M03-0055 Plans
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS. 2 IT SHALL BE ASSUMED THAT ALL SUBCONTRACTORS ARE EXPERIENCED AND THOROUGHLY KNOWLEDGEABLE IN THEIR RESPECTIVE AREAS OF THE CONSTRUCTION INDUSTRY AND SHALL PERFORM IN A RESPONSIBLE MANNER IN ESTABLISHED CONSTRUCTION SEQUENCE, RECOGNIZING THE PRIORITY OF THE CONSTRUCTION DOCUMENTS, DRAWING, AND DETAILS, AND SHALL INFORM THE PRIME CONTRACTOR OF POTENTIAL PROBLEMS WHEN DRAWINGS ARE UNCLEAR OR INCONSISTENT. 3. SUBCONTRACTORS SHALL BE RESPONSIBLE TO NOTIFY THE PRIME CONTRACTOR OF DISCREPANCIES OR CONFLICTS ON THESE CONSTRUCTION DOCUMENTS FOUND DURING BIDDING AND /OR CONSTRUCTION PRIOR TO PERFORMING THE WORK. SUCH DISCREPANCIES SHALL BE RECEIVED EXPEDITIOUSLY AND NOTIFICATION GIVEN TO THE SUBCONTRACTOR EITHER VERBALLY OR IN WRITING AS APPLICABLE TO THE CONDITION. 4. EXAMINATION OF BIDDING DOCUMENTS. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 5. INASMUCH AS DESIGN FOR REMODEL AND /OR REHABILITATION REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS CANNOT BE VERIFIED WITHOUT DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THE ENGINEER CANNOT ASSURE THE OWNER OR THE CONTRACTOR THAT THE PROFESSIONAL CONSULTING SERVICES HEREIN ENCOMPASS ALL CONTINGENCIES. FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. MAKE REASONABLE ALLOWANCES FOR UNSEEN CONDITIONS. 6. THE EXISTING BUILDING WILL BE OCCUPIED BY THE OWNER DURING CONSTRUCTION. CONTINUED OPERATION OF THE FACILITY SHALL NOT BE HINDERED BY THIS WORK. ACCOUNT FOR ALL ADDITIONAL COSTS WHICH MAY BE INCURRED DUE TO THE DIFFICULTY OF WORKING OVER AND AROUND EMPLOYEES, FURNITURE, EQUIPMENT, ETC.; AND DUE TO THE HOURS OF THE DAY IN WHICH AN AREA MAY BE ACCESSIBLE WHEN COMPILING HIS BID. 7. BE RESPONSIBLE TO FIELD VERIFY EXISTING EQUIPMENT OR DUCTWORK REMAINING TO BE CONNECTED TO NEW OR EXISTING SYSTEMS. PROVIDE DUCTWORK, PIPING, CONTROLS, DIFFUSERS, ETC,, AS REQUIRED TO RESTORE CONTINUITY OF SYSTEM (S), OR TO MAKE NEW WORK MEET EXISTING CONDITIONS, WHETHER INDICATED OR NOT. 8. IF NOT SPECIFICALLY DEFINED IN THESE CONSTRUCTION DOCUMENTS, MATERIALS AND /OR EQUIPMENT SHALL BE IDENTIFIED BY THE SUBCONTRACTOR WITHIN A REASONABLE TIME TO ALLOW SELECTION, PURCHASE, AND DELIVERY SO AS TO PREVENT DELAY ON THE JOB SCHEDULE. 9. PROVIDE MECHANICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOL111ON REQUIRED. VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. EXISTING FIXTURES, MECHANICAL EQUIPMENT, ETC., BEING REMOVED SHALL BE RETURNED TO THE OWNER. DISPOSE OF ALL REMOVED PIPING, DUCTWORK, ETC. UNLESS NOTED OTHERWISE. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED, UNLESS OTHERWISE NOTED. 10. ALL DUCTWORK, DIFFUSERS, PIPING, FIXTURES, AND EQUIPMENT SHOWN IN LIGHT LINE WEIGHT IS EXISTING, NEW INDICATED BY HEAVIER LINE WEIGHT, EXCEPT WHERE NOTED. PIPES, DUCTWORK, EQUIPMENT, ETC. TO BE REMOVED, ARE SHOWN HATCHED. 11. OFFSET PIPING, DUCTWORK, ETC. AS NECESSARY TO ACCOMMODATE STRUCTURE, BEAMS, COLUMNS, AND EXISTING EQUIPMENT. 12. ALL EXISTING SUPPORT RODS AND STRAPS NOW SUPPORTING DUCTS, PIPES, AIR TUBING, ELECTRICAL CONDUIT, ETC. THAT ARE REMOVED TO ALLOW ROOM FOR INSTALLATION OF NEW EQUIPMENT SHALL BE RELOCATED AND REINSTALLED, OR REPLACED IF DAMAGED. 13. CAP ALL DEMOLISHED AND ABANDONED DUCT TAKE -OFFS AT TRUNK DUCT. 14. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT. 15. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PERFORM HIS /HER WORK IN CONFORMANCE WITH ALL APPLICABLE CODES, ORDINANCES AND LIFE SAFETY FEATURES AS REQUIRED BY LOCAL, STATE, OR NATIONAL AUTHORITIES. THE CONTRACTOR SHALL VERIFY WITH THE ARCHITECT IF MODIFICATION OF HIS /HER WORK IS REQUIRED FOR COMPLIANCE. 16. ALL WORK OF ALL TRADES MUST BE IN STRICT COMPLIANCE, OR EXCEED THE MINIMUM MATERIAL AND METHOD REQUIREMENTS OF THE 1997 BUILDING, MECHANICAL, PLUMBING, FIRE AND 1999 NATIONAL ELECTRICAL CODES, NFPA, AND ALL LOCAL ORDINANCES AND AMENDMENTS AND MANUFACTURER'S INSTALLATION RECOMMENDATIONS. IF A CONFLICT BETWEEN THOSE PUBLICATIONS EXIST, THE MOST STRINGENT REQUIREMENT SHALL APPLY, 17. PAY FOR AND SECURE ALL REQUIRED PERMITS AND INSPECTIONS. PRIOR TO FINAL PAYMENT, TURN OVER TO ARCHITECT ALL CERTIFICATES OF COMPLETION. 18, GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND LABOR WHICH MAY OCCUR UNDER NORMAL USAGE. THE GUARANTY SHALL BE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. MECHANICAL SPECIFICATIONS.- 19. PROVIDE RECORD DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTINGS, ETC. 20. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION PRIOR TO ACCEPTANCE BY THE OWNER. 21. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. PERFORM AT A MINIMUM ALL CODE REQUIRED TESTS OR SYSTEMS. IF TESTS OF WORK ARE DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO ADDITIONAL COST TO OWNER. 22. PROVIDE A BASE BID WHICH SHALL INCLUDE ONLY SPECIFIED EQUIPMENT OR EQUIPMENT LISTED AS EQUIVALENT. NO SUBSTITUTIONS FOR THE LISTED EQUIPMENT SHALL BE ALLOWED IN THE BASE BID. A. THE MANUFACTURER OF EQUIPMENT OR MATERIALS FIRST NAMED ON THE DRAWINGS IS THE BASIS OF DESIGN. OTHER MANUFACTURERS LISTED ARE CONSIDERED GENERAL EQUIVALENTS ONLY. B. COORDINATION OF GENERAL EQUIVALENTS AND SUBSTITUTIONS: WHERE CONTRACT DOCUMENTS PERMIT SELECTION FROM SEVERAL GENERAL EQUIVALENTS, OR WHERE SUBSTITUTIONS ARE AUTHORIZED, COORDINATE CLEARANCE AND OTHER INTERFACE REQUIREMENTS WITH MECHANICAL AND OTHER WORK. 1. PROVIDE NECESSARY ADDITIONAL ITEMS SO THAT SELECTED OR SUBSTITUTED ITEM OPERATES EQUIVALENT TO THE BASIS OF DESIGN AND PROPERLY FITS IN THE AVAILABLE SPACE ALLOCATED FOR THE BASIS OF DESIGN. 2. PROVIDE ALL FEATURES WHICH ARE STANDARD ON THE BASIS OF DESIGN PLUS ANY SPECIFIED OPTIONS. 3. BE RESPONSIBLE FOR ASSURING THAT PIPING, CONDUIT, DUCT, FLUE, AND OTHER SERVICE LOCATIONS FOR GENERAL EQUIVALENTS OR SUBSTITUTIONS DO NOT CAUSE ACCESS, SERVICE, OR OPERATIONAL DIFFICULTIES ANY GREATER THAT WOULD BE ENCOUNTERED WITH THE BASE DESIGN. 23. ALL MATERIALS AND /OR EQUIPMENT SHALL BE HANDLED AND INSTALLED AS PER MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS. 24. SUBMIT ENTIRE HVAC AND PLUMBING AND FIRE PROTECTION SHOP DRAWING SUBMITTAL DATA AT ONE TIME. SUBMITTAL TO BE BOUND IN THREE -RING BINDERS, INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO: EQUIPMENT, INSULATION, DIFFUSERS, PUMPS, FANS, PIPING, VALVES, CONTROLS, AND FIRE PROTECTION. 25. FAILURE TO ORDER, OR RELEASE ORDER FOR MATERIALS AND /OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 26. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE OR FUNCTION. 27. COORDINATE ALL PENETRATIONS OF THE FLOOR SLAB PRIOR TO COMMENCING WORK. UTILIZE X -RAY AND VISUAL INVESTIGA110N OF EXISTING CONDITIONS AS REQUIRED PRIOR TO DRILLING OR CUTTING. COORDINATE ALL NEW PENETRATIONS WITH OTHER DIVISIONS OF THE WORK. ALL CONTRACTORS ARE INDIVIDUALLY RESPONSIBLE FOR ALL PENETRATIONS REQUIRED BY THEIR DIVISIONS. 28. PROVIDE 4" HIGH CONCRETE EQUIPMENT PADS BENEATH FLOOR MOUNTED MECHANICAL EQUIPMENT, IN ADDITION TO ANY BASE ASSEMBLIES REQUIRED BY MANUFACTURER. 30. DUCTS, PIPING, AND CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING COMPATIBLE WITH THE ROOFING SYSTEM. SEE ARCHITECTURAL DRAWINGS. IN THE ABSENCE OF ANY OTHER REQUIREMENTS, PROVIDE SHEET LEAD TYPE FLASHING FOR PLUMBING VENTS IN BUILT -UP ROOFS, TALL CONE WITH EPDM B00T FOR PIPE AND CONDUIT IN SINGLE PLY MEMBRANE ROOFS, AND CURBED ROOF PENETRATIONS IN ALL TYPES OF ROOF. INSTALLATION SHALL BE WATERTIGHT. 31. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR ALL CEILING PENETRATIONS AND AIR DEVICE LOCATIONS. 32. COORDINATE ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, ELECTRICAL, LANDSCAPING, AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION. 33. CAREFULLY VERIFY ELECTRICAL SERVICE VOLTAGE AND PHASE AVAILABLE. 34, MOUNT ALL STATS AT 4'6" A.F.F. COORDINATE LOCATION WITH WALL FINISH, AND TO AVOID CASEWORK, FURNITURE, DOOR SWINGS, HEAT SOURCES, AND EXTERIOR WALLS, NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO BEGINNING THERMOSTATS AT INSTALLATION. 35 S1i3MIT A WRITyTENw BALANCk: REP02T,.BY;A.,,.NBB, OR AABC.v:GR7FlED, BALANCING CONTRACTOR. BALANCING PROCEDURES SHALL BE CN ACCORDANCE WITH NEBB OR AABC GUIDELINES FOR PROPORTIONAL BALANCE. SUBMIT REPORT ON STANDARD NEBB FORMS OR SUBMIT FORMS FOR REVIEW PRIOR TO BALANCING. MEASUREMENTS SHALL INCLUDE ALL MOTOR AMPERAGE AND VOLTAGE READINGS; MOTOR AND FAN RPMS; STATIC PRESSURE AT INLET AND OUTLET OF ALL PACKAGED EQUIPMENT, FANS, COILS, AND FILTERS; PITOT TUBE MEASUREMENT OF SUPPLY, EXHAUST, RETURN, AND OUTSIDE AIR MAIN DUCTS, AT MINIMUM OUTSIDE AIR; VELOCITY DISTRIBUTION ACROSS THE FACE OF FILTERS; AIR INLET AND OUTLETS; WATER FLOW AT ALL FLOW MEASUREMENT STATIONS; INLET AND OUTLET PRESSURE AT PUMPS WITH FLOW CALCULATED FROM THE PUMP CURVE; WATER FLOW, TEMPERATURE DROP, AND PRESSURE DROP AT ALL COILS. A. PROVIDE BELTS AND SHEAVES AS REQUIRED FOR DRIVE CHANGES TO ADJUST FAN SPEED. B. ADJUST FLOWS TO WITHIN 107o OF REQUIRED QUANTITY. WHERE ROOM 39, SUPPORT PIPE WITH ROD AND CLEVIS, RING HANGERS, TRAPEZE, OR AIR PRESSURE RELATIONSHIP ARE REQUIRED TO BE MAINTAINED AS SHOWN CLAMPS. NO PIPE TAPE ALLOWED. ALL HANGERS SHALL BE SIZED FOR OD BY A DIFFERENTIAL OF SUPPLY AND EXHAUST /RETURN OR BY NOTE, ADJUST OF INSULATION, IF ANY. PROTECT INSULATED LINES WITH 20 GA SHEET SUPPLY TO WITHIN 10% AND THEN ADJUST EXHAUST /RETURN TO PROVIDE METAL SHIELDS FOR PIPING 1 -1/2" AND LESS. PROVIDE CALCIUM THE INDICATED ROOM PRESSURE. IF ACTUAL QUANTITY IS LESS THAN SILICATE INSULATION INSERTS FOR ALL INSULATED PIPING 2" AND 907., INVESTIGATE CAUSE, ATTEMPT TO RECTIFY AND NOTIFY ENGINEER. LARGER. MAINTAIN VAPOR BARRIER ON ALL COLD LINES. ISOLATE BARE SUBMITTAL OF BALANCE REPORT WITH LESS THAN REQUIRED FLOWS WITHOUT COPPER LINES FROM HANGERS WITH VIBRASORB OR EQUIVALENT, COPPER EXPLANATION IS CAUSE FOR REJECTION OF REPORT. COATED HANGERS ARE NOT SUFFICIENT, WRAPPING PIPE WITH TAPE NOT ACCEPTABLE. C. SUBMIT THREE (3) COPIES OF ALL SUBMITTALS IN ADDITION TO ANY REQUIRED BY THE CONTRACTOR AND HIS SUPPLIERS. THESE COPIES SHALL 40. MATERIALS; HYDRONIC PIPING BE RETAINED BY THE OWNER, ARCHITECT, AND ENGINEER. A. ABOVE GRADE, UP THROUGH 2 -1/2 ": SCHEDULE 40 STEEL PIPE WITH 36. DUCTWORK: (LOW VELOCITY) MALLEABLE IRON THREADED FITTINGS, OR TYPE "L" COPPER TUBE WITH WROUGHT COPPER FITTINGS AND 95 -5 NO LEAD SOLDER. A. FLEXIBLE CONNECTION: EQUIVALENT TO VENTFAB, FIREPROOF GLASS CLOTH, 10" W.G. RATED, B. ABOVE GRADE, 3" AND LARGER: SCHEDULE 40 STEEL PIPE WITH CAST IRON OR STEEL WELDING FITTINGS. B. ROUND DUCT: SPIRAL SEAM, GALVANIZED STEEL. DIE STAMPED OR 5 GORE ELBOWS, "SNAP - LOCK ", LONGITUDINAL SEAM DUCT, OR 41. INSULATE ALL NEW HEATING WATER AND DOMESTIC COLD PIPING WITH ADJUSTABLE FITTINGS ARE ACCEPTABLE ON INDIVIDUAL GRILLE /DIFFUSER U.L. APPROVED, WHITE, ALL SERVICE, GLASS FIBER, SNAP -ON, PIPE RUNOUTS ONLY. INSULATION. INSULATE FITTINGS WITH GLASS FIBER BLANKET INSULATION AND PREMOLDED P.V.C. COVERS. ALL MATERIALS SHALL HAVE C. LINER: A SMOKE DEVELOPED RATING OF 50 OR LESS AND A FLAME SPREAD RATING OF 25 OR LESS. INSULATION SHALL PASS UNINTERRUPTED THROUGH 1. LINE ALL SUPPLY AND OUTSIDE AIR, RETURN AIR DUCTS, AND HANGERS. VAPOR BARRIERS SHALL BE CONTINUOUS, AND SEALED WITH EXHAUST AIR RISERS WITH 1 ", 1.5 PCF, BLACK MATTE "NON- BREATHING" MASTIC ON COLD PIPING. ALL RAW EDGES OF i COATED INSULATING DUCT LINER. INSULATION SHALL BE NEATLY TRIMMED AND SEALED WITH MASTIC. 2. MATERIAL SHALL MEET ALL REQUIREMENTS OF NFPA -90. A. INSULATION THICKNESS: 3. INSTALL WITH ADHESIVE AND PINS IN ACCORDANCE WITH SMACNA 1. HEATING WATER: ALL SIZES - 1" RUNOUTS WITHIN 20 FEET OF "HVAC DUCT CONSTRUCTION STANDARDS ", TERMINAL UNIT - 1/2 ". 4. EXTERNALLY LINE ALL ROUND SUPPLY AIR DUCTS WITH FLEXIBLE 2. DOMESTIC COLD WATER: ALL SIZES - 1/2 ". GLASS FIBER, ANSI /ASTM C612; 0.002 INCH FOIL SCRIM FACING, 44. EQUIPMENT LABELS: LABEL ALL NEW PIPING AND EQUIPMENT. D. DUCTWORK: GALVANIZED SHEET STEEL; LOCK FORMING QUALITY; PROVIDE FULL BAND OR STRIP TYPE MARKERS AND FLOW ARROWS ON CONSTRUCTED TO THE LATEST EDITION OF SMACNA "HVAC DUCT PIPING. PROVIDE ENGRAVED PLASTIC VALVE TAGS WITH VALVE NUMBER CONSTRUCTION STANDARDS "; +/- 1" W.C. PRESSURE CLASSIFICATION, AND ATTACH WITH STANDARD CHAIN OR S- HOOKS. PROVIDE ENGRAVED SEAL CLASS "C "; WITH GALVANIZED STEEL FASTENERS, ANCHORS, ANGLES, PLASTIC SIGN ON OR NEAR SPECIFIED EQUIPMENT. STRAPS, ETC. 45. ESP gT`ECIgN�.DESIGN : <BUTLD REQUIREMENTS z ,t �� - °�> rT- E. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIRTIGHT WITH " UNITED MCGILL "UNI -GRIP" UL LISTED, WATER BASED, NON - HARDENING, A. THE RE SPRINKLER CONTRACTOR SHALL SERVE AS THE ENGINEER OF > ELASTIC SEALANT OR EQUIVALENT. RECORD FOR ALL WORK PERFORMED UNDER THIS DIVISION. IF REQUIRED SUBMIT COMPLETE BY THE AUTHORITY HAVING JURISDICTION, 37. ALL MUA -1 AND MUA -2 DUCTWORK DIMENSIONS ARE OUTSIDE INSULATION FIRE SPRINKLER SYSTEM HOPDRAWIN S AND HYDRAU IC CALCULATIONS, DIMENSIONS. DUCT WRAP HAS BEEN ACCOUNTED FOR. GENERATED BY CONTRACTOR. SHOW DRAWINGS SHALL BE A MINIMUM 1/8" `�` SCALE, SHOW DEVICE AND APPLIANCE LOCATIONS, BUILDING BACKGROUND 38. DUCTWORK NOTES: INFORMATION, ROOM OCCUPANCY DESCRIPTIONS, DOOR SWINGS, FIRE RATINGS AND FIRE PROTECTION SYSTEM LAYOUT AND DETAILS. SHOP A. DIFFUSER NECK SIZES IS SAME AS FLEXIBLE DUCT SIZE. DRAWINGS AND HYDRAULIC CALCULATIONS SHALL BE SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF COLORADO. B. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE SUBMIT SHOP DRAWINGS AND HYDRAULIC CALCULATIONS TO THE BUILDING MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 INSPECTIONS DIVISION AND FIRE PREVENTION BUREAU FIRST, AS DUCT WIDTH, APPLICABLE AND OBTAIN THEIR APPROVAL BEFORE SUBMISSIONS TO THE ARCHITECT. i 1. WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE SQUARE THROAT ELBOWS WITH SINGLE WIDTH (NON- AIRFOIL) TURNING VANES. B. EXTEND THE EXISTING SPRINKLER SYSTEM, RELOCATE EXIS11NO AND 4 ADD NEW SPRINKLER HEADS IN ACCORDANCE WITH NFPA 13, ALL ! 2. FOR DUCT DEPTHS OF 36" OF LESS, PROVIDE MANUFACTURED SINGLE APPLICABLE CODES AND ORDINANCES AND PROJECT REQUIREMENTS TO WIDTH (NON - AIRFOIL) TURNING VANES, WITH SPACING IN ACCORDANCE COMPLETE THE NEW WORK. WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR "STANDARD SPACING ", ! USE DOUBLE THICKNESS BLADES FOR DUCT DEPTHS GREATER THAN 36 ". USE NO TRAILING EDGES. C. ALL FLEXIBLE DUCTS SHALL NOT EXCEED FIVE FEET IN LENGTH. { FLEXIBLE DUCTWORK SHALL HAVE AN OUTER JACKET OF FIRE RETARDANT POLYETHYLENE VAPOR BARRIER MATERIAL, UNIFORM LAYER OF FIBERGLASS INSULATION, HIGH - STRENGTH GALVANIZED STEEL HELIX ENCAPSULATED IN REINFORCED "RIP STOP" ALUMINUM LAMINATE INTERIOR CORE, UL LISTED AND LABELED, CLASS 1 AIR DUCT. WORKING PRESSURE RATING: POS. 6 ", NEC. 4 ". FLEXMASTER TYPE 5 OR EQUIVALENT. SUBMIT SAMPLES TO DETERMINE EQUIVALENCE. iVa'CE o F TW,<,E Q F9ui jeFryYt £su7S q7 vac. SEC- _?r0 T>12 t c) oa- 1-0 II �-t ��� ifi1SAecTI()rt -rS �Cac.�� e� BEAUDIN GmzE Z*o, consulting Engineers, Inc. > MECHANICAL EQUIPMENT SPECIFICTICNS: MUA -1 & MUA -2, MAKE —UP AIR UNITS THE SUPPLY FAN UNIT SHALL BE OF THE BELT — DRIVEN, DOUBLE WIDTH, DOUBLE INLET, FORWARD CURVED CENTRIFUGAL BLOWER TYPE. THE BLOWER ASSEMBLY SHALL BE MOUNTED ON VIBRATION ISOLATORS. DRIVES SHALL BE SIZED FOR A MINIMUM OF 165% OF DRIVEN HORSEPOWER. ALL EXTERIOR HOUSING COMPONENTS OF THE SUPPLY UNIT SHALL BE CONSTRUCTED OF MINIMUM 18 GAUGE GALVANEAL STEEL, PAINTED WITH A WEATHERPROOF FINISH THAT HAS BEEN BAKED FOR DURABILITY. HEAVY GAUGE ADJUSTABLE ANGLE IRON SUPPORT LEGS SHALL BE FURNISHED AS REQUIRED. THE INLET OF THE UNIT SHALL CONTAIN BIRDSCREEN AND A BANK OF WASHABLE, REMOVABLE AiR FILTERS. FILTERS SHALL BE OF ONE — INCH ALUMINUM MESH TYPE, COATED WITH FILTER ADHESIVE COMPOUND AND SHALL BE U.L. CLASSIFIED. THE TOTAL FAN PACKAGE SHALL BE FURNISHED WITH A PREWIRED CONTROL CENTER WHICH SHALL INCLUDE, BUT NOT BE LIMITED TO, A MASTER —FUSED DISCONNECT FOR MAiN POWER CONNECTION, MAGNETIC MOTOR STARTERS WITH THERMAL OVERLOADS AND MANUAL RESET, FUSED 24 —VOLT CONTROL TRANSFORMER AND DISTRIBUTION TERMINAL STRIP FOR CONTROL WIRING CONNECTION. ALL ELECTRICAL COMPONENTS SHALL BE U.L LISTED, APPROVED OR CLASSIFIED WHERE APPLICABLE AND WIRED IN COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE. WIRING SHALL BE COMPLETE, REQUIRING ONLY ONE —POINT FIELD CONNECTION FOR POWER SERVICE AND ONE —POINT HELD CONNECTION FOR LOW — VOLTAGE CONTROL HARNESS. MC TO PROVIDE DUCT DETECTOR, FURNISH MOTORIZED BACKDRAFT DAMPER AS INTEGRAL PART OF SUPPLY UNIT. DAMPER UNIT SHALL OPEN UPON ENERGIZATION OF SUPPLY FAN AND CLOSE UPON SHUT —OFF OF SUPPLY FAN. HOT WATER HEATING COIL HOT WATER COIL SHALL BE ARI CERTIFIED. THE COIL SHALL BE OF EXTENDED SURFACE, STAGGERED TUBE, RIPPLE — CORRUGATED ALUMINUM PLATE FIN TYPE, INCLUDING, BUT NOT LIMITED TO, NON— FERROUS HEADERS, SEAMLESS COPPER TUBING, COOPER ALLOY BRAZED JOINTS, HEAVY GAUGE GALVANIZED STEEL CASING AND COILS WITH NO EXPOSED COPPER BETWEEN FINS. COMPLETE COILS SHALL BE TESTED AND GUARANTEED FOR 250 PSIG WORKING PRESSURES AND SHALL BE ENCLOSED IN A BAKED ENAMEL — COATED HOUSING SERVICEABLE THROUGH A LIFT —OUT ACCESS DOOR WITH ALUMINUM TWIST LATCHES, HEATING COIL SHALL BE SUPPLIED AS AN INTEGRAL PART OF THE FAN PACKAGE. ALL PIPING AND CONTROLS SHALL BE FURNISHED BY THE CONTRACTOR. EVAPORATIVE COOLING SECTION GALVANIZED STEEL CASTING, BAKED ENAMEL EXTERIOR FINISH, FOR (DOWN) (HORIZONTAL) DISCHARGE. FILTER PADS TO BE REPLACEABLE COTTON MESH WITH 3X3 PER INCH OUTSIDE SURFACE MESH AND 16X20 PER INCH INSIDE SURFACE MESH AND ASPEN AND REDWOOD FIBER FiLL. EACH FILTER CARTRIDGE SHALL HAVE WATER TROUGH WITH VISIBLE OUTSIDE ADJUSTMENT. ADJUSTABLE V-BELT DRIVE. MOTOR AND BLOWER WHEEL TO BE ISOLATED WITH RUBBER CUSHIONS. F.C. GALVANIZED STEEL, CEN TRiFUGAL BLOWER WHEEL WITH SELF ALIGNING PERMANENTLY LUBRICATED AND SEALED BALL BEARINGS. r HEAVY DUTY WATER RECIRCULATING PUMP AND MOTOR WITH PLASTIC SUC TION SCREEN, AND NECESSARY INTERNAL DISTRIBUTION PIPING. MAKE UP VALVE WITH ADJUSTABLE FLOAT ASSEMBLY. OVERFLOW PIPE TO EXTERIOR OF UNiT. GALVANIZED STEEL SUMP WITH WATERPROOF ASPHALTIC BASE UNDER COAT AND SEPARATE OVERFLOW AND DRAIN CONNECTIONS. CONTROLS: PROVIDE A 6 POSITION REMOTE WALL MOUNTED CONTROL SWITCH WHICH SHALL BE CAPABLE OF THE FOLLOWING POSITION; OFF, PUMP ONLY, HIGH COOL, LOW COOL, HIGH VENT, OR LOW VENT OPERATING FOR COOLING, VENTILATING OR PRE — WETTING OF THE PADS FROM A SINGLE SWITCH. PROVIDE A FiLL AND DRAIN KIT WHICH WILL AUTOMATICALLY DRAIN THE SUMP AND SUPPLY LINES WHEN THE OUTSIDE AIR TEMPERATURE DROPS BELOW 400F. THE KIT SHALL AUTOMATICALLY REFILL THE SUMP WHEN THE TEMPERATURE RISES ABOVE 550F. THE KiT SHALL INCLUDE A THREE —WAY WATER SUPPLY VALVE AND A TWO —WAY SUMP DRAIN DRIVE. PROVIDE A 12 OZ /YARD CANVAS COVER TO OWNER FOR WINTER USE. A. MAKE —UP AIR UNIT (MUA -1) B. 1. GENERAL A. RETURN AiR AND OUTSIDE AIR DAMPERS SHALL BE PROVIDED WITH THE FAN SYSTEM EQUIPMENT. B. THE OUTSIDE AIR DAMPER SHALL CLOSE AND THE RETURN AIR DAMPER SHALL OPEN WHENEVER THE SUPPLY FAN STOPS UNDER ANY CONDITIONS EXCEPT FROM FIRE CONTROLS. WHEN FIRE CONTROLS STOP THE FAN, ALL DAMPERS GO TO CLOSED, AND ALL FANS SHALL TURN OFF. C. THE HEATING COIL CONTROL VALVE SHALL BE POSITIONED TO FULL FLOW FROM HEAT SOURCE THROUGH COIL WHENEVER THE SUPPLY FAN GOES OFF. D. PROVIDE A FLOW SWITCH LOCATED IN THE COiL DISCHARGE PiPiNG SENSING WATER FLOW FROM THE HEATING COIL THAT SHALL SOUND AN ALARM AND TURN ON A RED WARNING LIGHT AT THE CONTROL PANEL AND STOP THE SUPPLY AIR FAN WHEN A NO FLOW CONDITION iS SENSED. PROVIDE AN ALARM SILENCER. LOCK OUT THIS ALARM AND THIS FAN INTERLOCK WHEN PUMP iS OFF FROM THE OUTSIDE AIR SENSOR WHICH NORMALLY CONTROLS THE OPERATION. A COIL AiR DISCHARGE FREEZE —STAT IS ALSO TO BE PROVIDED. WHEN A FREEZE CONDITION IS SENSED, ALL FANS SHALL BE OFF, AND THE HEATING WATER COIL SHALL DIVERT ALL FLOW THRU THE COIL. ALL OSA DAMPERS SHALL BE CLOSED. 2. CONTROL PANEL SHALL BE PROVIDED AND SHALL INCLUDE: A. OUTSIDE AIR TEMPERATURE SENSOR. B. A SEVEN DAY CLOCK WITH BACK —UP BATTERY. C. "DAY — NIGHT —AUTO" SWITCH D. PILOT LIGHTS FOR EACH OF THE FOLLOWING: 1) DAY 2) NIGHT 3 AUTO E. WITH THE SWITCH IN THE "DAY" POSITION, THE UNIT PROVIDES A NORMAL DAY CYCLE OPERATION AT ALL TiMES, 24 HOURS A DAY. THE DAY PILOT LIGHT WiLL BE ON. F. WHEN THE SWITCH IS IN THE "NIGHT" POSITION, THE NIGHT LIGHT WiLL BE ON CONTINUOUSLY, AND THE BUILDING WILL REMAIN ON NIGHT SETBACK, 24 HOURS A DAY. G. THE "AUTO" POSITION PROVIDES AUTOMATIC OPERATION WITH CHANGEOVER FROM NIGHT SETBACK TO DAY TEMPERATURES. iN THE AUTO POSITION, THE PILOT LIGHTS WILL INDICATE WHERE IN THE CYCLE THE UNiT IS OPERATION, AS FOLLOWS: (1) DAY CYCLE: THE DAY CYCLE IS TO START ONE HOUR BEFORE THE BUILDING iS OPEN TO ALLOW FOR WARM —UP OR COOL DOWN. THE SUPPLY FAN IS TO RUN CONTINUOUSLY. A ROOM THERMOSTAT WITH AUTOMATIC CHANGE- OVER FROM THE HEATING TO COOLING MODES AND A PANEL MOUNTED CONTROLLER SHALL MODULATE THE OUTSIDE AIR DAMPER TO ITS MINIMUM AND THE THREE WAY HEATING WATER COIL CONTROL VALVE TO MAINTAIN ROOM THERMOSTAT SETTING. IN THE COOLING MODE THE OUTSIDE AIR DAMPER SHALL MODULATE TO FULL OPEN. IF THE AIR TEMPERATURE iS ABOVE THE THERMOSTAT SETPOINT, THEN THE EVAPORATOR PUMP WILL CYCLE TO MAINTAIN ROOM THERMOSTAT SETTING. (2) NIGHT CYCLE: DURING THE "NIGHT CYCLE" THE SUPPLY AiR FAN SHALL BE OFF, THE OUTSIDE AIR DAMPERS SHALL BE CLOSED AND THE RETURN AiR DAMPER SHALL BE OPEN. THE HEATING COIL CONTROL VALVE SHALL BE POSITIONED FOR FULL FLOW FROM THE HEAT SOURCE THRU THE COIL A NIGHT THERMOSTAT SHALL CYCLE FAN TO MAINTAIN 657 MINIMUM TEMPERATURE, WITH O.A. DAMPER CLOSED, R.A. DAMPER OPEN. THE CONDENSING UNiT SHALL BE LOCKED OUT DURING THE NIGHT CYCLE. 3. BUILDING AUTOMATION SYSTEM INTERFACE (BAS) THE UNIT CONTROL PANEL SHALL BE TIED INTO THE EXISTING (BAS). THE BUILDING AUTOMATION SYSTEM (BAS) SHALL BE ABLE TO OVERRIDE THE AHU DISCHARGE AIR TEMPERATURE SETPOiNT. THE BAS SHALL ALSO BE ABLE TO OVERRIDE ROOM TEMPERATURE SET POINT, START —UP, OCCUPIED, MORNING WARM — UP HEATING, TIME OVERRIDE, STARTUP, COASTDOWN, NIGHT SETBACK, TiME SCHEDULES, AND PRIORITY SHUTDOWN COMMANDS. IF COMMUNICATION WITH THE BAS IS LOST, THE AHU SHALL USE ITS DEFAULT SETPOINT TO OPERATE IN THE OCCUPIED MODE AND AN ALARM WILL BE SENT TO THE BAS INDICATING A COMMUNICATION FAILURE RESULTING IN AN OPERATING MODE OVERRIDE. MAKE —UP AIR UNIT (MUA -2), EXHAUST FANS (EF -1 & EF -2) 1. GENERAL A. OUTSIDE AIR DAMPER SHALL BE PROVIDED WITH THE FAN SYSTEM EQUIPMENT. B. THE OUTSIDE AIR DAMPER SHALL CLOSE WHENEVER THE SUPPLY FAN STOPS UNDER ANY CONDITIONS, INCLUDING FIRE CONTROLS STOPPING THE FAN. C. THE HEATING COiL CONTROL VALVE SHALL BE POSITIONED TO FULL FLOW FROM HEAT SOURCE THROUGH COIL WHENEVER THE SUPPLY FAN GOES OFF. D. PROVIDE A FLOW SWITCH LOCATED IN THE COIL DISCHARGE PIPING SENSING WATER FLOW FROM THE HEATING COIL THAT SHALL SOUND AN ALARM AND TURN ON A RED WARNING LIGHT AT THE CONTROL PANEL AND STOP THE SUPPLY AIR FAN WHEN A NO FLOW COND111ON IS SENSED. PROVIDE AN ALARM SILENCER. LOCK OUT THIS ALARM AND THIS FAN INTERLOCK WHEN PUMP IS OFF FROM THE OUTSIDE AIR SENSOR WHICH NORMALLY CONTROLS THE OPERATION. A COiL AIR DISCHARGE FREEZE —STAT IS ALSO TO BE PROVIDED. WHEN A FREEZE CONDITION OCCURS, ALL FANS SHALL BE OFF, AND THE HEATING WATER VALVE SHALL DIVERT ALL FLOW THRU THE COIL 2. CONTROL PANEL SHALL BE PROVIDED AND SHALL INCLUDE: A. OUTSIDE AIR TEMPERATURE SENSOR. B. MANUAL ON /OFF SWITCH LOCATED IN THE KITCHEN. C. PILOT LIGHT INDICATING ON /OFF SWITCH POSITION (1) OFF SETTING: WHEN THE UNIT iS iN THE "OFF SETTING ", EF -1, EF -2, AND MUA -1 SHALL BE OFF. THE THREE —WAY HEATING WATER VALVE SHALL DIVERT FLOW TO THE COIL. A SPACE MOUNTED THERMOSTAT SHALL OVERRIDE THE MANUAL SWITCH SETTING WHEN THE SPACE TEMPERATURE DROPS BELOW 50'F(ADJ.). WHEN THE SWITCH IS OVERRIDDEN, THE SYSTEM SHALL ENTER THE "ON SETTING" UNTIL THE SPACE TEMPERATURE IS BROUGHT UP TO 70F(ADJ.). AT THiS TIME, THE SYSTEM OVERRIDE SHALL STOP, AND THE SYSTEM SHALL BE UNDER THE CONTROL OF THE MANUAL SWITCH. (2) ON SETTING: WHEN THE MANUAL SWITCH IS TURNED TO THE "ON SETTING ", EF -1, EF -2, AND MUA -1 SHALL ENERGIZE. THE OUTSIDE AIR DAMPER SHALL OPEN. THE THREE —WAY HEATING WATER VALVE AND EVAPORATIVE COOLER SHALL MODULATE IN SEQUENCE TO MAINTAIN A SUPPLY AIR TEMPERATURE OF 60F (ADJ.). WHEN THE MANUAL SWITCH IS TURNED TO THE "OFF SETTING ", EF -1, EF -2, AND MUA -1 SHALL DEENERGIZE, AND THE OUTSIDE AIR DAMPER SHALL CLOSE. 3. BUILDING AUTOMATION SYSTEM INTERFACE (BAS) THE UNIT CONTROL PANEL SHALL BE TiED INTO THE EXISTING (BAS). THE BUILDING AUTOMATION SYSTEM (BAS) SHALL BE ABLE TO OVERRIDE THE AHU DISCHARGE AIR TEMPERATURE SETPOINT. THE BAS SHALL ALSO BE ABLE TO OVERRIDE ROOM TEMPERATURE SET POINT, TIME OVERRIDE, STARTUP, COASTDOWN, TIME SCHEDULES, AND PRIORITY SHUTDOWN COMMANDS. IF COMMUNICATION WITH THE BAS IS LOST, THE AHU SHALL USE ITS DEFAULT SETPOINT TO OPERATE IN THE OCCUPIED MODE AND AN ALARM WILL BE SENT TO THE BAS INDICATING A COMMUNICATION FAILURE RESULTING IN AN OPERATING MODE OVERRIDE. 4. EVAPORATIVE COOLER DRAIN DOWN KIT z r 5 AUTOMATICALLY DRAIN THE SUMP AND SUPPLY LINES WHEN THE OUTSIDE AIR TEMPERATURE DROPS BELOW 40 F BELOW 400F. THE KIT SHALL AUTOMATICALLY REFILL THE SUMP WHEN THE TE&ERATURE RISES ABOVE 550F. THE KIT SHALL INCLUDE A THREE —WAY WATER SUPPLY VALVE AND A TWO —WAY SUMP DRAIN DRIVE. MECHANICALLEGEND NOTE: ALL SYMBOLS SHOWN ON LEGEND USE PATTERN ARE NOT NECESSARILY USED. AFF ABOVE FINISHED FLOOR REMARKS MANUFACTURER & MODEL NO. AFG ABOVE FINISHED GRADE ----- PUMP do EQUIPMENT CONNECTOR BFG BELOW FINISHED GRADE PIPE UNION BOP BOTTOM OF PIPE FROM FINISHED FLOOR y}4 DOUBLE CHECK BACKFLOW PREVENTER CFM CUBIC FEET PER MINUTE ® STEAM TRAP CLG CEILING CT -581 FT —FLOAT do THERMOSTATIC CONN CONNECT 0.80 TD— THERMODYNAMIC COTG CLEAN OUT TO GRADE 1 IB— INVERTED BUCKET ON DOWN — — PIPE ANCHOR (E) EXISTING --�— PIPE EXPANSION JOINT EAT ENTERING AiR TEMPERATURE 21 1W EXH EXHAUST —— FLEXIBLE CONNECTOR EWT ENTERING WATER TEMPERATURE 5,— -- SAFETY RELIEF VALVE FBO FURNISHED BY OWNER T AIR VENT LAT LEAVING AiR TEMPERATURE !]— PRESSURE —TEMP. TAP LWT LEAVING WATER TEMPERATURE NIC NOT iN CONTRACT PRESSURE GAUGE W/ PIG TAIL do COCK OBD OPPOSED BLADE VOLUME DAMPER THERMOMETER O.C. ON CENTER ® THERMOSTAT OSA OUTSIDE AiR — VACUUM BREAKER i,« TYPICAL 5800 5800 LINO UNLESS NOTED OTHERWISE 15" HORIZONTAL CLEANOUT — SMS — SNOWMELT SUPPLY ---lit VERTICAL CLEANOUT — SMR — SNOWMELT RETURN 12" 91 IREC FiLL FLOOR DRAIN — HWS — HEATING WATER SUPPLY ® FLOOR SINK — HWR — —CHS— HEATING WATER RETURN CHILLED WATER SUPPLY 12.3 ROOF DRAIN —CHR— CHILLED WATER RETURN (6)F/S FiRE /SMOKE DAMPER —RMS— RADIANT MANIFOLD SUPPLY FiRE DAMPER —RMR— RADIANT MANIFOLD RETURN (/ I& EXHAUST FAN ON ROOF W/ DUCT THRU ROOF. — CS — CONDENSER SUPPLY — CR _ CONDENSER RJR POINT OF DISCONNECTION — G — NATURAL GAS 9 ' POINT OF NEW CONNECTION — MG —' MEDIUM PRESSURE NATURAL GAS { FA AM I FIRE ALARM HORN /STROBE — D — — HPS — DRAIN PiPE t HIGH PRESSURE STEAM SUPPLY STRAINER W/ BLOW -OFF VALVE — HPR — — LPS — HIGH PRESSURE STEAM RETURN LOW PRESSURE STEAM SUPPLY SHOCK ABSORBER — LPR — LOW PRESSURE STEAM RETURN H�H — PC — PUMPED CONDENSATE HOSE BIBS f WALL HYDRANT — FOV — FUEL OIL VENT — FOF — FUEL OIL FiLL — GF — GLYCOL FEED FLOW SWITCH — RS — REFRIGERANT SUCTION — RL — REFRIGERANT LIQUID mm — RD — REFRIGERANT DISCHARGE SMOKE DETECTOR — - — DOMESTIC COLD WATER — RO — REVERSE OSMOSIS WATER — -- — DOMESTIC HOT WATER TEMPERATURE CONTROLLER -- -140'— DOMESTIC HOT WATER ( TEMP. SHOWN } -- HOT WATER CIRCULATING ® ACCESS PANEL — F — FIRE LINE SUPPLY DUCT DOWN —PW— PRESSURIZED WASTE JaSI REIURN/EXHAUST DUCT DOWN — V -____ — CV — PLUMBING VENT PIPE CHEMICAL VENT PIPE TURNING VANES SHOWN IN 90, ELBOW. —W— WASTE PIPE — GW — GREASE WASTE PIPE j, SINGLE BLADE DAMPER ( S.B.D. ), MOTORIZED — CW — CHEMICAL WASTE PIPE DAMPER, OPPOSED BLADE DAMPER ( O.B.D.. } S — SANITARY SEWER PIPE — ST — STORM DRAIN PIPE — ST(OF)— STORM DRAIN OVERFLOW PIPE — AIR EXTRACTOR — VAC — VACUUM PIPE t -----t DUCT SIZES ARE OUTSIDE SHEET METAL —CA— COMPRESSED AiR PIPE 24 2 DIMENSIONS. 1ST NO. IS SIZE OF SURFACE —MA— MEDICAL AIR PIPE SHOWN. 2ND NO. IS DUCT DEPTH. 0 — OXYGEN PIPE REGISTER N — NITROGEN PIPE —N20— NITROUS OXIDE PIPE —a::*— VENTURI/FLOW INDICAiER �� RETURN AIR OR EXHAUST AIR REGISTER. — —1T[— BUTTERFLY VALVE } pe}— SHUT OFF VALVE (BALL, GATE, BUTTERFLY) ��� �--� SUPPLY DIFFUSER; ARROWS INDICATE DIRECTION OF THROW. { — GLOBE VALVE --{� j— CHECK VALVE DOOR GRILLE ------ 0,4— FLOW CONTROL VALVE SECTION THRU SUPPLY AIR DUCT. SECTION THRU OUTSIDE AIR INTAKE, -- BALL VALVE RETURN AIR OR EXHAUST DUCT. -�— A2k PLUG OR BALANCING VALVE A�i (A) SECTION CUT LETTER. — CIRCUIT SETTER VALVE (S) SHEET SHOWN ON. — PLUG VALVE IN RISER i (( +- GATE OR GLOBE VALVE IN RISER CJ .. PLUMBING RISER �— DRAIN VALVE W/ HOSE END , -C> HEATING WATER; RISER — ' TEMPERATURE CONTROL VALVE CHILLED •WATER RISER: —{Q— PRESSURE REDUCING VALVE 0 , FiRE RISER,. , SOLENOID VALVE HVAC RISER GRILLE, REGISTER, DIFFUSER, & LOUVER SCHEDULE SYMBOL USE PATTERN ACCESSORIES FINISH MANUFACTURER &* MODEL N0. REMARKS MANUFACTURER & MODEL NO. SUPPLY SUPPLY FAN CFM CFM OSA E` !N W C. •L E ,SI�.P. W C. T FAN DIA. HEE CLASS R.P.M. MOTOR AIR CONDITIONS E ,AFT. W B T. ,�T TiTUS AIR CONDITIONS WATER CONDITIONS COIL 15' DEFL. OBD BY ARCH. T.L. W.T. �� DIFFUSER S , AT . PAD FtT. P D. IN. CT -581 RESTAURANT 5800 SUPPLY 0.80 0.75 15" FC 1 1120 5 LOUVERED OBD BY ARCH. �S — 90 DIFFUSER 180 160 21 1W 12.4 / RETURN 20$/3 2" THROW— TRANE EVAPORATIVE COOLER /SPRAY WASHER — AIREX SIZE 12 OR EQUAL 15* DEFL. OBD BY ARCH. GRILLE 350 RL FILL RELIEF LOUVERS & DAMPERS _ BAROMETRIC DAMPER BY ARCH. MCCB — UA -2 LOUVER 5800 5800 0.80 IF -31 15" * GRD EQUIVALENT: KRUEGER, METALLAIRE, HART & COOLEY, ANEMOSTAT AIR HANDLING UNIT SCHEDULE MARK AREA SERVED AIR DELIVERY CAPACITY j EVAPORATIVE COOLER HEATING COIL VfiS� FILTER MANUFACTURER & MODEL NO. REMARKS SUPPLY FAN CFM CFM OSA E` !N W C. •L E ,SI�.P. W C. T FAN DIA. HEE CLASS R.P.M. MOTOR AIR CONDITIONS E ,AFT. W B T. ,�T MBH TYPE AIR CONDITIONS WATER CONDITIONS COIL EFT. L ,AFT. MBH T.L. W.T. GPM PIPE S , AT . PAD FtT. P D. IN. MUA -1 RESTAURANT 5800 2200 0.80 0.75 15" FC 1 1120 5 82 60 63 12" 91 DIRECT 38 90 200 180 160 21 1W 12.4 1.3 0.1 20$/3 2" THROW— TRANE EVAPORATIVE COOLER /SPRAY WASHER — AIREX SIZE 12 OR EQUAL FILL AWAY MCCB PROVIDE FACTORY INSTALLED DRAIN —DOWN KIT UA -2 KITCHEN MAKE —UP 5800 5800 0.80 0.75 15" FC 1 1090 5 82 60 63 12" 91 IREC FiLL —19 80 460 180 160 50 21�i" 12.3 3 0.1 208 /3 2" THROW— AWAY TRANE MCCB EVAPORATIVE COOLER /SPRAY WASHER — AIREX SIZE 12 OR EQUAL PROVIDE FACTORY INSTALLED DRAIN —DOWN KIT *CARRIER, YORK EQUIVALENT BEAUDIN GANzE ro/ Consulting Engineers, tnc. ft 970) 90-MOS COPYRIaIT 2003 3q27&-3M0 7 582? 14 I I y STAJRS i El aiNc IN caum , EXISTING 28x16 GREASE AND 10x10 CONDENSATE EXHAUST UP TO REMAIN. -- _�DISCONNECT DUCT AND CAP ND If I I REF, T ,rr ,n4u F PARTIAL ii' DEMOLITION PLa SCALE; 1/8" = V -0" IN SCALE; 1/8" = 1'--0" F DEMO ALL EXISTING FANS, DUCTWORK, AND MECHANICAL EQUIPMENT IN THIS AREA, U.N.O. DISCONNECT DUCT AS SHOWN. CAP EXISTING TAKE -OFF ON 28x28 DUCT. EXISTING DUCT AND DIFFUSERS TO EXISTING DUCT AND DIFFUSERS TO REMAIN EXISTING DUCTS UNDERGROUND AND CONTINUED UP INTO SHAFT. EXISTING 20 "0 DUCT UP �--° -DECK ASS' XISTING 26 "0 DUCT UP E \XI�MNG 20 "0 DUCT UNDER FLOOR XlST1N ��ING TO REMAIN XI 4 DUCT UNDER FLOOR i CT TO REMAIN ,EXISTING 18 "0 RUNOUT UNDER FLOOR EXISTING 18 "0 DUCT STUBBED UP AT CEILING OF FLOOR BELOW PARTIAL UPPER LEVEL HEALTH CLUB DEMOLITION PLAN SCALE; 1/8" = 1 0 " NOTES: 1. ALL DUCTWORK, DIFFUSERS, ETC. SHOWN AS LIGHT LINE WEIGHT IS EXISTING TO REMAIN U.N.O. 2. ALL DUCTWORK, DIFFUSERS, ETC. SHOWN AS LIGHT LINE WEIGHT AND IS HATCHED IS TO BE REMOVED. 3. ALL DUCTWORK IN CHASES SHOWN AS DEMOED MAY BE ABANDONED IF NECESSARY. IF DUCTS ARE ABANDONED, CAP AS REQUIRED. 4. ALL ELECTRIC DUCT COILS IN THE KITCHEN AREA ARE TO BE REMOVED. BEAUDIN GANZE ConsWUng &&eers, Inc. ro/ lake ?9ah 0530) X55.4 -7334 CWYRK;FiT 2003 Oenver: (303)278 -3820 582214 0 z o F US cl) x w EXISTING TRANSFER GRILLE TO REMAIN i i L NEW 18x12 DUCT ROUTED --- IN JOIST SPACE. SEE ARCH DRAWINGS FOR FIRE RATINGS AND DETAILS. DIFFUSERS OUT OF BOTTOM OF DUCT. 2 PARTIAL FIRST FLOOR MECHANICAL PLAN SCALE: 1/8" — l'—O" 1z 13 — RA GRILLES LOCATED AT TOP OF 32x10 RA SHAFT BAROMETRIC RELIEF DAMPER LOCATED HIGH ON WALL. PROVIDE TYPE "C" RETURN GRILLE ON INTERIOR SIDE OF LOUVER. GRILLE TO BE SAME SIZE AS LOUVER. MATCH EXISTING DUCT SIZE. 36x12 SA DN IN SHAFT. F/S DAMPER AT FLOOR PENETRATION, TYP. NEW 18x12 DUCT ROUTED IN WRAPPED JOIST SPACE. SEE ARCH DRAWINGS FOR FIRE RATINGS AND DETAILS. DIFFUSERS OUT OF BOTTOM OF DUCT. 18x12 MUA DUCT DN. TRANSITION TO 18x12 SHOWN. CONNECT NEW 18x12 DUCT TO EXISTING 36xi O SA ON. EXISTING 36x1O SA DN TO REMAIN. EXISTING 34x12 RA DN TO REMAIN. COIL. —� AIR VENT.---- - SUPPLY. NOTE; PIPE COIL FOR COUNTERFLOW. ZONE HEATING COIL ASS Y DIAGRAM NO SCALE 0 I1 fTl 3Ox24 DUCT ROUTED BELOW STRUCTURAL BEAM. EXISTING DUCT AND-------- DIFFUSERS TO REMAIN 2SAU ?O SAL I UNFINISHED — SPACE EtEv, LOBBY E�ll EQUIP, ago i — ---(D 36x12 SA UP — XISTING 2riz "HWS /HWR AND NEW 1 "CW DN UNDER DUCT AND DN TO MAKE —UP AIR UNIT. CONNECT TO HEATING COIL AND EVAPORATIVE COOLER PUMP SUPPLIED BY MANUFACTURER. f El ROOM; n Q�' +0 6 zao TRANSITION EXISTING 18 "0 30x6 RA DUCT UP / `L RA DUCT TO 26x16. ROUTE WITH BALANCE DAMPER __,_,__.__ 26x16 DUCT IN CEILING OF SPACE IN VERTICAL. BELOW. TYP. EW 26x16 DUCT ROUTED IN HORIZONTAL RATED ASSEMBLY IN CEILING SPACE OF FLOOR BELOW. PARTIAL UPPER LEVEL HEALTH CLUB MECHANICAL PLAN SCALE- 1/8" = 1 -0 B EAUDIN GANZE vo/ Consulting Engineers, Inc. Vol: 970) 90—MOS rop"RIGFrr 90m Lois � 381Q 7334 582214 ;.,. ia+c fJ�fJJ1rn N$i'4,. PAU 11 I NvAs.1 DATE I COMMENT I KEY PLAN r SHEET NiMs. M3*0 1. DRAWINGS MAY NOT REFLECT EXISTING CONDITIONS. CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO START OF WORK. 2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK. 3. EXAMINATION OF BIDDING DOCUMENTS. A. EACH BIDDER SHALL EXAMINE THE BIDDING DOCUMENTS CAREFULLY, AND NOT LATER THAN SEVEN DAYS PRIOR TO THE DATE OF RECEIPT OF BIDS, SHALL MAKE WRITTEN REQUEST TO THE ARCHITECT FOR INTERPRETATION OR CORRECTION OF ANY DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS THEREIN WHICH HE MAY DISCOVER. THE ARCHITECT WILL BE ISSUE ANY INTERPRETATION OR CORRECTION AS AN ADDENDUM. ONLY A WRITTEN INTERPRETATION OR CORRECTION BY ADDENDUM SHALL BE BINDING. NO BIDDER SHALL RELY UPON INTERPRETATIONS OR CORRECTIONS GIVEN BY ANY OTHER METHOD. IF DISCREPANCIES, AMBIGUITIES, INCONSISTENCIES, OR ERRORS ARE NOT COVERED BY ADDENDUM OR WRITTEN DIRECTIVE, CONTRACTOR SHALL INCLUDE IN HIS BID, LABOR MATERIALS AND METHODS OF CONSTRUCTION RESULTING IN HIGHER COST. AFTER AWARD OF CONTRACT, NO ALLOWANCE OR EXTRA COMPENSATION WILL BE MADE ON BEHALF OF THE CONTRACTOR DUE TO HIS FAILURE TO MAKE THE WRITTEN REQUESTS AS DESCRIBED ABOVE. B. FAILURE TO REQUEST CLARIFICATION DURING THE BID PERIOD OF ANY INADEQUACY, OMISSION, OR CONFLICT WILL NOT RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES. THE SIGNING OF THE CONTRACT WILL BE CONSIDERED AS IMPLICITLY DENOTING THAT THE CONTRACTOR HAS A THOROUGH COMPREHENSION OF THE FULL INTENT AND SCOPE OF THE WORKING DRAWINGS AND SPECIFICATIONS. 4. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE iN HIS BID COSTS REQUIRED TO MAKE HIS WORK MEET EXISTING CONDITIONS. 5. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK WHICH COULD RESULT iN AN ACCIDENTAL OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK. 6. REVIEW ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND OTHER DRAWINGS PRIOR TO BID. 7. WORK SHALL BE PERFORMED iN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT. 8. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE OF COLORADO, AND NATIONAL CODES AND ORDINANCES: 9. PROVIDE PERMITS AND INSPECTIONS REQUIRED. 10. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER. 11. PROVIDE RECORD DRAWINGS TO ARCHITECT. DRAWINGS SHALL INCLUDE ALL ADDENDUM ITEMS, CHANGE ORDERS, ALTERATIONS, REROUTiNGS, ETC. 12. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE CONNECTED AND OPERABLE. 13. PROVIDE ENGRAVED NAMEPLATES ON SWITCHBOARDS, PANELBOARDS, DISCONNECT SWITCHES, MOTOR CONTROL CENTERS, TRANSFORMERS, ETC., INDICATING EQUIPMENT DESIGNATION (OR DESIGNATION OF EQUIPMENT SERVED), AND VOLTAGE. 14. PANEL DIRECTORIES SHALL BE REMOVABLE. SUBMIT PROPOSED SCHEDULE OF DIRECTORIES TO OWNER FOR APPROVAL. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED AND INSTALLED UNDER CLEAR PLASTIC COVERS. 15. PROVIDE DYMO -TAPE TAG INSIDE COVER OF EACH FUSIBLE SWITCH, INDICATING SIZE AND TYPE OF FUSES PROVIDED. 16. PRESENT SHOP DRAWING SUBMITTAL DATA AT ONE TIME, BOUND IN THREE -RING BINDERS, INDEXED IN A NEAT AND ORDERLY MANNER. PARTIAL SUBMITTALS WILL NOT BE ACCEPTED. SUBMITTALS SHALL INCLUDE, BUT NOT BE LIMITED TO WIRING DEVICES, SAFETY SWITCHES, ELECTRICAL SPECIFICATIONS. FUSES, MOTOR STARTERS, CONDUIT, AND CONDUIT FITTINGS. 17. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND /OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS. 18. PROVIDE ELECTRICAL DEMOL111ON REQUIRED. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOL111ON REQUIRED. CONTRACTOR SHALL ViSIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED. PROVIDE LABOR AND MATERIALS AS REQUIRED TO MAINTAIN AND /OR RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS. 19. FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT ARE REMAINING TO BE RECONNECTED TO NEW OR EXISTING SWITCHBOARDS/ PANELBOARDS. PROVIDE SWITCHES, RECEPTACLES, CONDUIT, WIRE, ETC. AS REQUIRED TO RESTORE CONTINUITY OF CIRCUIT(S). 20. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED CONDUIT, WIRE, CABLE, J- BOXES, RECEPTACLES, SWITCHES, LIGHTS, FIRE ALARM DEVICES, ETC. COMPLETE WITH ASSOCIATED CIRCUITING TO SOURCE. WHERE IT IS NOT FEASIBLE TO REMOVE THE ABOVE, OUTLET SHALL BE ABANDONED, WIRE REMOVED, AND BLANK COVER PLATES PROVIDED. 21. EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOR EXISTING BUILDINGS ARE TO BE NOTED "FOR GUIDANCE ONLY". THE ELECTRICAL CONTRACTOR TO FIELD CHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND TO INCLUDE IN HIS BID AN ALLOWANCE FOR REMOVAL AND /OR RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHER WORK AS REQUIRED. 22. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS, CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE SUBJECT TO OWNER APPROVAL. 23. IMMEDIATELY AFTER AWARD OF CONTRACT, VERIFY AVAILABLE PHYSICAL SPACE AND AMPACITY OF EXISTING PANELBOARDS, SWITCHBOARDS, DISTRIBUTION BOARDS, MOTOR CONTROL CENTERS, ETC., AND PROVIDE WRITTEN DOCUMENTATION OF FINDINGS TO THE ARCHITECT /ENGINEER. DOCUMENTATION SHALL INCLUDE A MINIMUM 24- HOUR RECORDING AMPERE READING ON ALL EXISTING SWITCHGEAR BEING UTILIZED FOR THIS PROJECT. 24. REVIEW ARCHITECTURAL., STRUCTURAL, AND MECHANICAL DRAWINGS AND PROVIDE LiGHTS,' SWITCHES, RECEPTACLES, TELEPHONE OUTLETS, EQUIPMENT CONNECTIONS, ETC. AND ASSOCIATED CIRCUITING IN NEW AND REMODELED AREAS, EVEN iF SUCH AREAS ARE NOT SHOWN ON ELECTRICAL DRAWINGS. LAYOUTS, FIXTURE TYPES, QUANTITIES, AND SPACINGS SHALL BE IN ACCORDANCE WITH SIMILAR AREAS ON THIS PROJECT. CONTRACTOR SHALL INCLUDE COSTS FOR THE ABOVE IN HIS BID. IN ADDITION, CONTRACTOR SHALL PROVIDE LAYOUT DRAWINGS FOR WORK IN SUCH AREAS AND SUBMIT FOR APPROVAL PRIOR TO ROUGH -IN. 25. EXISTING LIGHT FIXTURES, SWITCHGEAR, ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BE RETURNED TO THE OWNER, EXCEPT FOR THOSE ITEMS BEING RELOCATED. 26. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT. 27. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH -IN. 28. FiNAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED. 29. ELECTRICAL CONTRACTOR SHALL PROVIDE CONTROLS, INTERLOCKS, ACCESSORIES, ETC. IN MOTOR CONTROL STARTERS AS REQUIRED BY THE TEMPERATURE CONTROL CONTRACTOR. STARTERS SHALL CONTAIN 120V CONTROL TRANSFORMER, PILOT LIGHT, AND PUSHBUTTONS OR SELECTOR SWITCH AS REQUIRED, IN ADDITION TO OTHER ITEMS (AUXILIARY CONTACTS, DOOR SWITCHES, RELAYS, ETC.) REQUIRED. SUBMIT ELEMENTARY CONTROL DIAGRAMS. 30. INSTALL ALL MATERIALS IN ACCORDANCE WiTH THE MANUFACTURER'S EXISTING 120V CIRCUIT EXISTING WIRING TO BUILDING FIRE ALARM SYSTEM EXISTING FiRE -- EXTENGUISHING SYSTEM CONTROL PANEL CONNECT 120V GAS----- VALVE(S) AND RESET RELAY. COORDINATE WITH FIRE EXTINGUISHING SYSTEM CONTRACTOR. RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE ARCHITECT /ENGINEER'S ATTENTION PRIOR TO INSTALLATION. 31. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST TO OWNER. 32. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERAL USE. FOR HID FIXTURES AND WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZES INDICATED ARE FOR INSTALLATION iN A MAXIMUM 30 DEGREE CELSIUS AMBIENT. CONDUCTOR AMPACiTY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS. 600 VOLT ALUMINUM WiRE AND CABLE IN SIZES 1/0 AND LARGER MAY BE SUBSTITUTED FOR COPPER ON SERVICES AND FEEDERS IF AMPACITY IS EQUAL TO OR GREATER THAN COPPER, AND VOLTAGE DROP iS EQUAL TO OR LESS THAN COPPER AND SHALL BE TERMINATED AT SWITCHES, LUGS, CIRCUIT BREAKERS, ETC., WITH MAC - ADAPT SERIES "MPT" MACHINE COMPRESSION ADAPTERS OR EQUAL. 33. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR FACTORY WIRING iN EQUIPMENT PROVIDED UNDER THIS SECTION. 34. CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT. 35. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY. 36. WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS SUITABLE FOR 75 DEGREE CELSIUS. 37. PULLBOXES, CABINETS, ETC. MOUNTED ON THE EXTERIOR AT GRADE LEVEL, SHALL BE WEATHERPROOF TYPE WITH HINGED LOCKABLE COVERS SECURED WITH TAMPERPROOF SCREWS. 38. SEE DIVISION 15 DRAWINGS FOR LOCATION OF MECHANICAL EQUIPMENT. PROVIDE SERVICE TO, AND CONNECT EQUIPMENT AS REQUIRED. 39. DISCONNECT SWITCHES AND MOTOR CONTROL CENTERS SHALL MATCH EXISTING. 40. DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE. FUSIBLE SWITCHES SHALL ACCEPT CLASS 'R' FUSES ONLY, AND REJECT ALL OTHERS. 41. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE AND FUSES SHALL BE BUSSMANN. 42. ALL WIRING SHALL BE INSTALLED iN LISTED METALLIC RACEWAYS. RACEWAYS IN SLAB -ON -GRADE OR BELOW GRADE SHALL BE SCHEDULE 40 PVC. TRANSITIONS FROM BELOW TO ABOVE GRADE SHALL BE WITH RiGiD STEEL ELBOWS WiTH P.V.C. JACKET OR APPROVED EQUAL PROTECTION. EMT FITTINGS SHALL BE MALLEABLE IRON OR STEEL. CONNECTORS SHALL BE INSULATED THROAT TYPE. 43. NON- METALLIC AND FLEXIBLE METAL CONDUITS SHALL HAVE A CODE - SIZED COPPER GROUNDING CONDUCTOR. INCREASE CONDUIT SIZE AS REQUIRED. 44. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT SHALL BE WITH SEAL TITE FLEX AND APPROVED FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT. 45. FIRE ALARM SYSTEM. PROVIDE DEVICES, CONDUIT, WIRES, AND CABLE AS DIRECTED BY EQUIPMENT MANUFACTURER TO EXTEND EXISTING FIRE ALARM SYSTEM TO REMODELED AREAS. THE CONTRACTOR SHALL EXTEND WARRANTY FOR ALL PROGRAMMABLE CONTROLLERS UP TO MARCH 31, 2000 AND PAY FOR ALL DAMAGES CAUSED BY NON - COMPATIBLE CONTROLLERS. MATERIALS, EQUIPMENT, AND WORKMANSHIP SHALL MEET PREVAILING CODES. THE SYSTEM SHALL BE COMPLETE AND OPERABLE IN EVERY RESPECT. SUBMIT SINGLE LINE OF SYSTEM WITH SHOP DRAWINGS. THIS SINGLE LINE DIAGRAM SHALL SHOW DEVICES, CONDUIT, WIRE, AND CABLE SIZES, EQUIPMENT TO BE USED, AND SHALL BE STAMPED AND SIGNED BY LOCAL FIRE DEPARTMENT. SYSTEM CALIBRATION AND TESTING SHALL BE BY FACTORY CERTIFIED TECHNICIAN. NEW CIRCUITING TO TO 120V SHUNT TRIP BREAKERS. SEE PANEL SCHEDULE KITCHEN FIRE EXTINGUISHING SYSTEM CONTROL DIAGRAM NO SCALE NOTE: OPERATION OF EXTINGUISHING SYSTEM SHALL BE: 1. CLOSE GAS VALVES SERVING FUEL TO ALL GAS FIRED EQUIPMENT LOCATED UNDER COOKING EXHAUST HOODS. 2. TRIP ALL CIRCUIT BREAKERS SERVING POWER TO ALL ELECTRIC COOKING EQUIPMENT LOCATED UNDER COOKING EXHAUST HOODS. 3. STOP EXHAAST AND MAKE -UP AIR FANS WITH SHUNT TRIP. ELECTRICAL LEGEND AQ INCAN. OR HID FIXTURE W/ FIXTURE DESIGNATION Aa WALL MOUNTED LIGHT FIXTURE W/ FIXTURE DESIGNATION A® 2x4 FLUORESCENT LIGHT FIXTURE W/ FIXTURE DESIGNATION A 1x4 FLUORESCENT LIGHT FIXTURE W/ FIXTURE DESIGNATION FIXTURE ON NIGHT LIGHT OR EMER. CIRCUIT FLUORESCENT STRIP FIXTURE TRACK LIGHT AS NOTED OR SCHEDULED DIRECTIONAL ACCENT OR WALL -WASH FIXTURE 0-.0 POLE -MTD. FIXTURE 0 POST (BOLLARD) FIXTURE 0 61 NANLGFADTBT ISTACES S INDICATED BY SHADING 4=I> EMERGENCY BATTERY LIGHTS & DUPLEX RECEPTACLE AT 18" UNLESS NOTED CCU DUPLEX RECEPTACLE ABOVE COUNTER C- DOUBLE DUPLEX RECEPT. AT 18' UNLESS NOTED Q FLUSH FLOOR DUPLEX RECEPT. } FLUSH FLOOR DUPLEX RECEPT. HALF - SWITCHED SPECIAL OUTLET AS NOTED ( GFI DUPLEX RECEPTACLE AT 42" UNLESS NOTED DUPLEX RECEPT. HALF - SWITCHED AT 18' UNLESS NOTED iG RECEPTACLE 0 TELE -POWER POLE �} CLOCK OUTLET ccc MULTi- OUTLET PLUG STRIP 0 Q (2)4 JUNCTION BOX IN FLOOR, CEILING, OR IN WALL V ® TELEPHONE OUTLET IN WALL OR IN FLOOR 13 D COMPUTER OUTLET IN FLOOR OR WALL COMBINATION OATA/TELEPHONE OUTLET CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING CIRCUIT HOMERUN, 112 THWN, QTY AS REVD, W/ GROUND. 1/2 -C -- -- CONDUIT RUN BELOW FLOOR OR GRADE CONDUIT RUN EXPOSED EXISTING CONDUIT TO BE REMOVED 1/2 " -#12 THWN, W /GROUND QTY AS REVD W /GROUND o CONDUIT UP -. CONDUIT DOWN Ig SEALOFF �g CONDUIT STUB -OUT - CAP & MARK S LIGHT SWITCH AT 48" UNLESS NOTED SUBSCRIPTS: 3 = 3-WAY SNITCH 4 = 4-WAY SWITCH K = KEY - OPERATED SWATCH T = THERMAL OVERLOAD SWITCH P = SNATCH WITH PILOT LIGHT J = SWATCH IN DOOR JAMB NOT = VARIABLE SPEED SWATCH a - LOWER CASE LETTER AT FIXTURES AND SWITCHES (a. b. ETC.) INDICATES SWITCHING CtNITROL. jM DIMMER SWITCH ® MAGNETiC MOTOR STARTER ® MAGNETIC CONTACTOR Ey FUSED DISCONNECT SWITCH - 30 AMP UNLESS NOTED NON FUSED DISCONNECT SWITCH - 30 AMP UNLESS NOTED ®r COMBINATION DISCONNECT AND STARTER G PANELBOARD OR LOAD CENTER ® SWITCHBOARD. MOTOR CONTROL CENTER OR DISTRIBUTION BOARD TRANSFORMER GROUND p SPECIAL CABINET OR ECKAP. AS NOTED © PUSHBUTTON CONTROL STATION ® PHOTOELECTRIC CELL ® TiME SWITCH ® THERMOSTAT AT 60" UNLESS NOTED 8 DIVISION 15 EQUIPMENT ® CIRCUIT BREAKER MOTOR OUTLET AUTOMATIC TRANSFER SWITCH p PULL BOX O EQUIPMENT SINGLE LINE DIAGRAM SYMBOLS `*.- DISCONNECT SWITCH H -®- FUSES -�- CIRCUIT BREAKER CURRENT TRANSFORMER POTENTIAL TRANSFORMER METER ® SURGE SUPPRESSION DEVICE (� COLD WATER GROUND BUILDING STEEL GROUND GROUND FAULT PROTECTION SHUNT TRIP KIRK KEY SWITCH NOT£: LIGHT LINEWWEIGHT INDICATES EXISTING. INDICATES DEMOLITION. NOTE: ALL SYMBOLS SHOWN ON LEGEND ARE NOT NECESSARILY USED. 888REVIA'fEONS AFC -ABOVE FINISHED CEILING AFF - ABOVE FINISHED FLOOR AFG - ABOVE FINISHED GRADE AL - ALUMINUM BFG - BELOW FINISHED GRADE C - CONDUIT ONLY CKT - CIRCUIT CT - CURRENT TRANSFORMER EM - EMERGENCY EWC - ELECTRIC WATER COOLER (E) - EXISTING FBO - FURNISHED BY OWNER F/S - FiRE /SMOKE DAMPER GRD - GROUND GFI - GROUND FAULT INTERRUPTER IAW - IN ACCORDANCE WITH IG - ISOLATED GROUND NiC - NOT IN CONTRACT NIES - NOT IN ELECTRICAL SECTION NL -NIGHT LIGHT NTS - NOT TO SCALE STO - THERMAL OVERLOAD SWITCH TT - TELEPHONE TERMINAL TVSS- TRANSIENT VOLTAGE SURGE SUPPRESSOR UG - UNDERGROUND UNO - UNLESS NOTED OTHERWISE WP - WEATHER PROOF TX - TRANSFORMER XP - EXPLOSION PROOF +18" - MOUNTING HEIGHT TO CENTERLINE OF DEVICE AFF OR AFG FIRE ALARM SYSTEM ® FIRE ALARM CONTROL PANEL rA-M-1 FIRE ALARM ANNUNCIATOR PANEL Q MANUAL PULL STATION ti GENERAL ALARM HORN GENERAL ALARM COMBINATION HORN /STROBE (Sp FIRE ALARM SPEAKER COMBINATION FIRE ALARM SPEAKER /STROBE Qq FIRE ALARM STROBE 0 FIRE ALARM CHIME FA-5-1 THERMAL HEAT DETECTOR ® SMOKE/IONIZATION DETECTOR ® SMOKE/HEAT DETECTOR ® DUCT DETECTOR Q SPRINKLER SYSTEM FLOW SWITCH FF-r-1 SPRINKLER SYSTEM TAMPER SWITCH ® REMOTE TEST SNATCH FN FiREMANS PHONE (� INDICATOR LIGHT MECHANICAL EQUIPMENT SCHEDULE MARK DESCRIPTION VOLTAGE /PHASE HP /WATTS FLA MCA DISCONNECT FEEDER CiRCUIT REMARKS MUA -1 MAKE -UP AIR UNIT 208/3 5 HP 17.5 - 30A 3P 3 #10 & #10GND, 3/4 "C W- 13,15,17 2 MUA -2 MAKE -UP AIR UNIT 208/3 5 HP 17.5 - 30A 3P 3 #10 & #10GND, 3/4 "C W- 32,34,36 2 EP -1 EVAPORATIVE COOLER PUMP 120/1 1/4 HP 5.8 - 30A 1P 2 #12 & #12GND, 3/4 "C W -29 EP -2 EVAPORATIVE PUMP COOLER 120/1 1/4 HP 5.8 - 30A 1 P 2 #12 & #12GND, 3/4 "C W -30 + SHUNT TRIP (NEW) 2 E - 1 1200 1 4 5 ELEVATOR CAB LIGHTS 1 7450 M 7Z M IV V I tJ: 1. FIELD COORDINATE AND PROVIDE CONTROL WIRING. 2. MAKE CONNECTION TO DUCT DETECTOR. DUCT DETECTOR TO BE SUPPLIED BY MECHANICAL CONTRATOR AND WIRED BY ELECTRICAL CONTRACTOR. PROVIDE REMOTE INDICATOR LIGHT iN LOCATION APPROVED BY LOCAL AHJ. PANEL W 208 Y/ 120 VOLT 3PH 4 WIRE 400 AMPERE MAIN LO 400 AMPERE BUS LOCATION MECHANICAL ROOM 209 MOUNTING: SURFACE A.I.G. 10,000 E- Sul x= V Z LINE A LINE B LINE C CIRCUIT TYPE L/1R/M LM A S LOAD DESCRIPTION CiRCUiT BREAKER BUS CIRCUIT BREAKER CIRCUIT TYPE LOAD DESCRIPTION LOAD tr h Z CJ POLE TRIP A I B I C TRIP POLE L/R/m LM A S LINE A LINE B LINE C 1 SHUNT TRIP + 20 E SHAW OFFICE 1200 2 3 - 7450 35 M ELEVATOR 3 + SHUNT TRIP (NEW) 2 E - 1 1200 1 4 5 ELEVATOR CAB LIGHTS 1 7450 M 7Z M + 20 E SHAW OFFICE 21 1200 6 7 7450 1 20 M + 100 + M - 2 E - 1200 8 9 ELEVATOR CONTROLS 583 20 M SNOWMELT PUMP 2 v, 3 + - 20 1 E FIRE DAMPERS (NEW) 25 1200 10 11 TIME CLOCK 1 583 M - 20 1 L + 20 1 M EF -2 27 696 12 13 2102 M MUA -1 NEW 3 + 20 SPARE 14 15 2102 M + 2 16 17 2102 M - 35 + SHUNT TRIP (NEW) 18 19 1000 1 L ELEVATOR CAB LIGHTS 1 20 + 20 M EF -1 1321 20 21 1000 E ELEVATOR PIT 1 20 + M - 1321 22 23 1000 E ELEVATOR CONTROLS 1 20 + v, 3 M - 1321 24 25 300 E TIME CLOCK 1 20 + 20 1 L LOWER TEMP 1800 26 27 600 M UNIT HEATER 1 20 + 20 1 L LOWER TEMP 1800 28 29 696 M EVAP PUMP (NEW) 1 20 + SHUNT TRIP (NEW 30 31 SPARE 2 + 35 M MUA -2 NEW 2102 32 33 30 + M - 2102 34 35 957 M TEMP AIR HANDLER 2 +IZ 3 M 2102 36 37 957 M 30 + 20 1 M EVAP PUMP NEW) 696 38 39 957 M TEMP AIR HANDLER 2 +1 1 SPARE 40 41 957 M - 30 + SPARE 42 11809 112692 11,3745J SUB TOTALS 8319 71 5319 CIRCUIT TYPE L= LIGHTING, R= RECEPTACLE, M= MOTOR, LM= LARGEST MOTOR DESCRIPTION. E =EQUIPMENT, A= APPLIANCE, S= SUBFEED PANEL LiNE TOTALS NEC ADDER FEED THRU LOAD TOTAL VA /PH LINE AMPS TOTAL KVA LOAD FEEDER AMPS 18128 20315 19064 700 450 0 NOTES: ALL CIRCUITS ARE EXISTING UNLESS NOTED (NEW). NEW BREAKERS SHALL MATCH EXISTING AIC RATING, MANUFACTURER, AND TYPE. NEW BREAKERS FOR MUA -1 AND EF -1 SHALL HAVE SHUNT TRIP AS SHOWN. ALL BREAKERS ARE EXISTING EXCEPT NEW BREAKERS FOR AHU -1, MUA -1, AND EF -1. 18828 20765 19064 160 173 159 58.7 163 i i I ,R PROVIDED ,L CONTRACTOR ;TRICAL CONTRACTOR Uqm'�� mall r � r r li 11 � m r L. SCALE; 1/8" = 1' -0" NOTES: 1. REFER TO MECHANICAL EQUIPMENT SCHEDULE ON SHEET M1.0 FOR CIRCUITING, CONDUIT, FEEDER SIZES, ETC. 2. COORDINATE EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL DRAWINGS. 3. ALL ELECTRICAL LOADS BEING DEMOED SHALL BE DEMOED BACK TO SERVING ELECTRICAL PANEL. 4. ALL EXISTING LIGHTING SHALL REMAIN. CONTRACTOR TO COORDINATE WITH MECHANICAL CONTRACTOR ANY RELOCATION OF EXISTING LIGHTING FIXTURES. 5. REFER TO MECHANICAL DRAWINGS FOR FIRE DAMPER LOCATIONS. 9 V \ ' AIII 1 i3 PARTIAL ! ' FLOOR , ! ! ' • I SCALE: 1 /8" = 1' -0" 1� jf i i 1' Eby i� I �I Pl ,...,..� DEMO ALL EXISTING POWER CONNECTIONS TO ALL EQUIPMENT, LIGHTING, ETC. IN THIS AREA BEAUDIN DARE vo/ ConsWting Engineers, Inc. >ot s70} see -6108 taioa a�wr 530} 550-7334 r 2003 Oenver (303}278 -3820