HomeMy WebLinkAboutData Sheet 1051 IPF Common Cards Data Sheet 1051 /�l � B u I �t
Engineered Systems
IP Fire SeriesTM
Common Cards �`�`��
���_���
• CCR �����.
:, ��
• M B L R ��^s �
.� ..
..
. -,.�
f.
��.
Description -
The IP Fire SeriesT"' from AsBuiltT"" Engineered Systems is a
revolutionary IP-based fire control network consisting of a series of
addressable control modules that can be distributed throughout any
type of facility.
Features
Core modules connect to other core modules to form the fire protection Common cards can be connected
system. No central processing unit is required.With no single point of • to any IP Fire SeriesT"' distributed
failure, distributed modules provide the greatest degree of building display module(VPM/SDM)
protection.Any module failure will not impact the operation or timely Common cards may be daisy
response of any of the remaining modules. �
chained up to two per networked
Both distributed network systems and pre-configured central systems module
require the capability to accommodate common control or panel level • Common Control card (CCR)
functions. provides relays for Common
Alarm, Common Trouble and
The IP Fire SeriesT"" panel-level common cards can connect to any Common Supervisory
display module located anywhere on the network. • CCR relays NO/CO/NC, rated at 2A
@30VDC Resistive Load
The Common Control Relay Card (CCR)provides for Common Alarm, • City tie Masterbox/Line Reversal
Common Trouble and Common Supervisory relays(NO/CO/NC) Card
activated by events anywhere on the fire control network.The three • Simple ribbon cable connection
relays are rated at 2.OA @30 VDC Resistive load each. • Mounts directly onto cabinet
chassis
The CCR can be mounted with any VPM or SDM installed on the • Green/RoHS Compliant
network fire system by a simple ribbon cable connection. Multiple
instances of the CCR may be installed as required on each display
module installed on the network and up to two CCR boards may be
daisy chained together off of any single network module. The CCR is
mounted directly to the system chassis within the cabinet.
The Masterbox/Line Reversal card (MBLR) is also mounted with any
display module installed on the network fire system by a simple ribbon
cable connection. If present,the MBLR may be daisy-chained directly
off of the CCR. The MBLR is mounted directly to the system chassis Listinqs
within the cabinet.
UL File: S24573
IP Fire SeriesT"" network modules will continue to operate CFSM: Pending
independently during communication loss. Since the CCR and MBLR MEA: Pending
may be installed in multiple instances and located in distributed
enclosures throughout the facility, redundant connections to outbound
signaling systems such as dialing devices, digital transmitters or other
notification systems add security to the installed system by adding
redundant paths to external reporting agencies.
Product Data Sheet Number Rev/Revision Date = _ —
IPF SeriesT"" Common Cards 1051 1.3/5/1/2009 IPFIRESERIES"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
\J =_r ;_;_; � �_,'� i_� �-� _�
=�
- --�FYRk:�-�7TQ2Ury� -
� � ��
G -
�� �-
&
�' F z ' >
�_.� �-
Di �
�
+�S
�� �l i. i..rr ��:����� i > v V �
� �r� '� P� '� ��-�,
�
CCR Common Control Relay Card (CCR) Masterbox Line Reversal Card (MBLR)
Jumper/Switch Description Jumper/Switch Description
J1 Alarm Input Wiring Location J1-J3 Line Reversal Wire Connectors(Alarm,Trouble,Supervisory)
J2 Trouble input Wiring Location J4 Municipal Box Suita6le forconn.to Masferbox coils rated down to 13JS�
J3 Supervisory Input Wiring Location JPi-JP2 MBLR Configura[ion PMS(Apply to ALARMfiROUBLE Only)
JP1 Inter-Board Connector 1(In) JP3-JP4 Inter-Board Connec[ors
JP2 Inter-Board Connector 2(Ou[) JP5 Onboard Municipal Boz Disable Pins 1-2:Enable Pins 23:Oisable
• NC-NOrmallY�losed 51 Municipal Box Disable Switch
• CO-Common D1 Municipal LED S[atus(On:Disabled,Off-Enabled)
• NO-NOrmallyOpen • �JPl-1P2:PIN51-2:OperateNOrmally
• JP1 and JP2 chain connectors allow connections[o the ALM,and[o ano[her General • PINS 2-3:Combines AL4RM and TROUBLE conditions into one circuit
Relay Board(GRB),or to a Line Reversal/Mas[erbox Board(MBLR) • No2e:when mmbined,only 11(nL4kM)Is operaEional.
Technical Data
CCR MBLR
Quiescent Power Draw: 0 mA Quiescent Power Draw: 0 mA
Alarm Power Draw: 69 mA Alarm Power Draw: 92 mA
Orderinq Information
Part Number Data Sheet Description
CCR, MBLR 1051 Optional Common Control Relay Card
Related Modules,Accessorv Cards and Cabinets
Cabinets 1045 IPF-xy, IPF-XL and REM-Cabinet Options
IPF-xy, XL 1050 IPF-xy, IPF-XL Pre-Configured Systems
VPM/SDM 1010 VPM/SDM Configuration/Display Modules
ALM 1020 Analog SLC and NAC Circuits
UXB, UXB-KS 1052 Optional USB Extension Card
KPD 1053 Optional QWERTY Keypad
Product Name Data Sheet Number Rev/Revision Date = _ —
IPF SeriesT"' Common Cards 1051 1.3/5/1/2009 IPFIRESERIES-"
As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �•:
1451 Concord Street Fax: (508)788-8334 �� � � ' I�
Framingham, MA 01701-7782 Contact: info(a�asbuiltes.com
USA Visit: www.asbuiltes.com Engineered Systems
OO Copyright 2008 AsBuilt Engineered Systems, Inc.