HomeMy WebLinkAboutData Sheet 2812 IPF Series Addressable Input Output Module Data Sheet 2812 /�l � B u I �t
Engineered Systems
IP Fire SeriesTM
Input Output Module - �
• DXP-IOM • • ��- °- -
Description � :.
�, -
The IP Fire SeriesT"^ control system provides for Analog Loop Modules �°�-�� '` •�
. ..�„-..,.-,� . � r�
(ALM's)that may be installed throughout a protected facility in any number �
up to the IPF system maximum of 50 modules. IPF SeriesT"" ALM modules • • ..
offer analog addressable signaling line(SLC)circuits that may each have _ _ �� .�
up to 126 detectors or 126 addressable control devices in any - --
combination.
The AsBuilt addressable Input Output Module (DXP-IOM)provides for two
different types of input and one relay output all on single addressable
module yet consumes only one device address. Features
The DXP-IOM is a loop powered device that incorporates: . Opto-coupled, open collector
type input monitors 12VDC or
1. a supervised input circuit for switch monitoring, or, 24VDC circuits for activation
2. a non-supervised opto-coupled input(open collector)for the SeCOnd, supervised input type
monitoring of 12 or 24VDC input voltages, and, �
3. a volt-free relay output monitors standard dry contact
devices, Class A or B
The DXP-IOM connects to the SLC and is programmed via an 8 pin DIL • Volt-free relay output on same
switch (1-7 for addressing, 8 for Class A/B).There are no limitations on device
the number of DXP-IOM's that may be added to a single SLC loop(up to . Inputs and outputs opeYate
the SLC maximum of 126 device/detector types). independently and are tied to
The supervised inputs are designed to monitor the state of one or more other devices on the IPF
single-pole, volt-free contacts connected on a single pair of cables and system programmatically
may be wired in either a Class A or B (Style D or B)fashion. • Plate mounted for
surface/flush mounting in 4"
The non-supervised opto-coupled open collector input circuit can be used square boxes
to monitor for the activation of any 12 or 24VDC circuit. Supervision is not . Fully supervised
required if the connection length is less than 3 feet. . Field programmable
Regardless of which type of input is selected, activation will cause an input • LED for polling/alarm
event to be generated on the IPF Series control via the SLC connected to annunciation
the ALM. • DIL switch addressing
• Green/RoHS Compliant
The volt-free relay is fired programmatically through the IPF control
system and NOT automatically(by simple activation of the input-unless
programmed to do).The relay portion of the DXP-IOM may be activated
by any other input device on the system independent of the status of the
two input circuits located on the same card.This allows the DXP-IOM to
truly function as two distinct addressable controls while only occupying a Listinas
single SLC address point in a cost effective application.
UL File: S7003
The open connector input is non-supervised with a 30VDC maximum CSFM: 7300-1394:108
current. MEA: 294-95-E-4
The relay output is a non-supervised, programmable, dry contact with
current ratings of 24VDC. 1A:30 VAC .5A(resistive).
These devices all use end of line monitoring resistance of 47k'S�.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"^ Input Output Module 2812 1.3/5/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install,where indicated on the plans, addressable interface devices for the
monitoring and supervision of contact type devices connected to the Fire Alarm control. The devices shall monitor a
normally open dry contact. The contractor shall also furnish and install,where indicated on the plans, addressable
interface devices to be used in monitoring any 12VDC or 24VDC circuit whose status/activation is being monitored by
the Fire Alarm control. Further,the contractor shall furnish and install, where indicated on the plans, addressable
interface devices to be used to drop or activate power to systems being controlled by the Fire Alarm control (e.g..
elevator recall, door closure)by means of switching a relay. The addressable interface devices shall communicate to
the main fire control via the analog addressable circuit.The addressable interface device must be UL listed and UL
listed as compatible with the AsBuilt IP Fire Series network fire control.The addressable interFace device shall be As
Built Engineered Systems part numbers DXP-IOM.
Technical Data
Supervised Switch Monitor Input:
DXP-IOM: Normally open switch generates alarm on
Dimensions:4 '/2"W x 4'/z'H x 1 3/4"D closure.
Weight: 3 oz Contact Resistance: 5kS2 @ 200�A
LED visible through fascia plate label
Current Consumption: 600 �A typically Opto-Coupled Open Collector Input:
LED on:4 mA Low: <1.5VDC, High:>10VDC(30VDC max)
Relay on:4mA pulsed for 80ms OFF<1VDC; ON>10 VDC;
Switch on surge current: 3.5mA for 2s Voltages between 1.5 and 10VDC Indeterminate
Operating Temp: -4°F to 158°F
Humidity: 0%to 95% (no condensation or icing) Volt-Free Relay Output:
Shock: To UL 864 UL De-rated Contact: 2A@30VDC,
Vibration:To UL 864 .6A@120VAC
Orderinq Information
Part Number Data Sheet Description
DXP-IOM 2812 Input/Output Monitor(55000-820)
Related Modules
DXP-SDR 2814 Sounder Control Module (55000-825)
DXP-2PID 2816 Dual Priority Input Device(55000-790)
DXP-OCM 2818 Output Control Module(55000-863)
DXP-PIM 2810 Point Identification Module (55000-805)
DXP-MPIM 2810 Mini Point Identification Module (55000-831)
DXP-PID 2810 Priority Input Device (55000-806)
DXP-MPID 2810 Mini Priority Input Device(55000-830)
Related Data Sheets
Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109
XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103; XP-M, 2104
Addressable Base Options: All Bases,2310
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"^ Input Output Module 2812 1.3/5/1/2009 IPFIRfSERIES"