Description
A single set of IP Fire SeriesT"" addressable bases work with both the XP and
Discovery lines of intelligent detectors. Standard 4"(DXP-EZ4)and 6" (DXP-
EZ6)bases are flat and unobtrusive.4"and 6"four-wire relay bases and a 6" Features
four-wire sounder base are also available.
All AsBuilt bases for intelligent detectors utilize the patented XPERTT"" • 4" or 6" standard low-profile
programming card. The card mechanically stores the device address in the bases
base to ensure that the device address(and the custom programming in the . 4" and 6" relay bases
IPFT"" Series fire control associated with that address)cannot be moved or . Steady or Three-pulse
changed -regardless of how many time the detector head is replaced or temporal sounder bases with
maintained. high/low settings
Addressing the analog detector is easily accomplished by knocking out a • Sync modules for sounder
series of pips located on the XPERTT"' programming card. The card is then bases allow for multiple
inserted into the base.The pips now serve to configure mating switches that Configurations
are located on the bottom of the detector. When the detector head is . Zero inseYtion forCe
snapped into the base,the pips depress the switches on the detector and the . Address locked into base
address is set.Take the detector out of the base and the XPERT card Sleek, non-fading white
remains fixed in the base ensuring that any detector placed on that base will �
be set with the same address. polyCarbonate
• Sounder bases completely
Since the IPF SeriesT"" fire control maintains all data related to the address backwards compatible with
location (such as device type, custom text and control-by-event previous generations
programming)putting like-detectors in the wrong location will have no impact . Relay bases completely
on system performance. If the wrong device type is inserted in an address backwards compatible with
that previously had a different device type, the IPF system will put a trouble previous generations
on the system until the address is either restored to the original device type,
or, until the maintenance personnel change the system to accept the newly • DXP-IB isolating base accepts
installed device. any XP or DISC detectors
without the need for separate
Four wire relay and sounder bases are available to add flexibility to the line isolators—see DS 2300
system in meeting all local requirements. Relay and sounder bases require
separate 24V power supplies in accordance with NFPA.
Listinqs
When a relay(DXP-RLY)base's associated detector goes into an alarm
state, the relay will transfer and remain energized until the detector is 4" and 6" Bases:
successfully reset to the normal state. . UL File: S5022, S5053
• CSFM: 7300-1394:114
The sounder base(DXP-SND/T)offers selectable steady or temporal pattern . MEA: 294-95-E-4
outputs and selectable high or low volume levels.The three-pulse temporal Sounder Bases:
pattern is required by NFPA 72 for fire alarm evacuation for commercial and . UL File: S2829
residential applications.A series of synchronization modules(DXP65-xx)are CSFM: 7300-1004:117
available to synchronize an entire line or selective groups of sounder bases. . MEA: 73-93-E vo1.38
See DS 2300.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"' Bases/Intelligent Detectors 2310 1.4/10/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install, where indicated on the plans, either ionization, photoelectric, multisensor or
thermal sensor addressable detectors with one of the several addressable mounting base options available.
Mounting base options shall have the address mechanically located in the base to allow the free interchange of
detectors.The combination detector head and base must be UL listed and UL listed as compatible with the AsBuilt IP
Fire Series network fire controls. The detectors, bases and sync modules shall be As Built Engineered Systems part
numbers XP-P, XP-I, XP-T, XP-M, DISC-P, DISC-I, DISC-T, DISC-M, DXP-4, DXP-6, DXP-SND/T, DXP-RLY, DXP-
IB, DXI, DXP65.
Technical Data
DXP-EZ4 and DXP-EZ6: DXP-SND/T:
Alarm Current: none Quiescent Current: .03 mA
Standby current: none
Relay: none Alarm Current:
Sounder: none External Supply: 29 mA
Addressing facility: yes Detector Head: 8 mA
Captive terminals: yes
High Volume Selection: 85db @ 10 feet
Low Volume Selection: 75 db @ 10 feet
Orderinq Information
Part Number Data Sheet Description
DXP-4 2310 4"Analog Addressable Base(45681-210)
DXP-6 2310 6"Analog Addressable Base (45681-250)
DXP-RLY4 2310 4"Analog Addressable Relay Base (45681-242)
DXP-RLY 2310 4"Analog Addressable Relay Base(MB-RLYT-AA)
DXP-SND/T 2310 6"Analog Addressable Temporal Sounder Base(MB-SDRT-AA)
DXP65 2310 Sync Module—Temporal Sounder Bases(MB-SDRT-SM/G/R))
Related Modules
DXP-IB 2300 Isolating Base/Accepts any XP/Discovery Detector(45681-321)
DXI 2300 Line Isolator(55000-750)
DXP-LIB 2300 Base for DXI only(45681-211)
XP Detectors 2100-2104 XP Range of Detectors
DISC Detectors 2105-2109 Discovery Range of Detectors
Related Data Sheets
Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109
XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103; XP-M, 2104
Addressable Loop Devices: 2810-2818
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"" Bases/Intelli ent Detectors 2310 1.4/ 10/1/2009 IPFIRfSERIES"