HomeMy WebLinkAboutData Sheet 2816 IPF Series Dual Input Device Data Sheet 2816 /�l � B u I �t
Engineered Systems
IP Fire SeriesT"'
Dual Point Identification � �
Device �: � °. � �
��� �� :��, �
` �� �
.
• DXP-2 P I D a; �; . � :��
�___ _ . � .� _ ,:� `
T:
Description '� �
-.,z.�-,_ _.
The IP Fire SeriesT"" control system provides for Analog Loop Modules
(ALM's)that may be installed throughout a protected facility in any
number up to the IPF system maximum of 50 modules. IPF SeriesT"'
ALM modules offer analog addressable signaling line(SLC)circuits that Features
may each have up to 126 detectors or 126 addressable control devices
in any combination. • Dual Class A/B Input Circuits
on a single address
The AsBuilt Dual Priority Input Device(DXP-2PID)is an addressable . Monitors dry ContaCt devices
dual switch monitor that is a means of connecting and identifying two • priority interrupt feature for
conventional monitor point circuits at the main IPF SeriesT"' system. fast response
DXP-2PID switch monitors connect to the SLC, are programmed via an
8 pin DIL switch (1-7 for addressing, 8 for Class A/B), are polarity • Dual LED's visible through the
insensitive and are used to monitor one or two Class A or B (Style D or fascia plate label
B)circuits. • Field programmable
• Fully supervised
The DXP-2PID are designed to monitor the state of one or more single- . Plate mounted for
pole,volt-free contacts connected on a single pair of cables on two surface/flush mounting in 4"
separate circuits. square boxes
AsBuilt DXP-2PID switch monitors are available for surface/flush • LED for polling/alarm
mounting in 4"square boxes. annunCiation
• DIL switch addressing
In standby mode,the DXP-2PID monitors its internal circuitry for status . Green/RoHS Compliant
of the device itself and supervises both input circuits for faults. In the
event a fault is detected,the DXP-2PID will report a trouble to the IPF
SeriesT"" fire control.
The DXP-2PID incorporates the priority interrupt feature on each of its
two available circuits. Priority interrupt is used where a fast response is
required (as with pull stations). Priority input devices produce output
states of normal, off-normal and alarm.These devices do not produce
pre-alarm output states.
Terminal Block Assignments Listinqs
TB1 L1 —Loop In/Out UL File: S7003
TB5 L2—Loop In/Out
L1 and L2 non-polarized
TB3 Switch Monitor Circuit Class A or B
These devices all use end of line monitoring resistance of 47k'f2.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"' Dual PID 2816 1.3/5/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install,where indicated on the plans, addressable interface devices for the
monitoring and supervision of contact type devices connected to the Fire Alarm control.The devices shall monitor
one or two normally open dry contact circuits.The addressable interface devices shall communicate to the main fire
control via the analog addressable circuit. The addressable interface device must be UL listed and UL listed as
compatible with the AsBuilt IP Fire Series network fire controls. The addressable interface device shall be As Built
Engineered Systems part numbers DXP-2PID.
Technical Data
Dual Priority Input Device: �imensions:
Current Consumption: 600 NA typically Dimensions:4'/z"W x 4 '/z"H x 1 '/4"D
LED on:4 mA Weight: 3 oz
Operating Temp: -4°F to 158°F LED visible through fascia plate label
Humidity: 0%to 95% (no condensation or icing)
Shock: To UL 864
Vibration:To UL 864
Orderinq Information
Part Number Data Sheet Description
DXP-2PID 2816 Dual Priority Input Device(55000-790)
Related Modules
DXP-SDR 2814 Sounder Control Module (55000-825)
DXP-IOM 2812 Input/Output Monitor(55000-820)
DXP-OCM 2818 Output Control Module(55000-863)
DXP-PIM 2810 Point Identification Module (55000-805)
DXP-MPIM 2810 Mini Point Identification Module (55000-831)
DXP-PID 2810 Priority Input Device (55000-806)
DXP-MPID 2810 Mini Priority Input Device(55000-830)
Related Data Sheets
Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109
XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103;XP-M, 2104
Addressable Base Options: All Bases,2310
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"" Dual PID 2816 1.3/5/1/2009 IPFIRfSERIES"
As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �,
1451 Concord Street Fax: (508)788-8334 �� � � ' I�
Framingham, MA 01701-7782 Contact: info asbuiltes.com
USA Visit: www.asbuiltes.com Engineered Systems
O Copyright 2008 AsBuilt Engineered Systems, Inc.