall Office 36x10 SA DN. 1002 First Street EXISTING 36x1O SA DN TO REMAIN. McCall, ID 83638 EXISTING 34x12 RA DN TO REMAIN. "v, _4D RA GRILLES LOCATED AT TOP OF 32x10 RA SHAFT (TYP. 2) CONNECT 34x12 RA DUCT TO EXISTING 34x12 DN. E= I JI EXISTING 28x28 DUCT TO REMAIN ia( 18x18 SA OF EXISTING DUCT AND— DIFFUSERS TO REMAIN *' m IASSOCIATESI 32x10 SA UP ,, _---! EXISTING 2Yz" HWS /HWR DN TO AIR HANDLING UNIT. CONNECT TO HEATING COIL AS REQUIRED. REFER TO SHEET M3.1 DIAGRAM (g) FOR COIL CONNECTION DETAIL, TYP. EFRIGERANT LINES TO CU -1. SEE DRAWING 2 THIS SHEET FOR CONT. EFRIGERANT LINES DN TO UNIT .,...---- --14 "0 DUCT DN. TRANSITION TO EXISTING 20 "0 UNDERGROUND DUCTWORK. __----- -RA PLENUM BOX SAME SIZE AS UNIT INLET. UNIT MIXING BOX TO HAVE MOTORIZED RA AND OSA DAMPERS 26 "0 DUCT DN TO EXISTING 26 "0 UNDERGROUND C, C UCTWORK. EXISTING 2WHWS /HWR AND 1 "CW DN UNDER DUCT AND DN TO MAKE -UP AIR UNIT. CONNECT TO HEATING COIL AND EVAPORATIVE r COOLER PUMP SUPPLIED BY MANUFACTURER. OTORIZED OSA DAMPER CONNECT DUCTS TO EXISTING OSA LOUVER rA EXISTING 20 "SA DUCT UNDERGROUND TRANSITIONED UP TO 16x22 IN VERTICAL. EXISTING 26 "0 RA DUCT UP. TRANSITIONED TO TO 18x22 IN VERTICAL. SCALE: 1/8" = 1' -0" ti Tru-.'Cu BEAUDIN GANZE Consulting Engineers, Inc. Vol: ((970) 849 -6108 Luke 1a0� {530) 55D —i334 O nMer (3Q 2_78 -3820 2002 RDA 0 mt- Revisions: BP °vubmlealon Aug. 15/02 Drawing Tide: MECHANICAL PLANE ARCHITECTURE, PLANNING, INTERIOR DESIGN San Francisco Office 3818 Market St, Suite 18380 Sari Francisco, CA 94111 Tel: 415.392.4433 Fax: 415.392.4454 j i ' " Boulder Office 1434 Spruce Stree4 Sum 110 t D V_ $ .» Boulder, CO 80302 Tel; 303.449.4433 de- „ Fa)a 303.449.3366 McCall Office 1002 First Street McCall, ID 83638 Tel: 208.634.4540 Fax: 208.634.5498 32x10 SA UP ,, _---! EXISTING 2Yz" HWS /HWR DN TO AIR HANDLING UNIT. CONNECT TO HEATING COIL AS REQUIRED. REFER TO SHEET M3.1 DIAGRAM (g) FOR COIL CONNECTION DETAIL, TYP. EFRIGERANT LINES TO CU -1. SEE DRAWING 2 THIS SHEET FOR CONT. EFRIGERANT LINES DN TO UNIT .,...---- --14 "0 DUCT DN. TRANSITION TO EXISTING 20 "0 UNDERGROUND DUCTWORK. __----- -RA PLENUM BOX SAME SIZE AS UNIT INLET. UNIT MIXING BOX TO HAVE MOTORIZED RA AND OSA DAMPERS 26 "0 DUCT DN TO EXISTING 26 "0 UNDERGROUND C, C UCTWORK. EXISTING 2WHWS /HWR AND 1 "CW DN UNDER DUCT AND DN TO MAKE -UP AIR UNIT. CONNECT TO HEATING COIL AND EVAPORATIVE r COOLER PUMP SUPPLIED BY MANUFACTURER. OTORIZED OSA DAMPER CONNECT DUCTS TO EXISTING OSA LOUVER rA EXISTING 20 "SA DUCT UNDERGROUND TRANSITIONED UP TO 16x22 IN VERTICAL. EXISTING 26 "0 RA DUCT UP. TRANSITIONED TO TO 18x22 IN VERTICAL. SCALE: 1/8" = 1' -0" ti Tru-.'Cu BEAUDIN GANZE Consulting Engineers, Inc. Vol: ((970) 849 -6108 Luke 1a0� {530) 55D —i334 O nMer (3Q 2_78 -3820 2002 RDA 0 mt- Revisions: BP °vubmlealon Aug. 15/02 Drawing Tide: MECHANICAL PLANE NOTE: COORDINATE ROOF PENETRATIONS WITH ROOFING MANUFACTURER. ANCHOR FAN TO DUCT TRANSITION FROM CEILING GRILLE SIZE TO DAMPER SIZE. RUN FLASHING UP UNDER FAN BASE. FLASHING AND COUNTER — FLASHING. EXHAUST FAN. BIRD SCREEN. PRE —FAQ CURB WITH 1,� INSULATION. ROOFING, ! It j NO SCALE MINIMUM VELOCITY = 1500 FPM MAXIMUM VELOCITY = 2500 FPM DUCTWORK SHALL BE 16 GA. EXHAUST TERMINATION SHALL BE 10' MINIMUM FROM GALVANIZED Wf WELDED ADJACENT BUILDING, PROPERTY LINE, OR AIR WALL JOINTS. INTAKES AND 10' ABOVE ADJOINING GRADE LEVEL. VENTILATED -- i CLEANOUT DOORS IN DUCTS SHAFT. r SHALL BE SLIDING OR HINGED AND BE TIGHT FITTING. PROVIDE 18" BETWEEN DUCTS AND COMBUSTIBLES OR 3" MINIMUM SHAFT SEPARATION AS PER CODE— INDIVIDUAL FIRE FROM PROTECTED COMBUSTIBLES. RESISTIVE SHAFT IS REQUIRED EXCLUSIVELY FOR EACH EXHAUST SYSTEM. THIS SHAFT SHALL BE SPACED I 1 AWAY FROM THE DUCT A MINIMUM OF 3" AND A MAXIMUM OF 12 ". CEILING FIRE RESISTIVE SHAFT ACCESS OPENING EQUIPPED WITH TIGHT FITTING SLIDING OR HINGED DOORS HAVING A FIRE RESISTIVE RATING EQUAL TO SHAFT ENCLOSURE. GREASE HOOD EXHAUST DUCT DIAGRAM NO SCALE COIL. ------ AIR VENT. NOTE: PIPE COIL FOR COUNTERFLOW. ZONE HEATING COIL ASS 'Y DIAGRAM NO SCALE (D ) 1C7 11 TRANSITION EXHAUST DUCTS TO ---., FAN OPENINGS. FANS MUST HAVE AN ACCESSIBLE 30" WALKWAY ON ONE SIDE OF EACH OF THE EXHAUST FANS. FAN OUTLETS MUST BE ATLEAST 2' ABOVE ADJACENT ROOF SURFACE WITHIN= 10', TYP. REFER TO DIAGRAM THIS SHEET. REFER TO DIAGRAM (6) -- ---' THIS SHEET. 4 PARTIAL ROOF FLOOR PLAN SCALE: 1/8" — _ 1'-0" 0 0 —8 XT CONNECT TO EXISTING DUCTS IN FLOOR. OFI CONDENSATE EXHAUST AND SHAFT TO AVOID FAN C� 8 STAIRS 0\o>' KITCHEN i ago f war Oi IIVINC ROOM 11 PARTIAL SECOND FLOOR PLAN SCALE: 1/8" — _ 1'-0" 2 PARTIAL THIRD FLOOR PLAN — _Q) E1 _0 0 (10 G 12 1 i 3 PARTIAL FOURTH FLOOR PLAN _ SCALE: 1/8" — 1'-0" BEAUDIN GANZE / Con�sWting Engineers, Inc. i i>�a�•(' °ago - Dertver {303}27s -3820 2002 RDA ASSOCIATES ARCHITECTURE, PLANNING, INTERIOR DESIGN San Francisco Office 388 Market St,, Suite #380 San Francisco, CA 94111 Tel: 415392.4433 Fax 415392.4454 Boulder Office 1434 Sprum Stree 4 Suite 110 Boulder, CO 80302 Tel: 303.449.4433 Fan 303.4493366 McCall Office 1002 First Street McCall, ID 83638 Tel: 208.634.4540 Fax: 208.634.5498 ii p P_ PMPd'- 1 Revisions: BP SubmiBaton A "q. 1W02 EXISTING 120V CIRCUIT EXISTING WIRING TO BUILDING FIRE ALARM SYSTEM EXISTING FIRE ---"�. EXTENGUISHING SYSTEM CONTROL PANEL CONNECT 120V GAS---, VALVE(S) AND RESET RELAY. COORDINATE WITH FIRE EXTINGUISHING SYSTEM CONTRACTOR. 1. DRAWINGS MAY NOT REFLECT EXISTING CONDITIONS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF WORK. 2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK. 3. EXAMINATION OF BIDDING DOCUMENTS. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES. OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 4. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS. 5. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK. 6. REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL. AND OTHER DRAWINGS PRIOR TO BID. 7. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT. 8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF COLORADO, AND NATIONAL CODES AND ORDINANCES. 9. PROVIDE PERMITS AND INSPECTIONS REQUIRED. 10. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. 11. PROVIDE RECORD DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC. 12. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE. 13. PROVIDE ENGRAVED NAMEPLATES ON SWITCHBOARDS, PANELBOARDS, DISCONNECT SWITCHES, MOTOR CONTROL CENTERS, TRANSFORMERS, ETC., INDICATING EQUIPMENT DESIGNATION (OR DESIGNATION OF EQUIPMENT SERVED), AND VOLTAGE. 14. PANEL DIRECTORIES SHALL BE REMOVABLE. SUBMIT PROPOSED SCHEDULE OF DIRECTORIES TO OWNER FOR APPROVAL. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS. 15. PROVIDE DYMO -TAPE TAG INSIDE COVER OF EACH FUSIBLE SWITCH, INDICATING SIZE AND TYPE OF FUSES PROVIDED. 16. PRESENT SHOP DRAWING SUBMITTAL DATA AT ONE TIME, BOUND IN THREE -RING BINDERS, INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO WIRING DEVICES, SAFETY SWITCHES, NEW CIRCUITING TO TO 120V SHUNT TRIP BREAKERS. SEE PANEL SCHEDULE KITCHEN FIRE EXTINGUISHING SYSTEM CONTROL DIAGRAM NO SCALE NOTE: OPERATION OF EXTINGUISHING SYSTEM SHALL BE: 1. CLOSE GAS VALVES SERVING FUEL TO ALL GAS FIRED EQUIPMENT LOCATED UNDER COOKING EXHAUST HOODS. 2. TRIP ALL CIRCUIT BREAKERS SERVING POWER TO ALL ELECTRIC COOKING EQUIPMENT LOCATED UNDER COOKING EXHAUST HOODS. 3. STOP EXHUAST AND MAKE -UP AIR FANS WITH SHUNT TRIP. ELECTRICAL SPECIFICATIONS: FUSES, MOTOR STARTERS, CONDUIT, AND CONDUIT FITTINGS. 17. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND /OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 18. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. PROVIDE LABOR AND MATERIALS AS REQUIRED TO MAINTAIN AND /OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS. 19. FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT ARE REMAINING TO BE RECONNECTED TO NEW OR EXISTING SWITCHBOARDS/ PANELBOARDS. PROVIDE SWITCHES, RECEPTACLES, CONDUIT, WIRE, ETC. AS REQUIRED TO RESTORE CONTINUITY OF CIRCUIT(S). 20. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED CONDUIT, WIRE, CABLE, J- BOXES, RECEPTACLES, SWITCHES, LIGHTS, FIRE ALARM DEVICES, ETC. COMPLETE WITH ASSOCIATED CIRCUITING TO SOURCE. WHERE IT IS NOT FEASIBLE TO REMOVE THE ABOVE, OUTLET SHALL BE ABANDONED, WIRE REMOVED, AND BLANK COVER PLATES PROVIDED. 21. EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOR EXISTING BUILDINGS ARE TO BE NOTED "FOR GUIDANCE ONLY". THE ELECTRICAL CONTRACTOR TO FIELD CHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND TO INCLUDE IN HIS BID AN ALLOWANCE FOR REMOVAL AND /OR RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHER WORK AS REQUIRED. 22. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL. 23. IMMEDIATELY AFTER AWARD OF CONTRACT, VERIFY AVAILABLE PHYSICAL SPACE AND AMPACITY OF EXISTING PANELBOARDS. SWITCHBOARDS, DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC., AND PROVIDE WRITTEN DOCUMENTATION OF FINDINGS TO THE ARCHITECT /ENGINEER. DOCUMENTATION SHALL INCLUDE A MINIMUM 24- HOUR RECORDING AMPERE READING ON ALL EXISTING SWITCHGEAR BEING UTILIZED FOR THIS PROJECT. 24. REVIEW ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND PROVIDE LIGHTS, SWITCHES, RECEPTACLES, TELEPHONE OUTLETS, EQUIPMENT CONNECTIONS, ETC. AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS, EVEN IF SUCH AREAS ARE NOT SHOWN ON ELECTRICAL DRAWINGS. LAYOUTS, FIXTURE TYPES, QUANTITIES, AND SPACINGS SHALL BE IN ACCORDANCE WITH SIMILAR AREAS ON THIS PROJECT. CONTRACTOR SHALL INCLUDE COSTS FOR THE ABOVE IN HIS BID. IN ADDITION, CONTRACTOR SHALL PROVIDE LAYOUT DRAWINGS FOR WORK IN SUCH AREAS AND SUBMIT FOR APPROVAL PRIOR TO ROUGH -IN. 25. EXISTING LIGHT FIXTURES, SWITCHGEAR, ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BE RETURNED TO THE OWNER, EXCEPT FOR THOSE ITEMS BEING RELOCATED. 26. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT. 27. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH -IN. 28. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED. 29. ELECTRICAL CONTRACTOR SHALL PROVIDE CONTROLS, INTERLOCKS, ACCESSORIES, ETC. IN MOTOR CONTROL STARTERS AS REQUIRED BY THE TEMPERATURE CONTROL CONTRACTOR. STARTERS SHALL CONTAIN 120V CONTROL TRANSFORMER, PILOT LIGHT, AND PUSHBUTTONS OR SELECTOR SWITCH AS REQUIRED, IN ADDITION TO OTHER ITEMS (AUXILIARY CONTACTS, DOOR SWITCHES, RELAYS, ETC.) REQUIRED. SUBMIT ELEMENTARY CONTROL DIAGRAMS. 30. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT /ENGINEER'S ATTENTION PRIOR TO INSTALLATION. 31. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO OWNER. 32. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERAL USE. FOR HID FIXTURES AND WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREE CELSIUS AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS. 600 VOLT ALUMINUM WIRE AND CABLE IN SIZES 1/0 AND LARGER MAY BE SUBSTITUTED FOR COPPER ON SERVICES AND FEEDERS IF AMPACITY IS EQUAL TO OR GREATER THAN COPPER, AND VOLTAGE DROP IS EQUAL TO OR LESS THAN COPPER AND SHALL BE TERMINATED AT SWITCHES, LUGS, CIRCUIT BREAKERS, ETC., WITH MAC - ADAPT SERIES "MPT" MACHINE COMPRESSION ADAPTERS OR EQUAL. 33. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION. 34. CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. 35. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY. 36. WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75 DEGREE CELSIUS. 37. PULLBOXES, CABINETS, ETC. MOUNTED ON THE EXTERIOR AT GRADE LEVEL, SHALL BE WEATHERPROOF TYPE WITH HINGED LOCKABLE COVERS SECURED WITH TAMPERPROOF SCREWS. 38. SEE DIVISION 15 DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO, AND CONNECT EQUIPMENT AS REQUIRED. 39. DISCONNECT SWITCHES AND MOTOR CONTROL CENTERS SHALL MATCH EXISTING. 40. DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE. FUSIBLE SWITCHES SHALL ACCEPT CLASS 'R' FUSES ONLY, AND REJECT ALL OTHERS. 41. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE AND FUSES SHALL BE BUSSMANN. 42. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS. RACEWAYS IN SLAB -ON -GRADE OR BELOW GRADE SHALL BE SCHEDULE 40 PVC. TRANSITIONS FROM BELOW TO ABOVE GRADE SHALL BE WITH RIGID STEEL ELBOWS WITH P.V.C. JACKET OR APPROVED EQUAL PROTECTION. EMT FITTINGS SHALL BE MALLEABLE IRON OR STEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE. 43. NON- METALLIC AND FLEXIBLE METAL CONDUITS SHALL HAVE A CODE - SIZED COPPER GROUNDING CONDUCTOR. INCREASE CONDUIT SIZE AS REQUIRED. 44. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT SHALL BE WITH SEAL TITE FLEX AND APPROVED FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT. 45. FIRE ALARM SYSTEM. PROVIDE DEVICES, CONDUIT, WIRES, AND CABLE AS DIRECTED BY EQUIPMENT MANUFACTURER TO EXTEND EXISTING FIRE ALARM SYSTEM TO REMODELED AREAS. THE CONTRACTOR SHALL EXTEND WARRANTY FOR ALL PROGRAMMABLE CONTROLLERS UP TO MARCH 31, 2000 AND PAY FOR ALL DAMAGES CAUSED BY NON- COMPATIBLE CONTROLLERS. MATERIALS, EQUIPMENT, AND WORKMANSHIP SHALL MEET PREVAILING CODES. THE SYSTEM SHALL BE COMPLETE AND OPERABLE IN EVERY RESPECT. SUBMIT SINGLE LINE OF SYSTEM WITH SHOP DRAWINGS. THIS SINGLE LINE DIAGRAM SHALL SHOW DEVICES, CONDUIT, WIRE, AND CABLE SIZES, EQUIPMENT TO BE USED, AND SHALL BE STAMPED AND SIGNED BY LOCAL FIRE DEPARTMENT. SYSTEM CALIBRATION AND TESTING SHALL BE BY FACTORY CERTIFIED TECHNICIAN. PANEL W 08 120 VOLT P ' ' 00 AMPERE MAIN LO 00 AMPERE i LOCATION MECHANICAL ROOM 209 MOUNTING: SURFACE a 000 I,-W 11809 EOA15 13745 CIRCUIT 13940 CIRCUIT BUS CIRCUIT CIRCUIT I 25749 LOAD 25381 If I- Li-1 450 0 0 TYPE LOAD DESCRIPTION BREAKER EXHAUST FAN INNSTANLGL FACES INDICATED 26449 BREAKER TYPE LOAD DESCRIPTION 220 226 212 m D 0:2 LINE A LINE B LINE C L /R/M SPECIAL OUTLET AS NOTED POLE TRIP A B C TRIP POLE L /R/M 111 LINE A LINE 8 LINE C 2 JUNCTION BOX IN FLOOR. CEILING. OR IN WALL. ® TELEPHONE OUTLET IN WALL OR IN FLOOR ® D COMPUTER OUTLET IN FLOOR OR WALL v COMBINATION DATA /TELEPHONE OUTLET 3 #4 & #1OGND, 1 "C CONDUIT RUN CONCEALED IN WALL OR ABOVE CE)UNG I CIRCUIT HOMERUN, #12 THWN, QTY AS REQ'D, W/ GROUND. 1/2 "C - - -_ CONDUIT RUN BELOW FLOOR OR GRADE 1/4 HP CONDUIT RUN EXPOSED �G�GrGyt EXISTING CONDUIT TO BE REMOVED 2 #12 & #12GND, 314 "C 1/2 " -#12 THWN, W /GROUND QTY AS REQ'D W /GROUND u Z CONDUIT UP --------- . CONDUIT DOWN LMZF =Z6Z S SEALOFF -�3 CONDUIT STUB -OUT - CAP & MARK S UGHT SWITCH AT 48" UNLESS NOTED a,UEI%m1pTS: 3 = 3-WAY SWITCH LM A S K = KEY - OPERATED SWITCH T = THERMAL OVERLOAD SWITCH Z CJ 1 J = SWITCH IN DOOR JAMB NOV = VASRIABLE SPEED SWITCH SHUNT TRIP a - LOWER CASE LETTER AT FIXTURES AND + SWITCHING CONTROL. 20 DIMMER SWITCH E SHAW OFFICE 1200 MAGNETIC CONTACTOR E]' 2 3 NON FUSED DISCONNECT SWITCH - 30 AMP UNLESS NOTED 7450 COMBINATION DISCONNECT AND STARTER M ELEVATOR 3 SWITCHBOARD, MOTOR CONTROL CENTER + TRANSFORMER 2 E - SPECIAL CABINET OR EQUIP. AS NOTED 1200 PUSHBUTTON CONTROL STATION 4 5 ® TIME SWITCH 7450 M - DIVISION 15 EQUIPMENT ® CIRCUIT BREAKER + 20 AUTOMATIC TRANSFER SWITCH E SHAW OFFICE a EQUIPMENT 1200 6 7 7450 -�ti- CIRCUIT BREAKER M - 100 + METER ® SURGE SUPPRESSION DEVICE 2 E 1200 GROUND FAULT PROTECTION 8 9 583 NOTIE. LIGHT UNEWJGHT INDICATES EXISTING. INDICATES DEMOUTION. M SNOWMELT PUMP 2 + 20 1 E FIRE DAMPERS (NEW) 1200 10 11 583 M - 20 F + 20 1 M EF -2 NEW 696 12 13 2102 M AHU -1 NEW 3 + 20 SPARE 14 15 2102 M - + 2 - 16 17 2102 M Z 35 + SHUNT TRIP (NEW) 18 19 1000 L ELEVATOR CAB LIGHTS 1 20 + 20 M EF -1 (NEW) 1321 20 21 1000 E ELEVATOR PIT 1 20 + M - 1321 22 23 1000 E ELEVATOR CONTROLS 1 20 + 3 M - 1321 24 25 300 E 11ME CLOCK 1 20 + 20 1 L LOWER TEMP 1800 26 27 600 M UNIT HEATER 1 20 + 20 1 L LOWER TEMP 1800 28 29 696 M EVAP PUMP (NEW) 1 20 + SHUNT TRIP NEW 30 31 SPARE 2 + 35 M MUA -1 NEW 2102 32 33 30 + M - 2102 34 35 957 M TEMP AIR HANDLER 2 + 3 M - 2102 36 37 957 M__ 30 + 60 M CU -1 NEW 6317 38 39 957 M TEMP AIR HANDL!�±�30 + M - 6317 40 41 957 M - 1 1+ 3 1 M - 6317 42 ELECTRICAL LEGEND AQ 11809 12692 13745 SUB TOTALS 13940 13940 1636 ®0 CIRCUIT TYPE L =LIGHTING, R= RECEPTACLE, M= MOTOR, LM= LARGEST MOTOR DESCRIPTION: E= EQUIPMENT, A= APPLIANCE, S= SUBFEED PANEL LINE TOTALS NEC ADDER FEED THRU LOAD TOTAL VA /PH LINE AMPS TOTAL KVA LOAD FEEDER AMPS 25749 26632 25381 O 700 450 0 0 NOTES: ALL CIRCUITS ARE EXISTING UNLESS NOTED (NEW). NEW BREAKERS SHALL MATCH EXISTING AIC RATING, MANUFACTURER, AND TYPE. NEW BREAKERS FOR MUA -1 AND EF -1 SHALL HAVE SHUNT TRIP AS SHOWN. ALL BREAKERS ARE EXISTING EXCEPT NEW BREAKERS FOR AHU -1, MUA -1, AND EF -1. AS BYTSHADING EXHAUST FAN INNSTANLGL FACES INDICATED 26449 27082 25381 DUPLEX RECEPTACLE AT 18" UNLESS NOTED 220 226 212 DOUBLE DUPLEX RECEPT. AT 18" UNLESS NOTED 78.9 219.0 ELECTRICAL LEGEND AQ INCAN. OR HID FIXTURE W/ FIXTURE DESIGNATION Oi WALL MOUNTED LIGHT FIXTURE W/ FIXTURE DESIGNATION A® 2.4 FLUORESCENT LIGHT FIXTURE W/ FIXTURE DESIGNATION A 10 FLUORESCENT LIGHT FIXTURE W/ FIXTURE DESIGNATION ®0 FIXTURE ON NIGHT LIGHT OR EMER. CIRCUIT REMARKS FLUORESCENT STRIP FIXTURE EXHAUST FAN TRACK LIGHT AS NOTED OR SCHEDULED O DIRECTIONAL ACCENT OR WALL-WASH FIXTURE 0.o{0 POLE -MTD. FIXTURE 0 POST (BOLLARD) FIXTURE AS BYTSHADING EXHAUST FAN INNSTANLGL FACES INDICATED 4,-p EMERGENCY BATTERY LIGHTS 0. DUPLEX RECEPTACLE AT 18" UNLESS NOTED CO: DUPLEX RECEPTACLE ABOVE COUNTER 0- DOUBLE DUPLEX RECEPT. AT 18" UNLESS NOTED 0 FLUSH FLOOR DUPLEX RECEPT. e FLUSH FLOOR DUPLEX RECEPT. HALF - SWITCHED ® SPECIAL OUTLET AS NOTED 3 #10 & #1OGND, 3/4 "C CFI DUPLEX RECEPTACLE AT 42" UNLESS NOTED 2 DUPLEX RECEPT: HALF - SWITCHED AT 18" UNLESS NOTED MAKE -UP AIR UNIT IG RECEPTACLE 0 TELE -POWER POLE 111 CLOCK OUTLET �orra MULTI - OUTLET PLUG STRIP 2 JUNCTION BOX IN FLOOR. CEILING. OR IN WALL. ® TELEPHONE OUTLET IN WALL OR IN FLOOR ® D COMPUTER OUTLET IN FLOOR OR WALL v COMBINATION DATA /TELEPHONE OUTLET 3 #4 & #1OGND, 1 "C CONDUIT RUN CONCEALED IN WALL OR ABOVE CE)UNG CIRCUIT HOMERUN, #12 THWN, QTY AS REQ'D, W/ GROUND. 1/2 "C - - -_ CONDUIT RUN BELOW FLOOR OR GRADE 1/4 HP CONDUIT RUN EXPOSED �G�GrGyt EXISTING CONDUIT TO BE REMOVED 2 #12 & #12GND, 314 "C 1/2 " -#12 THWN, W /GROUND QTY AS REQ'D W /GROUND -o CONDUIT UP --------- . CONDUIT DOWN SEALOFF -�3 CONDUIT STUB -OUT - CAP & MARK S UGHT SWITCH AT 48" UNLESS NOTED a,UEI%m1pTS: 3 = 3-WAY SWITCH 4 = 4-WAY SWITCH K = KEY - OPERATED SWITCH T = THERMAL OVERLOAD SWITCH P = SWITCH WITH PILOT UGHT J = SWITCH IN DOOR JAMB NOV = VASRIABLE SPEED SWITCH a - LOWER CASE LETTER AT FIXTURES AND SWITCHES (a, h. ETC.) INDICATES SWITCHING CONTROL. DIMMER SWITCH ® MAGNETIC MOTOR STARTER © MAGNETIC CONTACTOR E]' FUSED DISCONNECT SWITCH - 30 AMP UNLESS NOTED Upi NON FUSED DISCONNECT SWITCH - 30 AMP UNLESS NOTED COMBINATION DISCONNECT AND STARTER PANELBOARD OR LOAD CENTER ® SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION BOARD TRANSFORMER GROUND 0 SPECIAL CABINET OR EQUIP. AS NOTED I] PUSHBUTTON CONTROL STATION PHOTOELECTRIC CELL ® TIME SWITCH (T� THERMOSTAT AT 60" UNLESS NOTED 8 DIVISION 15 EQUIPMENT ® CIRCUIT BREAKER MOTOR OUTLET FA-Ts-1 AUTOMATIC TRANSFER SWITCH ® PULL BOX a EQUIPMENT SINME LINE DIAGRAM SYMBOLS DISCONNECT SWITCH -{Cg- FUSES -�ti- CIRCUIT BREAKER CURRENT TRANSFORMER POTENTIAL TRANSFORMER © METER ® SURGE SUPPRESSION DEVICE Q COLD WATER GROUND BUILDING STEEL. GROUND GROUND FAULT PROTECTION SHUNT TRIP KIRK KEY SWITCH NOTIE. LIGHT UNEWJGHT INDICATES EXISTING. INDICATES DEMOUTION. NOTE: ALL SYMBOLS SHOWN ON LEGEND ARE NOT NECESSARILY USED. ABBREMATIONS AFC - ABOVE FINISHED CEILING AFF - ABOVE FINISHED FLOOR AFG - ABOVE FINISHED GRADE AL - ALUMINUM BFG - BELOW FINISHED GRADE C - CONDUIT ONLY CKT - CIRCUIT CT - CURRENT TRANSFORMER EM - EMERGENCY EWC - ELECTRIC WATER COOLER (E) - EXISTING FBO - FURNISHED BY OWNER F/S - FIRE /SMOKE DAMPER GRD - GROUND Gn - GROUND FAULT INTERRUPTER IAW - IN ACCORDANCE WITH IG - ISOLATED GROUND NIC - NOT IN CONTRACT NIES - NOT IN ELECTRICAL SECTION NL - NIGHT UGHT NTS - NOT TO SCALE STO - THERMAL OVERLOAD SWITCH TT - TELEPHONE TERMINAL TVSS- TRANSIENT VOLTAGE SURGE SUPPRESSOR UG - UNDERGROUND UNO - UNLESS NOTED OTHERWISE WP - WEATHER PROOF TX - TRANSFORMER XP - EXPLOSION PROOF +18 "- MOUNTING HEIGHT TO CENTERLINE OF DEVICE AFF OR AFG EIRE ALARM SYSTEM ® FIRE ALARM CONTROL PANEL ® FIRE ALARM ANNUNCIATOR PANEL ® MANUAL PULL STATION GENERAL ALARM HORN I1 GENERAL ALARM COMBINATION HORN /STROBE US FIRE ALARM SPEAKER (S q OOMBINA71ON FIRE ALARM SPEAKER /STROBE �q FIRE ALARM STROBE C� j' FIRE ALARM CHIME ® THERMAL HEAT DETECTOR ® SMOKE AONIZATION DETECTOR ® SMOKE/HEAT DETECTOR ® DUCT DETECTOR FFFFI SPRINKLER SYSTEM FLOW SWITCH FF-T I SPRINKLER SYSTEM TAMPER SWITCH RTS REMOTE TEST SWITCH FjFIREMANS PHONE INDICATOR UGHT MECHANICAL EQUIPMENT SCHEDULE MARK DESCRIPTION VOLTAGE /PHASE HP /WATTS FLA MCA DISCONNECT FEEDER CIRCUIT REMARKS EF -1 EXHAUST FAN 208/3 3 HP 11.0 - 30A 3P 3 #12 & #12GND, 3/4 "C W- 20,22,24 EF -2 EXHAUST FAN 120 /1 1/4 HP 5.8 - 30A 1P 2 #12 & #12GND, 3/4 "C W -12 AHU -1 AIR HANDLING UNIT 208/3 5 HP 17.5 - 30A 3P 3 #10 & #1OGND, 3/4 "C W- 13,15,17 2 MUA -1 MAKE -UP AIR UNIT 208/3 5 HP 17.5 - 30A 3P 3 #10 & #10GND, 3/4 "C W- 32,34,36 2 CU -1 CONDENSING UNIT 208/3 - - 52.6 60A 3P 3 #4 & #1OGND, 1 "C W- 38,40.42 EP -1 EVAPORATIVE COOLER PUMP 120/1 1/4 HP 5.8 - 30A 1P 2 #12 & #12GND, 314 "C W -29 NOTES: 1. FIELD COORDINATE AND PROVIDE CONTROL WIRING. 2. MAKE CONNECTION TO DUCT DETECTOR. DUCT DETECTOR TO BE SUPPLIED BY MECHANICAL CONTRATOR AND WIRED BY ELECTRICAL CONTRACTOR. PROVIDE REMOTE INDICATOR LIGHT IN LOCATION APPROVED BY LOCAL AHJ. BEAUDIN GAME Consulting Engineers, Inc. a () 65LLa t, I 50 0 -7334 Denver: (303)278 -3820 2002 RDA RESORT DESIGN ASSOCIATES Sari Francisco Office 388 Market St., Suite *380 San Fmndsco, CA 94111 Tel: 415.392.4433 Fax 415.392.4454 Boulder ice 1434 5pnwe &ree4 Suite 110 Boulder, CO 80302 Tel: 303.449.4433 Fwa 303.449.3366 i .l. O 11R 1 002 First Street McCall, ID 83638 Tel: 208.634.4540 Fact: 208.634,5498 = I R . OVA! E Revisions: 13F Submission Aug. 15/02 SIceeC (D } 6 11 . PARTIAL ROOF FLOOR PLAN � SCALE: 1/8" = l'—O" 1 I z V ` N I /ME CHA#i'JA 209 0 0 E1 ----o _ El - EXISTING PANEL ' - — E �\--DUCT DETECTOR PROVIDED BY MECHANICAL CONTRACTOR WIRED BY ELECTRICAL CONTRACTOR \(TYP 2) PARTIAL UPPER LEVEL HEALTH CLUB ELECTRICAL PLAN _ SCALE: 1 /8" - 1 1 -a ,> NOTES: 1. REFER TO MECHANICAL EQUIPMENT SCHEDULE ON SHEET M1.0 FOR CIRCUITING, CONDUIT, FEEDER SIZES, ETC. 2. COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL DRAWINGS. 3. ALL ELECTRICAL LOADS BEING DEMOED SHALL BE DEMOED BACK TO SERVING ELECTRICAL PANEL. 4. ALL EXISTING LIGHTING SHALL REMAIN. CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR ANY RELOCATION OF EXISTING LIGHTING FIXTURES. 5. REFER TO MECHANICAL DRAWINGS FOR FIRE DAMPER LOCATIONS. i Ilk f III I � SCALE: 1/8" = 1' —O" (E) EAR { LT-(D I { f , -- -DEMO ALL EXISTING POWER CONNECTIONS TO ALL EQUIPMENT, LIGHTING, ETC. IN THIS AREA l EF / \ Lill f I f 41j , (D �N To _ PAT Spy 1 SCALE: 1/8" = 1' -0" Q ffif� {��ff ��Fli tt t #�'rl11tt4111�,i. BEAUDIN GANZE Consulting Engineers, Inc. Vat (970) 949 -°6108 Lake Tahoe (530) 550 -7334 C3anNa' (303)278 -3820 2002 RDA ASSOCIATES Revisions: BP °ukamraaron Aug. 15/02 �1 1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS. 2. IT SHALL BE ASSUMED THAT ALL SUBCONTRACTORS ARE EXPERIENCED AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A RESPONSIBLE MANNER IN ESTABLISHED CONSTRUCTION SEQUENCE, RECOGNIZING THE PRIORITY OF THE CONSTRUCTION DOCUMENTS, DRAWING, AND DETAILS, AND SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN DRAWINGS ARE UNCLEAR OR INCONSISTENT. 3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME CONTRACTOR OF DISCREPANCIES OR CONFLICTS ON THESE CONSTRUCTION DOCUMENTS FOUND DURING BIDDING AND /OR CONSTRUCTION PRIOR TO PERFORMING THE WORK. SUCH DISCREPANCIES SHALL BE RECEIVED EXPEDITIOUSLY AND NOTIFICATION GIVEN TO THE SUBCONTRACTOR EITHER VERBALLY OR IN WRITING AS APPLICABLE TO THE CONDITION. 4. EXAMINATION OF BIDDING DOCUMENTS. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 5. INASMUCH AS DESIGN FOR REMODEL AND /OR REHABILITATION REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THE ENGINEER CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES HEREIN ENCOMPASS ALL CONTINGENCIES. FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR UNSEEN CONDITIONS. 6. THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE HINDERED BY THIS WORK. ACCOUNT FOR ALL ADDITIONAL COSTS WHICH MAY BE INCURRED DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, FURNITURE, EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN AREA MAY BE ACCESSIBLE WHEN COMPILING HIS BID. 7. BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR DUCTWORK REMAINING TO BE CONNECTED TO NEW OR EXISTING SYSTEMS. PROVIDE DUCTWORK, PIPING, CONTROLS, DIFFUSERS, ETC., AS REQUIRED TO RESTORE CONTINUITY OF SYSTEM (S), OR TO MAKE NEW WORK MEET EXISTING CONDITIONS, WHETHER INDICATED OR NOT. 8. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS, MATERIALS AND /OR EQUIPMENT SHALL BE IDENTIFIED BY THE SUBCONTRACTOR WITHIN A REASONABLE TIME TO ALLOW SELECTION, PURCHASE, AND DELIVERY SO AS TO PREVENT DELAY ON THE JOB SCHEDULE. 9. PROVIDE MECHANICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED. VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. EXISTING FIXTURES, MECHANICAL EQUIPMENT, ETC., BEING REMOVED SHALL BE RETURNED TO THE OWNER. DISPOSE OF ALL REMOVED PIPING, DUCTWORK, ETC. UNLESS NOTED OTHERWISE. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED, UNLESS OTHERWISE NOTED. 10. ALL DUCTWORK, DIFFUSERS, PIPING, FIXTURES, AND EQUIPMENT SHOWN IN LIGHT LINE WEIGHT IS EXISTING, NEW INDICATED BY HEAVIER LINE WEIGHT, EXCEPT WHERE NOTED. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED. 11. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE STRUCTURE, BEAMS, COLUMNS, AND EXISTING EQUIPMENT. 12. ALL EXISTING SUPPORT RODS AND STRAPS NOW SUPPORTING DUCTS, PIPES, AIR TUBING, ELECTRICAL CONDUIT, ETC. THAT ARE REMOVED TO ALLOW ROOM FOR INSTALLATION OF NEW EQUIPMENT SHALL BE RELOCATED AND REINSTALLED, OR REPLACED IF DAMAGED. 13. CAP ALL DEMOLISHED AND ABANDONED DUCT TAKE -OFFS AT TRUNK DUCT. 14. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT. 15. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS /HER WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF MODIFICATION OF HIS /HER WORK IS REQUIRED FOR COMPLIANCE. 16. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE 1997 BUILDING, MECHANICAL, PLUMBING, FIRE AND 1999 NATIONAL ELECTRICAL CODES, NFPA, AND ALL LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'S INSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS EXIST, THE MOST STRINGENT REQUIREMENT SHALL APPLY. 17. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF COMPLETION. 18. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND LABOR WHICH MAY OCCUR UNDER NORMAL USAGE. THE GUARANTY SHALL BE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. MECHANICAL SPECIFICATIONS; 19. PROVIDE RECORD DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC. 20. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER, 21. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO ADDITIONAL COST TO OWNER. 22. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE LISTED EQUIPMENT SHALL BE ALLOWED IN THE BASE BID. A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED ARE CONSIDERED GENERAL EQUIVALENTS ONLY. B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS: WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERAL EQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL AND OTHER WORK. 1. PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND PROPERLY FITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF DESIGN. 2. PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF DESIGN PLUS ANY SPECIFIED OPTIONS. 3. BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT, FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR SUBSTITUTIONS DO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE DESIGN. 23. ALL MATERIALS AND /OR EQUIPMENT SHALL BE HANDLED AND INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS. 24. SUBMIT ENTIRE HVAC AND PLUMBING AND FIRE PROTECTION SHOP DRAWING SUBMITTAL DATA AT ONE TIME. SUBMITTAL TO BE BOUND IN THREE -RING BINDERS, INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, INSULATION, DIFFUSERS, PUMPS, FANS, PIPING, VALVES, CONTROLS, AND FIRE PROTECTION. 25. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND /OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 26. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE OR FUNCTION. 27. COORDINATE ALL PENETRATIONS OF THE FLOOR SLAB PRIOR TO COMMENCING WORK. UTILIZE X -RAY AND VISUAL INVESTIGATION OF EXISTING CONDITIONS AS REQUIRED PRIOR TO DRILLING OR CUTTING. COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE WORK. ALL CONTRACTORS ARE INDIVIDUALLY RESPONSIBLE FOR ALL PENETRATIONS REQUIRED BY THEIR DIVISIONS. 28. PROVIDE 4" HIGH CONCRETE EQUIPMENT PADS BENEATH FLOOR MOUNTED MECHANICAL EQUIPMENT, IN ADDITION TO ANY BASE ASSEMBLIES REQUIRED BY MANUFACTURER. 29. FIRE STOPPING REQUIREMENT. PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FOR FIRE STOPS ASTM -E- 814. ACCEPTABLE MATERIALS INCLUDE: DOW CORNING RTV FIRE STOP FOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 150 CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING CONSTRUCTION GAPS; 3M CP -25 CAULK AND FS -195 INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICAL CABLE. SUBMIT UL LISTED APPLICATION DATA FOR EACH TYPE OF PENETRATION ENCOUNTERED. 30. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE ARCHITECTURAL DRAWINGS. IN THE ABSENCE OF ANY OTHER REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS IN BUILT -UP ROOFS, TALL CONE NTH EPDM BOOT FOR PIPE AND CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BE WATERTIGHT. 31. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING PENETRATIONS AND AIR DEVICE LOCATIONS. 32. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, ELECTRICAL, LANDSCAPING, AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION. 33. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE. 34. MOUNT ALL STATS AT 4'6" A.F.F. COORDINATE LOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS. NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTATS AT INSTALLATION. 35. SUBMIT A WRITTEN BALANCE REPORT BY A NEBB OR AABC CERTIFIED BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE IN ACCORDANCE WITH NEBB OR AABC GUIDELINES FOR PROPORTIONAL BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW PRIOR TO BALANCING. MEASUREMENTS SHALL INCLUDE ALL MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC PRESSURE AT INLET AND OUTLET OF ALL PACKAGED EQUIPMENT, FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM OUTSIDE AIR; VELOCITY DISTRIBUTION ACROSS THE FACE OF FILTERS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOW MEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE DROP, AND PRESSURE DROP AT ALL COILS. A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO ADJUST FAN SPEED. B. ADJUST FLOWS TO WITHIN 10% OF REQUIRED QUANTITY. WHERE ROOM AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN BY A DIFFERENTIAL OF SUPPLY AND EXHAUST /RETURN OR BY NOTE, ADJUST SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST /RETURN TO PROVIDE THE INDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN 907., INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. SUBMITTAL OF BALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT EXPLANATION IS CAUSE FOR REJECTION OF REPORT. C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL BE RETAINED BY THE OWNER, ARCHITECT, AND ENGINEER. 36. DUCTWORK: (LOW VELOCITY) A. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS CLOTH, 10" W.C. RATED. B. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5 GORE ELBOWS. "SNAP - LOCK ", LONGITUDINAL SEAM DUCT, OR ADJUSTABLE FITTINGS ARE ACCEPTABLE ON INDIVIDUAL GRILLE /DIFFUSER RUNOUTS ONLY. C. LINER: 1. LINE ALL SUPPLY AND OUTSIDE AIR, RETURN AIR DUCTS, EXHAUST AIR RISERS, AND MAKE UP AIR RISERS WITH V. 1.5 PCF, BLACK MATTE COATED INSULATING DUCT LINER. 2. MATERIAL SHALL MEET ALL REQUIREMENTS OF NFPA -90. 3. INSTALL WITH ADHESIVE AND PINS IN ACCORDANCE WITH SMACNA "HVAC DUCT CONSTRUCTION STANDARDS`. 4. EXTERNALLY LINE ALL ROUND SUPPLY AIR DUCTS WITH FLEXIBLE GLASS FIBER, ANSI /ASTM C612; 0.002 INCH FOIL SCRIM FACING. D. DUCTWORK: GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; CONSTRUCTED TO THE LATEST EDITION OF SMACNA "HVAC DUCT CONSTRUCTION STANDARDS% +/- 1" W.C. PRESSURE CLASSIFICATION, SEAL CLASS "C "; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, STRAPS, ETC. E. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH UNITED MCGILL "UNI -GRIP" UL LISTED, WATER BASED, NON - HARDENING, ELASTIC SEALANT OR EQUIVALENT. 37. ALL AHU -1 DUCTWORK DIMENSIONS ARE OUTSIDE SHEET METAL DIMENSIONS. DUCT LINER HAS BEEN ACCOUNTED FOR. ALL MUA -1 DUCTWORK DIMENSIONS ARE OUTSIDE INSULATION DIMENSIONS. DUCT WRAP HAS BEEN ACCOUNTED FOR. 38. DUCTWORK NOTES: A. DIFFUSER NECK SIZES IS SAME AS FLEXIBLE DUCT SIZE. B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH. 1. WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT ELBOWS WITH SINGLE WIDTH (NON - AIRFOIL) TURNING VANES. 2. FOR DUCT DEPTHS OF 36" OF LESS, PROVIDE MANUFACTURED SINGLE WIDTH (NON - AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR "STANDARD SPACING ", USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36 ". USE NO TRAILING EDGES. C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED FIVE FEET IN LENGTH. FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASS INSULATION, HIGH- STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN REINFORCED "RIP STOP" ALUMINUM LAMINATE INTERIOR CORE, UL LISTED AND LABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POS. 60 , NEC. 4 ". FLEXMASTER TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINE EQUIVALENCE. 39. GREASE EXHAUST DUCT A. MATERIAL: 1. CONCEALED TO VIEW. 16 GAUGE, GALVANIZED OR UNCOATED CARBON STEEL. 2. EXPOSED TO VIEW: 16 GAUGE STAINLESS STEEL. B. SEAMS: WELDED OR BRAZED. REPAIR GALVANIZED COATING AT WELDS. GRIND AND POLISH SEAMS ON EXPOSED STAINLESS STEEL. C. MATERIALS IN ACCORDANCE WITH NFPA 96. D. INSTALL IN ACCORDANCE WITH UNIFORM MECHANICAL CODE, NFPA 96, AND LOCAL MODIFICATIONS TO THOSE CODES. E. HORIZONTAL DUCT LESS THAN 75 FEET IN ONE RUN SHALL BE PITCHED AT 1/4" PER FOOT TOWARDS THE HOOD OR A DRAIN POINT. F. SEE ARCHITECTURAL DRAWINGS FOR ENCLOSURE REQUIREMENTS. 1. SEE DIVISION 1 FOR SHAFT WALL ENCLOSURE SYSTEMS. 2. INSTALL DUCT SO A MINIMUM OF 3" AND A MAXIMUM OF 12" IS MAINTAINED BETWEEN DUCT AND ENCLOSURE. G. USE NO TURNING VANES, TIE RODS, DAMPERS, OR OTHER INTERNAL STRUCTURES WHICH WILL COLLECT GREASE. ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUSED FITTINGS. H. PROVIDE CLEANOUTS AS FOLLOWS: 1. VERTICAL DUCTS SHALL EITHER HAVE ONE OPENING AT THE TOP LARGE ENOUGH FOR PERSONNEL ENTRANCE AND DESCENT OR A MINIMUM 12 "x6" OPENINGS AT EVERY FLOOR. 2. OPENINGS SHALL HAVE A FLANGED FRAME, EXTENDING 1" OFF THE DUCT WALL. CLOSURE PANELS SHALL BE ATTACHED TO THE FLANGE BY MEANS OF THREADED STUDS WELDED TO THE FLANGE, PROTRUDING THROUGH HOLES IN THE PANEL AND FASTENED BY MEANS OF WING NUTS. PROVIDE "FIBER FRAX" OR EQUIVALENT HIGH TEMPERATURE (1500 DEGREE F) ROPE TYPE GASKET BONDED TO EITHER THE GASKET OR PANEL. 3. PROVIDE ACCESS DOORS IN THE ENCLOSURE AT ALL CLEANOUTS. A. USE UL LISTED METHODS FOR BLANKET TYPE FIRE RATED ENCLOSURES. B. USE UL LISTED FIRE RATED ACCESS DOORS IN SHAFT WALL ENCLOSURES. 40. SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR CLAMPS. NO PIPE TAPE ALLOWED. ALL HANGERS SHALL BE SIZED FOR OD OF INSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET METAL SHIELDS FOR PIPING 1 -1/2" AND LESS. PROVIDE CALCIUM SILICATE INSULATION INSERTS FOR ALL INSULATED PIPING 2" AND LARGER. MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE COPPER LINES FROM HANGERS WITH VIBRASORB OR EQUIVALENT, COPPER COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT ACCEPTABLE. 41. MATERIALS; HYDRONIC PIPING A. ABOVE GRADE, UP THROUGH 2 -1/2 ": SCHEDULE 40 STEEL PIPE WITH MALLEABLE IRON THREADED FITTINGS, OR TYPE "L" COPPER TUBE WITH WROUGHT COPPER FITTINGS AND 95 -5 NO LEAD SOLDER. B. ABOVE GRADE, 3" AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST IRON OR STEEL WELDING FITTINGS. 42. REFRIGERATION PIPING -TYPE "L ", ACR GRADE COPPER, CLEANED, DEHYDRATED, AND CAPPED AT THE FACTORY. USE WROUGHT COPPER FITTINGS AND HARD SOLDER HAVING A MINIMUM MELTING POINT OF 1100 DEGREE F FOR BURIED LINES, 95 -5 SOLDER FOR NON - BURIED LINES. VALVES AND SPECIALTIES SHALL BE STANDARD BRASS OR BRONZE VALVES FOR REFRIGERATION SERVICE. BURIED PIPE SHALL BE SURROUNDED BY 4" CLEAN SAND. 43. INSULATE ALL NEW HEATING WATER AND DOMESTIC COLD PIPING WITH U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP -ON, PIPE INSULATION. INSULATE FITTINGS WITH GLASS FIBER BLANKET INSULATION AND PREMOLDED P.V.C. COVERS, ALL MATERIALS SHALL HAVE A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 OR LESS, INSULATION SHALL PASS UNINTERRUPTED THROUGH HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH "NON- BREATHING" MASTIC ON COLD PIPING. ALL RAW EDGES OF INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC. A. INSULATION THICKNESS: 1. HEATING WATER: ALL SIZES - 1" RUNOUTS WITHIN 20 FEET OF TERMINAL UNIT - 1/2 ". 2. DOMESTIC COLD WATER: ALL SIZES - 1/2". 44. EQUIPMENT LABELS: LABEL ALL NEW PIPING AND EQUIPMENT. PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON PIPING. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER AND ATTACH WITH STANDARD CHAIN OR S- NOOKS. PROVIDE ENGRAVED PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT. 45. FIRE PROTECTION DESIGN /BUILD REQUIREMENTS: A. THE FIRE SPRINKLER CONTRACTOR SHALL SERVE AS THE ENGINEER OF RECORD FOR ALL WORK PERFORMED UNDER THIS DIVISION. IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, (A.H.J.) SUBMIT COMPLETE FIRE SPRINKLER SYSTEM SHOP DRAWINGS AND HYDRAULIC CALCULATIONS, GENERATED BY CONTRACTOR. SHOW DRAWINGS SHALL BE A MINIMUM 1/$" SCALE, SHOW DEVICE AND APPLIANCE LOCATIONS, BUILDING BACKGROUND INFORMATION, ROOM OCCUPANCY DESCRIPTIONS, DOOR SWINGS, FIRE RATINGS AND FIRE PROTECTION SYSTEM LAYOUT AND DETAILS. SHOP DRAWINGS AND HYDRAULIC CALCULATIONS SHALL BE SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF COLORADO. SUBMIT SHOP DRAWINGS AND HYDRAULIC CALCULATIONS TO THE BUILDING INSPECTIONS DIVISION AND FIRE PREVENTION BUREAU FIRST, AS APPLICABLE AND OBTAIN THEIR APPROVAL BEFORE SUBMISSIONS TO THE ARCHITECT. B. EXTEND THE EXISTING SPRINKLER SYSTEM, RELOCATE EXISTING AND ADD NEW SPRINKLER HEADS IN ACCORDANCE WITH NFPA 13, ALL APPLICABLE CODES AND ORDINANCES AND PROJECT REQUIREMENTS TO COMPLETE THE NEW WORK. PRICING NOTE: PROVIDE ADD ALTERNATE PRICING TO PROVIDE A 43 MBH DUCT COIL IN THE 32x10 SA DUCT SERVING THE NORTH END OF THE RETTURANT. PROVIDE A 1" HWS /HWR. CONNECT TO 4" HWS /HWR IN CORRIDOR. PRICE SHALL INCLUDE ALL PIPING, INSTALLATION, BALANCING, CONTROLS, ETC. TO MAKE A COMPLETE AND OPERABLE SYSTEM. N 0 A rwq DAUM GmzE ro/ Consulting Engineers, Inc. Lake 1drar9(530) -733+ Denver: (30PW -3820 2002 RDA RESORT DESIGN ARCHITECTURE, PLANNING, INTERIOR DESIGN 388 Market St., Suite #380 San Francisco, CA 94111 Tel: 415,392.4433 Fax 415.392.4454 Boulder Office 1434 Spruce Street, Suite 110 Boulder, CO 80302 Tel: 303,449.4433 Fax 303.449.3366 McCall Office 1002 First Street McCall, ID 83638 Tel: 208.634.4540 Fax: 208.634.5498 I r14 i E Drawing Title: MECHANICAL COVER SHEET Date: 9/16/02 Project No: 5822.13 Drawn by: T60 Reviewed by: - -- MT-5 I i �f