Loading...
HomeMy WebLinkAboutData Sheet 2814 IPF Series Sounder Control Module Data Sheet 2814 /�l � B u I �t Engineered Systems IP Fire SeriesTM Sounder Control Module ����- �� � • DXP-SDR �_ �.-�� � �� Description �,�,. � � :�r�-� t� --- - The IP Fire SeriesT"" control system provides for Analog Loop Modules - (ALM's)that may be installed throughout a protected facility in any =�� number up to the IPF system maximum of 50 modules. IPF SeriesT"^ _ ___ ALM modules offer analog addressable signaling line(SLC)circuits that may each have up to 126 detectors or 126 addressable control devices in any combination. AsBuilt Sounder Control Modules(DXP-SDR)are addressable devices Features that provide a means to remotely locate a fully supervised circuit for the operation of signal appliance such as horns, strobes and horn/strobes. • Supervises and operates The DXP-SDR can also monitor and control PA speaker circuits from the addressable notification main IPF SeriesT"" system via the SLC. appliance circuit • Supervises DC power in DXP-SDR Sounder Control Modules connect to the SLC, are . Class A or B NAC CirCUit programmed via an 8 pin DIL switch (1-7 for addressing, 8 for Class Group addressing for DXP- A/B)and are polarity insensitive. � SDR/NAC synchronization The DXP-SDR notification appliance circuits are rated for 2A.A separate • LED annunCiates aCtivation external 24V power supply must be used. The external supply must be • Fully supervised power limited per NFPA. . PA Speaker Circuit (35-70V) In standby mode,the DXP-SDR monitors its internal circuitry for status • Plate mounted versions of the device itself and supervises the NAC or speaker circuits for faults. available for surface/flush In the event a fault is detected, the DXP-SDR will report a trouble to the mounting in 4" square boxes IPF SeriesT"' fire control. • LED for polling/alarm annunciation The DXP-SDR module incorporates a synchronization facility which . DIL switch addressing allows the outputs of groups of modules to be synchronized by . Green/RoHS Compliant commands from the IP Fire SeriesT"' control panel. Multiple DXP-SDR devices may be programmed to multiple Group Addresses through the Group Addressing switch (S2). When used as a PA speaker circuit a separate audio amplifier is required (35-70V). The audio amplifier must have wire supervision capability as per NFPA. Terminal Block Assignments Terminals are suitable for 14-26 AWG cables. Listinqs TB1 L1 —Loop In/Out UL File: S7003 L2—Loop In/Out CSFM: 7300-1394:108 L1 and L2 are non-polarized MEA: 294-95-E-4 T63 External Supply+ve and—ve Input and Output TB2 Class A or B NAC circuit These devices all use end of line monitoring resistance of 47k'S2. Product Data Sheet Number Rev/Revision Date = _ IPF SeriesT"' Sounder Control Module 2814 1.3/5/1/2009 IPFIRESERIES'" OO Copyright 2008 AsBuilt Engineered Systems, Inc. Enqineer Specification The contractor shall furnish and install,where indicated on the plans, addressable interface devices for the monitoring, supervision and control of addressable NAC circuits or PA speaker circuits connected to the Fire Alarm control. The devices shall monitor and activate/deactivate NAC appliances or Speakers.When used to monitor/control NAC appliance circuits the addressable device must be capable of synchronizing with other similar devices attached to the same SLC.The addressable interface devices shall communicate to the main fire control via the analog addressable circuit.The addressable interFace device must be UL listed and UL listed as compatible with the AsBuilt IP Fire Series network fire controls.The addressable interface device shall be As Built Engineered Systems part numbers DXP-SDR. Technical Data Sounder: Relay output is 4PC0, UL de-rated contact 2A @ Sounder Control Module: 30VDC, .6A @ 125VAC Dimensions:4 '/2"W x 4'/z'H x 1 3/4"D Opto-isolated input for external 24V power supply Weight: 3 oz EOL monitoring resistance 47kf2 LED visible through fascia plate label Current Consumption: PA Speaker Supply: Normal Operation/Sounder drive active): 1 mA typically Opto-isolated input for 35V-70V Audio input. Relay Activated:4mA typically pulsed for 150ms (To avoid fault conditions when using in PA Power up surge: 6mA max for 150ms mode, move jumper J1 to 'PA' mode to disable LED on:4 mA supply monitoring Operating Temp: -4°F to 158°F Humidity: 0%to 95% (no condensation or icing) Synchronization: Shock: To UL 864 Switch S2 sets the`Group Address'to Vibration:To UL 864 synchronize multiple Sounder modules on the same SLC Orderinq Information Part Number Data Sheet Description DXP-SDR 2814 Sounder Control Module (55000-825) Related Modules DXP-IOM 2812 Input/Output Monitor(55000-820) DXP-2PID 2816 Dual Priority Input Device(55000-790) DXP-OCM 2818 Output Control Module(55000-863) DXP-PIM 2810 Point Identification Module (55000-805) DXP-MPIM 2810 Mini Point Identification Module (55000-831) DXP-PID 2810 Priority Input Device (55000-806) DXP-MPID 2810 Mini Priority Input Device(55000-830) Related Data Sheets Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109 XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103; XP-M, 2104 Addressable Base Options: All Bases,2310 Product Name Data Sheet Number Rev/Revision Date = _ _ IPF SeriesT"" Sounder Control Module 2814 1.3/5/1/2009 IPFIRfSERIES" As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �, 1451 Concord Street Fax: (508)788-8334 �� � � ' I� Framingham, MA 01701-7782 Contact: info asbuiltes.com USA Visit: www.asbuiltes.com Engineered Systems O Copyright 2008 AsBuilt Engineered Systems, Inc.