Description
The AsBuilt intelligent analog addressable photoelectric detector(DISC-P)
operates seamlessly with the AsBuilt IP Fire SeriesT"" network fire control.
The DISGP communicates to and is managed and controlled by the IPF —
SeriesT"" analog loop module(ALM).
The Disc-P is physically distinguished from the Discovery ionization Features
detector(DISC-I)by the clear colored dual LED's. The LED's light steady
when in an alarm condition and flash briefly when polled by the ALM. The . Improved detection capabilities with
dual LED's provide for 360 degree visibility. smoldering,smoky fires
• Discovery detectors distribute
Operation intelligence across the installed
system
The DISC-P constantly monitors its sensing chamber and its internal . Patented infrared smoke sensing
electronics utilizing a patented smoke chamber and infrared smoke design
sensing design. . Sleek, non-fading white polycarbonate
enclosure
An infrared light emitting diode with its collimator is arranged at an obtuse Zero insertion force base
angle to the photo-diode. The photo-diode has an integral daylight �
blocking filter. The IR LED emits a burst of collimated light every second. • 5 user selectable modes
In clear air the photo-diode receives no light directly from the IR LED • Powerful transient rejection algorithms
because of the angular arrangement and the chamber baffles.When . Conventional device mode
smoke enters the chamber it scatters light from the emitter IR LED onto . patented XPert programming card
the photo-diode in an amount related to the smoke characteristics and eliminates addressing errors during
density. The photo-diode signal is processed to provide an analog value
for transmission when the detector is interrogated by the ALM. system installation and maintenance
• Alarm flag sends signal to system
Upon crossing the alarm threshold the detector will make the even when device is not being
determination that an alarm condition exists and send a signal to the ALM interrogated
that interrupts the normal polling process to signal the alarm condition. • Wide variety of addressable
The ALM puts the changed state on the IP network and all outputs input/output devices
associated with the specific detector are activated. . Relay and synchronized temporal
sounderbases
The DISC-P manages its own automatic drift compensation thereby . Green/RoHS Compliant
accelerating overall system performance by offloading the management of
the device compensation values from the ALM to the DISC-P.
Compensation is made to adjust the detector for the infiltration and Listinqs
accumulation of dirt and dust over time. By compensating the detector
alarm thresholds the sensing window is adjusted to remain at original UL File: S5022
factory specifications. CSFM: 7272-1394:118
MEA: 294-95-E-4
Like all Discovery devices,the DISC-P has five pre-programmed user
settings that may be accessed and changed from the IPF Series network
control. Further, the pre-programmed settings are utilized in establishing
the automatic sensitivity values in place with the IPF Day/Night sensitivity
programming.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"" DeteCtors DISC-P 2106 1.4/10/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install, where indicated on the plans, intelligent photoelectric smoke detectors with one
of the several addressable mounting base options available.The detector base will contain the patented XPERT
programming card which will permit the free interchange of sensor heads without requiring additional programming of
the detector head or attached base.The intelligent detector shall be self compensating, self reporting and contain dual
integral LED's which will flash intermittently when polled and shall latch when the unit goes into Alarm. The detector
head shall have 5 programmable settings that can be accessed automatically or by manual setting from the fire control
which will allow the detector sensitivity settings of the individual detector to be modified as required.The combination of
the detector head and twist lock mounting base shall be UL listed and UL listed as compatible with the AsBuilt IP Fire
Series network fire controls.The detector base shall be installed without regard to wire polarity.The photoelectric
detector shall be the AsBuilt model DISC-P.
Technical Data Five Pre-Proqrammed User Sensitivitv Settinqs
Operating Voltage: 17-28VDC . Mode 1 1.7%/ft. Obscuration 5 Seconds to Alarm
Standby Current: 400uA avg./650uA peak
Alarm LED Current: 3.4mA
Remote Alarm Output: 5mA max • Mode 2 1.7%/ft. Obscuration 30 Seconds to Alarm
Temperature range: 32°F to 140°F(0°C-60°C)
Relative Humidity(non-condensing):0%-95% . Mode 3 2.3%/ft. Obscuration 5 Seconds to Alarm
Clean-air Analog Value: 23 +4/-0
Alarm Level Analog Value: 55 Mode 4 2.3%/ft. Obscuration 30 Seconds to Alarm
Wire Supply: Two-wire supply, polarity insensitive �
Recommended Spacing:
Meets the 30 ft. (9.1 m)spacing guidelines in NFPA 72 • Mode 5 2.9°/o/ft. Obscuration 5 Seconds to Alarm
Chapter 2, however,this spacing is based on ideal
conditions and should be used as a layout guide only.
Orderina Information
Part Number Data Sheet Description
DISC-P 2106 Intelligent Analog Addressable Photo Detector(model 58000-650)
DXP-6 2310 6" Low Profile Base w/Expert Card (model 45681-250)
DXP-4 2310 4" Low Profile Base w/Expert Card (model 45681-210)
DXP-RLY 2310 6" Low Profile 4-wire Relay Base (model MB-RLYT-AA)
DXP-SND/T 2310 6" Low Profile 4-wire Sounder Base(model MB-SDRT-AA)
DXP65 2310 Sync Module for Temporal Sounder Bases(model MB-SDRT-SM/G/R)
DXI 2300 Line Isolator(55000-750)
DXP-LIB 2300 Isolating Base for DXI only(45681-211)
DXP-IB 2300 Line Isolating Base for Use with XP/DISC Detectors(45681-321)
DXP-XPC Additional XPERT programming card
DXP-XPC#A Order"A"for Addresses 1-42, "B"for 43-84, "C"for 85-126,#for Loop#
DXP-126 126 Pre-Programmed XPERT cards
DXP-REM Remote LED (24V)
Related Data Sheets
Discovery Detectors: DISC-I, 2107; DISC-T, 2108; DISC-M, 2109
XP Detectors: XP-P, 2101; XP-I, 2102; XP-T, 2103;XP-M, 2104
Addressable Devices: DXP-PIM/MPIM, DXP-PID/MPID, 2810; DXP-IOM, 2812; DXP-SDR, 2814, DXP-
2PID, 2816; DXP-OCR, 2818
Addressable Base Options: All Bases,2310
Product Name Data Sheet Number Rev/Revision Date = — _