Description
The architecture of an IPF SeriesT"' fire control network is comprised of a
series of IP-based distributable modules.These modules include Features
alternate configurations of analog loop and NAC circuit modules(ALM-
xy), standard display modules (SDM), annunciator control modules . Provides power for all IPF Series
(ACM)and other specialized modules noted in other documents. modules, routers and connected
With distributed systems, power requirements can be varied according to devices
system layout. With IP Fire SeriesT"" controls, power can be centrally • Provides battery and brown out
supervision
located and then distributed from the central location to remote system Switching 8A Power Supply unit
modules or power can be supplied along with the remote system • mounts in IPF pre-configured or
modules. remote cabinets
• Switching 4A Battery Charging
The Power Supply(PS-24) provides 24V/8A of system power. Power is unit mounts in IPF pre-configured
available for all modules, switches/routers and attached devices. or remote cabinets
• Supervised and Controlled by the
Battery charging is accomplished by the Auxiliary Power Supply(APS-4) power Supply Monitor(PSM)
which provides 24V/4A of battery charging power. The APS-4 is capable . Charges 70Ah Batteries
of charging 70Ah batteries. . IPF-XL can accommodate multiple
power supplies with a total of 12A
The Power Supply Monitor(PSM)supervises the power supply, battery of available power and an
charger and provides for internal/external distribution of power throughout additional 8A of dedicated battery
the system.The PSM also monitors for brownout conditions, low/no charging capacity
batteries and other electrical monitoring functions established by UL • Maximum number on an individual
864/9�h edition. system: unlimited
• Internal and power-limited external
Multiple instances of the PS-24,APS-4 and PSM may be installed power taps
through an IP Fire SeriesT"" control system as required. There is no • Green/RoHS Compliant
system limitation on the amount of power that can be distributed.
Special remote cabinetry to accommodate the PS-24,APS-4, PSM and
batteries is available when installing power with remote system modules. Listinqs
See DS 1045 IPF SeriesT"" Distributed System Cabinet Options for more
information. UL File: S24573
CSFM: Pending
Like all IP Fire SeriesT"" modules,the PS-24, APS-4 and PSM are MEA: Pending
compliant with the Restrictions on Hazardous Substance Directive
(RoHS)and are free of many of the toxins normally associated with the
electronic manufacturing process: Lead, Mercury, Cadmium, Hexavalent
Chromium, Polybrominated Biphenyls and Polybrominated Diphenyl
Ether.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"" PSM, PS-24,APS-4 1040 1.3/5/1/2009 IPFIRESERIES"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install, where indicated on the plans, integral power supply and battery charger
modules for local and distributed IPF Series fire system modules. The power supply, battery charger and monitor
card shall be fully supervised and shall monitor for the presence of AC power as well as battery power and also
monitor for low/no battery and brown out conditions.The battery charger shall be capable of charging 70 AH batteries
The power supply, battery charger and power supply monitor must be UL listed and UL listed as compatible with the
AsBuilt IPF and REM Series fire controls. The power supply, battery charger and power supply monitor modules shall
be As Built Engineered Systems part numbers PS-24,APS-4 and PSM.
Technical Data
PS-24 PSM Power Supply Monitor
Input Voltage Range: 88-132 VAC Input Power: 110 VAC/60Hz
Output Voltage: 24V Output to Modules in Same Enclosure:
Output Current: 8A 24 VDC/8A/non-resettable
Working Humidity: 20-90% RH non-cond. Output Leaving Cabinet to Modules in Remote Enclosures:
APS--4 24 VDC/3.5A/non-resettable
Input Voltage Range: 88-132 VAC Rechargeable Battery Circuit:
Output Voltage: 27.6V Type: Sealed Lead Acid
Output Current:4A Voltage: 27.6
Working Humidity: 20-90% RH non-cond. Max.Amp Hour Capacity: 70
Expected Standby Op:48 Hours
Orderina Information
Part Number Data Sheet Description
PS-24 1040 8A Power Supply
AP-4 1040 4A Battery Charger
PSM 1040 Power Supply Monitor Card
Related Modules,Accessorv Cards and Cabinets
VPM/SDM 1010 VPM/SDM Configuration and Display Modules
ALM 1020 Analog SLC and NAC Circuits
Cabinets 1045 IPF-xy, IPF-XL and REM-Cabinet Options
IPF/IPF-XL 1050 IPF-xy, IPF-XL Pre-Configured Systems
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"" PSM, PS-24,APS-4 1040 1.3/5/1/2009 IPFIRfSERIES"
As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �,
1451 Concord Street Fax: (508)788-8334 �� � � ' I�
Framingham, MA 01701-7782 Contact: info asbuiltes.com
USA Visit: www.asbuiltes.com Engineered Systems
O Copyright 2008 AsBuilt Engineered Systems, Inc.