Loading...
HomeMy WebLinkAboutData Sheet 2401 DXP-AD2 Addressable Duct Detectors Data Sheet 2401 /�l � B u I �t Engineered Systems Two-Wire Addressable Duct Detectors • DXP-AD2 ` , : , __,�:- � � �f, _ Description - -- DXP-AD2 Series Smoke Duct Detector is the latest analog addressable innovation for early detection of smoke and products of combustion present in air moving through HVAC ducts in Commercial, Industrial, and Residential applications. The unit is designed to prevent the recirculation or spread of smoke by air handling systems,fans, and blowers. Complete systems may be shut down via the AsBuilt IPF SeriesT"" fire control panel in the event of smoke detection. Features The DXP-AD2 connects to the SLC loop monitored and controlled . Listed for velocities between 100- by the AsBuilt ALM module.The DXP-AD2 is addressed through 4000 ft./min the use of the patented XPERTT"" programming card. The ALM . Listed for high-temperature monitors the SLC for faults and troubles and reports the DXP-AD2 applications status to the IPF fire control unit.When an alarm condition is . Patent pending "No-Tools reported to the IPF system by the DXP-AD2, pre-programmed Required"front or rear loading output events energize DXP-OCM output control modules and removing sampling/exhaust associated with the specific DXP-AD2 to take control of required tubes building functions. . Patent pending "Test Port Valve" The DXP-AD2 is designed and built to meet all local code allows for aerosol smoke testing without cover removal requirements, as well as the NFPA and ICC standards regarding Clear cover fitted with four captive HVAC supply and return duct smoke detectors. Output terminals • °'No-Tools Required" are provided for a remote alarm indicator accessory. thumbscrews The DXP-AD2 includes many features that represent true • Instantaneous cover removal innovations from current generation duct smoke detectors. trouble indication • Vertical terminal block for easier The DXP-AD2 is shipped complete with a 7"exhaust tube, wiring sampling tube end cap, a mounting template and mounting • External mounting tabs do not hardware. require cover removal to install • Duct wall gaskets on back of The DXP-AD2 has a number of accessory products including the enclosure are pre-installed MSR-50 and MSR-100 remote indicator/controls, a weatherproof • Large terminal connection screws enclosure and TG-2000 test gas. • Compatible with the WP-2000 weatherproof enclosure • Models: Photo DXP-AD2-P(Model SL-DAA-P) lon DXP-AD2-I (Model SL-DAA-N) • Sampling Tubes: STN:-1.0 12"or less STN:-2.5 6"to 2.5' Listinqs STN:-5.0 2.5'to 5" STN:-10.0 5.0'to 10' UL File: S2829 • Air Velocity: 100-4000'/min. CSFM: 3240-1004:115 • Humidity:10-95% RH Non-Condensing/Non-Freezing MEA Accepted: 73-92-E Vol.35 • Wiring: Solid or Stranded#12 to#22 AWG terminals • Dimensions: 13.5 L x 4.5 W x2.25 H • Max. Net Weight: 2 Ibs. Product Data Sheet Rev/Revision Date = _ _ Number — — IP FIRE SERIES-" Two Wire Addressable Duct Detectors 2401 1.3/5/1/2009 O Copyright 2008 AsBuilt Engineered Systems, Inc. Enqineer Specification The contractor shall furnish and install, where indicated on the plans, ionization or photoelectric type duct detectors for the control of air handling units by the Fire Alarm control.The addressable analog duct detector will contain the patented XPERT programming card for ease of addressing.The addressable analog doctor shall also be capable of handling air velocities of 100 to 4000 feet per second,the detector head shall contain no additional screens or filters, a method of smoke testing the detector without removing the duct detector cover must be provided, cover and sampling tube or installation shall not require the use of tubes and sampling tubes must be capable of installation or removal from the front and rear of the detector for inspection and testing. The addressable analog duct detector shall be UL listed and UL listed as compatible with the AsBuilt IP Fire Series network fire controls. The analog addressable duct detector shall be the AsBuilt model DXP-AD2-P (photo)and DXP-AD2-I (ion). Wirinq Detail Terminal Connections Remote Accessorv Wirinq 6 -R Remote Alarm Accessory 5 +R 4 L2 - FACP SLC{Laap}- � r� BLACK 3 �� '�_re': - - • - RER �_'_:....• ALARAt � j 2 L� LED ._.. FACP SI�C{Loop}+ �;R`� 'E L1 � a.,i , RFn Orderinq Information Part Number Data Sheet Description DXP-AD2-P 2401 Two Wire Photo Analog Addressable Duct Detector(SL-DAA-P) DXP-AD2-I 2401 Two-Wire lon Analog Addressable Duct Detector(SL-DAA-N) Related Modules DXP-AD4R-P 2402 Four-Wire Photo Analog Addressable Duct Detector(SL-DA4R-P) DXP-AD4R-I 2402 Four-Wire lon Analog Addressable Duct Detector(SL-DA4R-N) MSR-50 2410 MS-50 Advanced Remote Accessories MSR-100 2412 MS-50 Advanced Remote Accessories Accessories 2416 MS Remote Accessories WP2000 Weatherproof Enclosure TG2000 Test Gas Related Data Sheets IP Fire SeriesT"" Intelligent Fire Controls: 1000-1055 Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109 XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103;XP-M, 2104 Addressable Base Options: All Bases,2310 Product Name Data Sheet Number Rev/Revision Date = _ _ Two Wire Addressable Duct Detectors 2401 1.3/5/1/2009 IPFIRfSERIES" As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �, 1451 Concord Street Fax: (508)788-8334 �� � � ' I� Framingham, MA 01701-7782 Contact: info asbuiltes.com USA Visit: www.asbuiltes.com Engineered Systems O Copyright 2008 AsBuilt Engineered Systems, Inc.