HomeMy WebLinkAboutData Sheet 2818 IPF Series Output Control Module Data Sheet 2818 /�l � B u I �t
Engineered Systems
IP Fire SeriesTM
Output Control Module - ��
,�, .�,:��_ .
�
• DXP-OC M ��
� ��
M..�..u... _ .
, �
�� --__ . :
_
Description Features
The IP Fire SeriesT"^ control system provides for Analog Loop . Form C dry relay contacts
Modules(ALM's)that may be installed throughout a protected Automatically controls
facility in any number up to the IPF system maximum of 50 �
modules. IPF SeriesT"^ ALM modules offer analog addressable building functions
signaling line (SLC)circuits that may each have up to 126 • Fully supervised
detectors or 126 addressable control devices in any combination. . Field programmable
• Plate mounted for
The AsBuilt output control monitor(DXP-OCM) is an addressable surFace/flush mounting in 4"
device that is a means of connecting to and controlling building square boxes
functions such as electromagnetic door holders, dampers, motors, LED for polling/alarm
elevators and disconnects from the main IPF SeriesT"^ system. �
annunciation
The DXP-OCM connects to the SLC, is programmed via a 7 pin • DIL switch addressing
DIL switch and is polarity insensitive. • Green/RoHS Compliant
Single or multiple initiating points on the IPF SeriesT"' fire control
are assigned to specific DXP-OCM modules that may be
connected anywhere on the SLC. When an event is generated by
an initiating device,the pre-programmed assignment
automatically fires the Form C dry contacts located on the DXP-
OCM effecting a change in status to the attached building control
device(s).
In standby mode, the DXP-OCM monitors its internal circuitry for
status of the device itself and supervises the external control
circuit for faults. In the event a fault is detected, the DXP-OCM will
report a trouble to the IPF SeriesT"' fire control.
When tied to specific smoke detectors, switch monitors and other
initiating devices,the DXP-OCM allows the IPF SeriesT"^ fire Listinqs
control to exercise significant automatic control over all building
functions in accordance with local building requirements. UL File: S7003
The DXP-OCM is plate mounted on a 4'/4 x 4'/4 plastic plate for
surface or flush mounting on 4"square boxes.The DXP-OCM is
fully supervised,field programmable and has an integral LED that
is visible through the front plate.The LED flashes on device poll
to show that it is active.The red LED latches ON upon activation.
Product Data Sheet Number Rev/Revision Date = _
IPF SeriesT"' Output Control Module 2818 1.3/5/1/2009 IPFIRESERIES'"
OO Copyright 2008 AsBuilt Engineered Systems, Inc.
Enqineer Specification
The contractor shall furnish and install,where indicated on the plans, addressable interface devices for the
monitoring, supervision and control of programmable relays connected to the Fire Alarm control. The devices shall
act as an interface between the Fire Alarm control and building functions such as electromagnetic door holders,
dampers, motors, elevators and disconnects and give the Fire Alarm the ability to change the state of the attached
building control functions during an emergency condition . The addressable interface device shall communicate to the
main fire control via the analog addressable circuit.The addressable interface device must be UL listed and UL listed
as compatible with the AsBuilt IP Fire Series network fire controls. The addressable interface device shall be As Built
Engineered Systems part numbers DXP-OCM.
Technical Data
All DeviCes: Dimensions:
Current Consumption: 600 NA typically Dimensions:4'/z"W x 4 '/z"H x 1"D
LED on:4 mA Weight: 3 oz
Operating Temp: -4°F to 158°F LED visible through fascia plate label
Humidity: 0%to 95% (no condensation or icing)
Shock: To UL 864
Vibration:To UL 864
Orderinq Information
Part Number Data Sheet Description
DXP-OCM 2818 Output Control Module(55000-863)
Related Modules
DXP-PIM 2810 Point Identification Module (55000-805)
DXP-MPIM 2810 Mini Point Identification Module (55000-831)
DXP-PID 2810 Priority Input Device (55000-806)
DXP-MPID 2810 Mini Priority Input Device(55000-830)
DXP-IOM 2812 Input/Output Monitor(55000-820)
DXP-SDR 2814 Sounder(55000-825)
DXP-2PID 2816 Dual Priority Input Device(55000-790)
DXP-OCM 2818 Output Control Module(55000-863)
Related Data Sheets
Discovery Detectors: DISC-P, 2106; DISC-I, 2107; DISC-T, 2108; DISC-M, 2109
XP Detectors: XP-P, 2101;XP-I, 2102;XP-T, 2103;XP-M, 2104
Addressable Base Options: All Bases,2310
Product Name Data Sheet Number Rev/Revision Date = _ _
IPF SeriesT"^ Output Control Module 2818 1.3/5/1/2009 IPFIRfSERIES"
As Built Engineered Systems, Inc. Phone: (508)788-8333 ■ �,
1451 Concord Street Fax: (508)788-8334 �� � � ' I�
Framingham, MA 01701-7782 Contact: info asbuiltes.com
USA Visit: www.asbuiltes.com Engineered Systems
O Copyright 2008 AsBuilt Engineered Systems, Inc.